background image

Static Uninterruptible Power Supply

 

Page 16 of 16 

Eaton 9390 Guide Specification 

October 9, 2009 

 

 

 

f) 

Check for the voltage difference between the Inverter output and the 
Bypass source. 

g) 

Optional on site full-load, step-load, and battery discharge tests using 
supplier furnished load bank, shall also be offered. 

5. 

Operational Training:  Before leaving the site, the field service engineer shall 
familiarize responsible personnel with the operation of the UPS.  The UPS 
equipment shall be available for demonstration of the modes of operation. 

 
3.03 

WARRANTY 

 

All components of the UPS system shall be covered by a standard one-year limited factory 
warranty and service protection package. 
 
One-year limited factory warranty shall include replacement coverage for the UPS parts for a 
period of 18 months from shipment or 12 months from start-up, whichever occurs sooner. 
 
One-year service protection package shall include 7x24 on-site repair/replacement labor for UPS 
parts and batteries; 7x24 technical support coverage; and 7x24 remote monitoring service (with 
monthly reports for UPS and battery performance). Standard response time shall be 8 hours from 
receipt of call. Manufacturer shall also offer, as an option, 7x24 on-site service support with 
guaranteed response times of 4, or 2 hours in certain major metropolitan areas.  Additional 
preventive maintenance visits shall be available as an option for both UPS and battery 
components. 
 
Manufacturer shall also include Start-up services consisting of:  5x8 Start-up service of UPS and 
batteries, with option for 7x24 Start-up.  On-site user training, Site Audit, installation and 
commissioning of monitoring service, and validation of one-year limited factory warranty will be 
performed during the start-up. 
 
Manufacturer shall also offer an optional service plan to provide 7x24 on-site coverage 
(preventive and corrective) for UPS and batteries, guaranteed response time, remote monitoring, 
Web access to service site history, annual Site Audit, UPS and battery preventive maintenance 
visit, and discounts on upgrade and modification kits.  Manufacturer shall also provide an optional 
battery service plan to provide parts-and-labor coverage for partial and full battery strings, either 
with preventive maintenance or replacement coverage. 
 
 
 
 
 
 

END 

Содержание Powerware 9390

Страница 1: ...UPS Module shall operate as an on line fully automatic system in the following modes 1 Normal Utilizing commercial AC power the critical load shall be continuously supplied by the Inverter The Invert...

Страница 2: ...EC 62040 1 1 International Electrotechnical Commission Uninterruptible power systems UPS Part 1 1 General and safety requirements for UPS used in operator access areas E IEC 62040 1 2 International El...

Страница 3: ...f all field service offices must be submitted with the proposal Third party maintenance will not be accepted E Spare Parts Support Parts supplies shall be located in the field to provide 80 of all eme...

Страница 4: ...nts the IGBTs from sourcing current in excess of their published ratings 3 An option shall be provided to allow the rectifier to be capable of operating from a delta transformer output or high impedan...

Страница 5: ...onditions a Bypass voltage out of limits 10 of nominal b Bypass frequency out of limits 3 Hz adjustable factory set c Bypass out of synchronization d Bypass phase rotation installation error 6 Static...

Страница 6: ...ocations 1 Rectifier charger input connections 3 wire plus ground 2 Bypass input connections 3 wire plus ground for 3 wire plus ground output configuration 480Vac or 4 wire plus ground for 4 wire plus...

Страница 7: ...ll be removable from the front of the battery cabinet 4 Each battery cabinet shall feature a DC rated circuit breaker The circuit breaker within the battery cabinet shall only provide protection to th...

Страница 8: ...VAC 3 wire plus ground for 3 wire plus ground output configuration 2 Operating input voltage range 10 15 of average nominal input voltage without battery discharge 3 For 60Hz systems operating input f...

Страница 9: ...6 DC sensing Redundant DC voltage sensing methods shall be incorporated for providing battery over voltage protection 7 Battery charger characteristics The UPS battery charging system shall have the...

Страница 10: ...le 11 Phase angle control a Balanced linear load shall be 1 degree from nominal 120 degrees b Unbalanced linear loads shall less than 5 degrees from average phase voltage for 100 load unbalance 12 Pha...

Страница 11: ...e UPS shall withstand a 25 kV pulse without damage and with no disturbance or adverse effect to the critical load 11 Efficiency The UPS efficiency shall greater than 99 over the range of 10 to 100 loa...

Страница 12: ...cessor controlled circuitry The UPS controls shall have the following design and operating characteristics 1 Fully automatic operation of the UPS shall be provided through the use of microprocessor co...

Страница 13: ...tive cover which provides the following signals and communication features in a Class 2 environment 1 Alarm contact A dry contact for annunciating a summary alarm shall be provided for customer use Th...

Страница 14: ...attended sequential shutdown of one or multiple computers powered by one UPS This shutdown shall be performed via in network or out of network means The order of shutdown shall be user defined allowin...

Страница 15: ...ation operator training generator testing etc B The following procedures and tests shall be performed by Field Service personnel during the UPS startup 1 Visual Inspection a Visually inspect all equip...

Страница 16: ...g service with monthly reports for UPS and battery performance Standard response time shall be 8 hours from receipt of call Manufacturer shall also offer as an option 7x24 on site service support with...

Отзывы: