INSTALLATION
EATON
Powerware
®
9125 (9910-P30) UPS Installation Guide for IBM
®
Applications
S
164201636 Rev A
22
2.
UPS and FC 6750 PDM:
If you are installing a UPS and a PDM and
non-redundant power to the device(s) is desired, plug all the
equipment into the PDM output receptacles (see Figure 34 on
page 28) using the original device power cords (see Table 11 for
IBM plug types supported). Distribute the load evenly between the
rows of receptacles on the PDM.
If you are installing a UPS and a PDM and dual-redundant power to
the device(s) is desired, plug the minimum number of power cord(s)
required to operate the device into the PDM output receptacles
(see Figure 34 on page 28) using the original device power cords
(see Table 11 for IBM plug types supported). Then plug the
remaining (redundant) power cord(s) into a non-UPS protected
output receptacle (e.g., PDU or mains) or a second UPS with a PDM
using device power cords. Distribute the load evenly between the
rows of receptacles on the PDM.
NOTE
The PDM allows a UPS to be removed for service while providing conditioned power
to the protected device(s).
NOTE
The redundant power source must be protected with Transient Voltage Surge
Suppression (TVSS).
Table 11. FC 6750 PDM Plug Types Supported
IBM Plug Type
Description
Quantity Supported
4
NEMA 5-15P
2
5
NEMA 6-15P
4
29
NEMA 6-20P
4
10
NEMA L6-15P
2
NOTE If the IBM plug type selected with the equipment to be protected is not contained
in this table, change/order the plug type on the equipment to match the plug types
supported.
NOTE
DO NOT protect laser printers with the UPS because of the exceptionally high power
requirements of the heating elements.