www.powerware.com
1.800.356.5794
POWERWARE 9 BATTERY BACKUP TIMES (in minutes)
700-1000 VA Models
Load
Standard
(VA/Watts)
Internal Batteries
+1 EBM
+2 EBMs
200/140
37
271
546
400/280
19
142
278
700/490
9
72
156
850/595
6
59
124
1000/700
5
48
104
1250-2000 VA Models
Load
Standard
(VA/Watts)
Internal Batteries
+1 EBM
+2 EBMs
+3 EBMs
+4 EBMs
400/280
46
177
331
501
682
700/490
25
96
180
272
370
850/595
21
76
142
214
292
1000/700
16
61
115
174
237
1250/875
11
46
87
131
179
1500/1050
8
37
70
106
144
1800/1260
6
30
57
85
116
2000/1400
5
26
49
74
100
2500-3000 VA Models
Load
Standard
(VA/Watts)
Internal Batteries
+1 EBM
+2 EBMs
+3 EBMs
+4 EBMs
1250/875
16
57
90
150
200
1500/1050
13
55
72
120
160
2500/1750
7
28
48
68
88
3000/2100
5
25
38
54
70
Note: Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
POWERWARE 9 EBC BACKUP TIMES (in minutes)
Discharge Time
EXTERNAL EBC-48 CABINETS. For use with 1250, 1500, 2000 VA
VA
Watts
+1 EBC-48
+2 EBC-48s
+3 EBC-48s
650
455
838
800
560
662
1000
700
506
1200
840
406
1250
875
387
1400
980
340
761
1500
1050
315
705
1600
1120
294
658
1800
1260
258
578
2000
1400
224
501
802
EXTERNAL EBC-72 CABINETS. For use with 2500, 3000 VA
VA
Watts
+1 EBC-72
+2 EBC-72s
+3 EBC-72s
+4 EBC-72s
1000
700
387
1500
1050
245
2000
1400
175
368
2500
1750
135
284
446
3000
2100
107
225
354
490
1. Actual runtimes not supported by Powerware LanSafe software. *Discharge time @100% of the UPS rating.
Note: Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
SINGLE-PHASE SERIES 9
Powerware 9125 (700–3000 VA) EBM Backup Times