5.3 REMOVING UPS MODULE FROM RPR-2 DEVICE
In certain cases where the UPS needs to be replaced due to a
warranty repair, the UPS will need to be removed.
1. Locate the UPS module on the lower base of the RPR-2.
2. Remove the UPS retaining bracket hardware (x4), and store the
UPS retaining bracket for reassembly. (Figure 5.4)
3. Disconnect the 120V power supply from the UPS Module
(Figure 5.5) and carefully slide the UPS module forward to
remove it from the UPS sleeve. (Figure 5.6)
Figurt 5.4. RtmNving UPS Rtoaining Brackto (x4)
Figurt 5.5. DiscNnntcoing 120V PNwtr Supply FrNm UPS MNdult
Figurt 5.8. Unpluging UPS MNdult
Figurt 5.6. RtmNving UPS MNdult FrNm RPR-2 Dtvict
Figurt 5.9. RtmNving UPS Baootry CNvtr Plaot Hardwart (x1)
Figurt 5.7. RtmNving UPS MNdult FrNno CNvtr
5.4 REPLACEMENT OF THE UPS MODULE BATTERIES
Once the UPS module has been removed from the RPR-2 device,
the UPS module batteries can be replaced.
Note:
N
All ohrtt baootrits shNuld bt rtplactd ao oht samt oimt.
1. Remove the front cover of the UPS module by pulling the left
two corners away from the unit. (Figure 5.7)
2. Disconnect the battery by pulling apart the battery terminals.
(Figure 5.8)