Static Uninterruptible Power Supply

 

Page 8 of 8 

Eaton 9390 Guide Specification 

October 9, 2009 

 

 

 

shall be designed for remote installation using customer-supplied wiring and conduit, and 
shall be capable of free-standing or wall-mounted installation. 

 

 

2.05 

UNINTERRUPTIBLE POWER SUPPLY RATINGS AND OPERATING CHARACTERISTICS 

 

A. 

UPS Continuous Ratings.  The UPS shall be rated: 

UPS Rating (max) 

Optional Rating (1) 

Optional Rating (2)   Optional Rating (3)  

40kVA/36kW 

30kVA/27kW 

20kVA/18kW 

n/a 

80kVA/72kW 

60kVA/54kW 

50kVA/45kW 

40kVA/36kW 

120kVA/108kW 

100kVA/90kW 

n/a 

n/a 

160kVA/144kW 

120kVA/108kW 

100kVA/90kW 

n/a 

 

UPS Rating (max) is the maximum output possible from the UPS (for a load 
power factor range of 0.9 lagging to 0.9 leading). The UPS shall not require de-
rating when supporting a leading power factor load of 0.9 or greater. The UPS 
may be ordered with any of the three (3) optional ratings (where available) and 
later upgraded to its corresponding full UPS Rating (max).  

 

B. 

Rectifier/charger input: 

1. 

Nominal three phase input voltage: 208 (or 480) VAC: 

3-wire plus ground for 3-wire plus ground output configuration 

2. 

Operating input voltage range: +10%, -15% of average nominal input voltage 
without battery discharge. 

3. 

For 60Hz systems, operating input frequency range shall be 55 to 65Hz. 

4. 

Input power factor 0.99 lagging.  

5. 

Normal input current limit:  The UPS shall have the following programmable input 
current limit settings while operating in normal mode: 

a) 

Rectifier/charger input current limit shall be adjustable from 100 to 115% 
of full-load input current. 

b) 

Battery input current limit shall be adjustable from 10% to 15% of the 
UPS full load input current regardless of the actual load on the UPS. 

6. 

On generator input current limit:  The UPS shall have the following programmable 
input current limit settings while operating in normal mode on generator: 

a) 

Rectifier/charger input current limit shall be adjustable from 100% to 
115% of full-load input current. 

b) 

Battery recharge input current limit shall be adjustable from 10% to 15% 
of the UPS full load input current regardless of the actual load on the 
UPS. 

7. 

Input current total harmonic distortion (THD) shall be less than 4.5%. 

8. 

Power walk-in:  Ramp-up to full utility load adjustable from 3 seconds to 60 
seconds. 

 

C. 

Bypass input: 

Содержание Powerware 9390

Страница 1: ...UPS Module shall operate as an on line fully automatic system in the following modes 1 Normal Utilizing commercial AC power the critical load shall be continuously supplied by the Inverter The Invert...

Страница 2: ...EC 62040 1 1 International Electrotechnical Commission Uninterruptible power systems UPS Part 1 1 General and safety requirements for UPS used in operator access areas E IEC 62040 1 2 International El...

Страница 3: ...f all field service offices must be submitted with the proposal Third party maintenance will not be accepted E Spare Parts Support Parts supplies shall be located in the field to provide 80 of all eme...

Страница 4: ...nts the IGBTs from sourcing current in excess of their published ratings 3 An option shall be provided to allow the rectifier to be capable of operating from a delta transformer output or high impedan...

Страница 5: ...onditions a Bypass voltage out of limits 10 of nominal b Bypass frequency out of limits 3 Hz adjustable factory set c Bypass out of synchronization d Bypass phase rotation installation error 6 Static...

Страница 6: ...ocations 1 Rectifier charger input connections 3 wire plus ground 2 Bypass input connections 3 wire plus ground for 3 wire plus ground output configuration 480Vac or 4 wire plus ground for 4 wire plus...

Страница 7: ...ll be removable from the front of the battery cabinet 4 Each battery cabinet shall feature a DC rated circuit breaker The circuit breaker within the battery cabinet shall only provide protection to th...

Страница 8: ...VAC 3 wire plus ground for 3 wire plus ground output configuration 2 Operating input voltage range 10 15 of average nominal input voltage without battery discharge 3 For 60Hz systems operating input f...

Страница 9: ...6 DC sensing Redundant DC voltage sensing methods shall be incorporated for providing battery over voltage protection 7 Battery charger characteristics The UPS battery charging system shall have the...

Страница 10: ...le 11 Phase angle control a Balanced linear load shall be 1 degree from nominal 120 degrees b Unbalanced linear loads shall less than 5 degrees from average phase voltage for 100 load unbalance 12 Pha...

Страница 11: ...e UPS shall withstand a 25 kV pulse without damage and with no disturbance or adverse effect to the critical load 11 Efficiency The UPS efficiency shall greater than 99 over the range of 10 to 100 loa...

Страница 12: ...cessor controlled circuitry The UPS controls shall have the following design and operating characteristics 1 Fully automatic operation of the UPS shall be provided through the use of microprocessor co...

Страница 13: ...tive cover which provides the following signals and communication features in a Class 2 environment 1 Alarm contact A dry contact for annunciating a summary alarm shall be provided for customer use Th...

Страница 14: ...attended sequential shutdown of one or multiple computers powered by one UPS This shutdown shall be performed via in network or out of network means The order of shutdown shall be user defined allowin...

Страница 15: ...ation operator training generator testing etc B The following procedures and tests shall be performed by Field Service personnel during the UPS startup 1 Visual Inspection a Visually inspect all equip...

Страница 16: ...g service with monthly reports for UPS and battery performance Standard response time shall be 8 hours from receipt of call Manufacturer shall also offer as an option 7x24 on site service support with...

Отзывы: