COMMUNICATION
EATON
Powerware
®
9125 (9910-P30) UPS Installation Guide for IBM
®
Applications
S
164201636 Rev A
47
Serial (TTY) Interface Overview
To serially (TTY) connect the UPS to a p5, pSeries, RS/6000
®
,
OpenPower or other system you need:
S
An Eaton-supplied serial interface cable (labeled 124102044-001),
located in the P30 accessory kit
S
Powerware LanSafe
®
Power Management Software from the
Software Suite CD, located in the P30 accessory kit
For p5 installations, you also need:
S
An IBM-supplied 2-port Asynchronous EIA adapter (FC 5723) installed
on a p5 server (the pSeries does not require an EIA adapter)
S
An IBM-supplied maintenance package 5200-05 for AIX
®
5.2L V5.2
(APAR IY66260); or the maintenance package 5300-01 for AIX 5.3L
V5.3 (APAR IY62267)
Follow the software installation instructions contained on the Software
Suite CD to install the Powerware LanSafe software. Connect the serial
cable as shown in Figure 45.
Serial Interface Cable
(labeled 124102044-001)
IBM p5 Server
2-Port Asynchronous
EIA Adapter
(FC 5723)
UPS
Communication Port
Figure 45. Serial (TTY) Interface