OPERATION
EATON
Powerware
®
9125 (9910-P30) UPS Installation Guide for IBM
®
Applications
S
164201636 Rev A
32
Turning the UPS Off
NOTE
Pressing the Off
button while the UPS is in Battery mode causes the UPS to shut
down immediately.
To turn off the UPS:
1.
Prepare your equipment for shutdown.
2.
Press and hold the Off
button for approximately three seconds.
The UPS transfers to Standby mode (if utility power is available) and
removes power from your equipment.
3.
Unplug or remove utility power from the UPS; the UPS shuts down
in five seconds. All front panel indicators flash briefly prior to
shutdown.
If you do not unplug or remove utility power from the UPS, it
remains in Standby mode.
Initiating the Self-Test
NOTE
The batteries must be fully charged and the UPS must not be in Battery mode to
perform the self-test.
Press and hold the
button for three seconds to initiate the self-test.
During the five-second test, the bar graph indicators cycle through twice.
If the alarm beeps or a UPS alarm indicator stays on, refer to
“Troubleshooting” in the
Powerware 9125 Two-in-One UPS
(2500/3000 VA) User’s Guide
.