background image

Static Uninterruptible Power Supply

 

Page 13 of 13 

Eaton 9390 Guide Specification 

October 9, 2009 

 

 

 

the load.  A text message shall indicate if the battery charge is low or if the 
battery is installed but disconnected. 

4. 

ALARM:  This shall indicate that the UPS detects an alarm condition, outlined in 
detail in the operator’s manual. 

 

D. 

Control Panel Controls:  The UPS control panel shall provide the following functions from 
front panel push buttons: 

1. 

EVENTS: Displays the list of Active System Events and a historical log of system 
events. Historical logs shall include a detailed time stamped list of the latest 128 
events. 

2. 

METERS:  Displays performance meters for the system or critical load.  When 
selected, the front display shall show individual screens of input parameters, 
output parameters or bypass parameters including; voltage, current and 
frequency. In addition, the battery display shall show runtime remaining. 

3. 

CONTROLS:  Displays a System Controls screen.  Allows selection of operating 
mode, normal, bypass, charger on/off and Power Module on/off. 

4. 

SETUP:  Allows display contrast, date and time information serial communication 
port configuration and display of firmware revision numbers. 

5. 

RETURN:  Confirms selection or returns to previous screen. 

 

E. 

Interface panel:  The UPS shall be equipped with an interface panel, located behind a 
protective cover, which provides the following signals and communication features in a 
Class 2 environment: 

1. 

Alarm contact:  A dry contact for annunciating a summary alarm shall be provided 
for customer use. This contact shall be Form “C” capable of supplying both N/O 
and N/C contacts.  Contact ratings shall be 5A max at a voltage not to exceed 
28VDC or 277VAC. 

2. 

RS232 (EIA / TIA-232) communications interface:  Circuitry shall be provided for 
one RS232 (EIA / TIA-232) communication port for connection to automated 
service department diagnostic tools.   This port may be used with simple (“dumb”) 
terminals to gain remote access to all unit operation information. 

3. 

Building alarms: Two inputs shall be provided for monitoring the status of 
external dry contacts.  Building alarms shall be set up through the UPS 
configuration mode function on the RS232 (EIA / TIA-232) port. 

4. 

External EPO contacts: Shall be provided to connect an external remote 
emergency power off switch to shutdown the UPS and de-energize the critical 
load. 

5. 

Battery control contacts: Contacts shall be provided to connect the battery UVR  
and auxiliary signals from a battery breaker or battery disconnect switch. 

6. 

External bypass indicator connection: A connection point shall be provided to 
acknowledge that an external maintenance bypass has been closed around the 
UPS, placing the critical load on utility power. 

7. 

The system shall have options to add four (4) additional building alarms, 384 
logged events, 4 additional languages, Mandarin or Russian as a primary 
language.    

 

2.08 

COMMUNICATIONS 

 

Содержание Powerware 9390

Страница 1: ...UPS Module shall operate as an on line fully automatic system in the following modes 1 Normal Utilizing commercial AC power the critical load shall be continuously supplied by the Inverter The Invert...

Страница 2: ...EC 62040 1 1 International Electrotechnical Commission Uninterruptible power systems UPS Part 1 1 General and safety requirements for UPS used in operator access areas E IEC 62040 1 2 International El...

Страница 3: ...f all field service offices must be submitted with the proposal Third party maintenance will not be accepted E Spare Parts Support Parts supplies shall be located in the field to provide 80 of all eme...

Страница 4: ...nts the IGBTs from sourcing current in excess of their published ratings 3 An option shall be provided to allow the rectifier to be capable of operating from a delta transformer output or high impedan...

Страница 5: ...onditions a Bypass voltage out of limits 10 of nominal b Bypass frequency out of limits 3 Hz adjustable factory set c Bypass out of synchronization d Bypass phase rotation installation error 6 Static...

Страница 6: ...ocations 1 Rectifier charger input connections 3 wire plus ground 2 Bypass input connections 3 wire plus ground for 3 wire plus ground output configuration 480Vac or 4 wire plus ground for 4 wire plus...

Страница 7: ...ll be removable from the front of the battery cabinet 4 Each battery cabinet shall feature a DC rated circuit breaker The circuit breaker within the battery cabinet shall only provide protection to th...

Страница 8: ...VAC 3 wire plus ground for 3 wire plus ground output configuration 2 Operating input voltage range 10 15 of average nominal input voltage without battery discharge 3 For 60Hz systems operating input f...

Страница 9: ...6 DC sensing Redundant DC voltage sensing methods shall be incorporated for providing battery over voltage protection 7 Battery charger characteristics The UPS battery charging system shall have the...

Страница 10: ...le 11 Phase angle control a Balanced linear load shall be 1 degree from nominal 120 degrees b Unbalanced linear loads shall less than 5 degrees from average phase voltage for 100 load unbalance 12 Pha...

Страница 11: ...e UPS shall withstand a 25 kV pulse without damage and with no disturbance or adverse effect to the critical load 11 Efficiency The UPS efficiency shall greater than 99 over the range of 10 to 100 loa...

Страница 12: ...cessor controlled circuitry The UPS controls shall have the following design and operating characteristics 1 Fully automatic operation of the UPS shall be provided through the use of microprocessor co...

Страница 13: ...tive cover which provides the following signals and communication features in a Class 2 environment 1 Alarm contact A dry contact for annunciating a summary alarm shall be provided for customer use Th...

Страница 14: ...attended sequential shutdown of one or multiple computers powered by one UPS This shutdown shall be performed via in network or out of network means The order of shutdown shall be user defined allowin...

Страница 15: ...ation operator training generator testing etc B The following procedures and tests shall be performed by Field Service personnel during the UPS startup 1 Visual Inspection a Visually inspect all equip...

Страница 16: ...g service with monthly reports for UPS and battery performance Standard response time shall be 8 hours from receipt of call Manufacturer shall also offer as an option 7x24 on site service support with...

Отзывы: