background image

Static Uninterruptible Power Supply

 

Page 14 of 14 

Eaton 9390 Guide Specification 

October 9, 2009 

 

 

 

A. 

Communications Bay:  The UPS shall be equipped with field configurable 
communications bays that will accommodate four (4) communication devices  

B. 

Remote Monitoring: 

1. 

Optional WEB/SNMP communication capabilities will be available for all 
systems.  

2. 

The UPS shall be able to be monitored remotely via communications devices.  
UPS manufacturer shall provide optional communications devices capable of 
communicating via various industry standard protocols such as RS232 and 
ModBus.  Monitoring of UPS status may also be performed through isolated dry 
contact Form C relays.   

3. 

Remote monitoring of the UPS shall also be possible through status indicators 
elsewhere in the same facility through a device that replicates these indicators.  

The UPS communication capability should be able to integrate into any industry standard 
Building Management System (BMS) and/or Network Management System (NMS). The 
UPS must also be able to be monitored via any standard Internet browser (i.e. Internet 
Explorer and Netscape).

 

All optional hardware interfaces shall be “Hot-swappable” (UPS maintains power to 
critical applications while changing interfaces).  

C. 

Shutdown: 

1. 

There shall be a mechanism that provides graceful, orderly, unattended, 
sequential shutdown of one or multiple computers powered by one UPS.  This 
shutdown shall be performed via in-network or out-of-network means.  The order 
of shutdown shall be user-defined, allowing the maximization of runtime on 
battery for more critical systems.  

2. 

Shutdown of AS/400 computers shall be possible through open-collector relay 
contacts or isolated, dry contact, Form-C relays. 

3. 

The UPS shall also be capable of interfacing with an operating system’s built-in 
shutdown routine, e.g. Windows NT.  This shall be done through a cable 
connection to the optional serial port on the UPS.  

D. 

Notification: 

1. 

There shall be a mechanism to send alerts to key personnel via email or SNMP 
traps.  An alarm notification may also be sent by a network message.  

2. 

Dial-out to a computer for alarm notification may be performed.  The user may 
respond by dialing-in to retrieve alarm history and a summary of current meter 
status. 

3. 

Management:  A remote battery test may be performed via an Ethernet network. 
The UPS shall be tested through invoking a single command. 

 

 
2.08 

UPS MODULE PROTECTION 

 

A. 

Rectifier/Charger and Bypass protection shall be provided through individual fusing of 
each phase. 

B. 

Battery protection shall be provided by thermal-magnetic molded-case circuit breakers in 
each battery cabinet (if standard battery pack is provided) or external protective device 
for an external battery. 

C. 

Electronic current limiting circuitry and fuses in the Inverter circuit shall provide output 
protection.  

Содержание Powerware 9390

Страница 1: ...UPS Module shall operate as an on line fully automatic system in the following modes 1 Normal Utilizing commercial AC power the critical load shall be continuously supplied by the Inverter The Invert...

Страница 2: ...EC 62040 1 1 International Electrotechnical Commission Uninterruptible power systems UPS Part 1 1 General and safety requirements for UPS used in operator access areas E IEC 62040 1 2 International El...

Страница 3: ...f all field service offices must be submitted with the proposal Third party maintenance will not be accepted E Spare Parts Support Parts supplies shall be located in the field to provide 80 of all eme...

Страница 4: ...nts the IGBTs from sourcing current in excess of their published ratings 3 An option shall be provided to allow the rectifier to be capable of operating from a delta transformer output or high impedan...

Страница 5: ...onditions a Bypass voltage out of limits 10 of nominal b Bypass frequency out of limits 3 Hz adjustable factory set c Bypass out of synchronization d Bypass phase rotation installation error 6 Static...

Страница 6: ...ocations 1 Rectifier charger input connections 3 wire plus ground 2 Bypass input connections 3 wire plus ground for 3 wire plus ground output configuration 480Vac or 4 wire plus ground for 4 wire plus...

Страница 7: ...ll be removable from the front of the battery cabinet 4 Each battery cabinet shall feature a DC rated circuit breaker The circuit breaker within the battery cabinet shall only provide protection to th...

Страница 8: ...VAC 3 wire plus ground for 3 wire plus ground output configuration 2 Operating input voltage range 10 15 of average nominal input voltage without battery discharge 3 For 60Hz systems operating input f...

Страница 9: ...6 DC sensing Redundant DC voltage sensing methods shall be incorporated for providing battery over voltage protection 7 Battery charger characteristics The UPS battery charging system shall have the...

Страница 10: ...le 11 Phase angle control a Balanced linear load shall be 1 degree from nominal 120 degrees b Unbalanced linear loads shall less than 5 degrees from average phase voltage for 100 load unbalance 12 Pha...

Страница 11: ...e UPS shall withstand a 25 kV pulse without damage and with no disturbance or adverse effect to the critical load 11 Efficiency The UPS efficiency shall greater than 99 over the range of 10 to 100 loa...

Страница 12: ...cessor controlled circuitry The UPS controls shall have the following design and operating characteristics 1 Fully automatic operation of the UPS shall be provided through the use of microprocessor co...

Страница 13: ...tive cover which provides the following signals and communication features in a Class 2 environment 1 Alarm contact A dry contact for annunciating a summary alarm shall be provided for customer use Th...

Страница 14: ...attended sequential shutdown of one or multiple computers powered by one UPS This shutdown shall be performed via in network or out of network means The order of shutdown shall be user defined allowin...

Страница 15: ...ation operator training generator testing etc B The following procedures and tests shall be performed by Field Service personnel during the UPS startup 1 Visual Inspection a Visually inspect all equip...

Страница 16: ...g service with monthly reports for UPS and battery performance Standard response time shall be 8 hours from receipt of call Manufacturer shall also offer as an option 7x24 on site service support with...

Отзывы: