EATON CORPORATION
Reference Guide & Price Book
THREE-PHASE SERIES 9
Powerware BladeUPS (
continued
)
POWERWARE RACK POWER MODULE CONFIGURATOR
Description
Quantity
Part
List
Number Digit
Value
Price
Output Receptacle Plate #1 &
L21-20R
2
8 & 9
1
$400
Output Receptacle Plate #2
L21-30R
2
2
$445
L6-15R
3
3
$245
L6-20R
3
4
$260
L6-30R
3
5
$200
5-15R
6
6
$170
5-20R
6
7
$175
L14-20R
3
8
$180
L14-30R
3
9
$245
IEC320-C13 (208v)
12
A
$180
IEC320-C19 (208v)
6
B
$160
L15-20
E
$400
L15-30
F
$445
C13 (230v)
C
$180
C19 (230v)
D
$160
Metering Choices
Power Equalizer
10
1
$0
Energy Management System, NO card
2
Available May 2007
$695
Energy Management System, with card
3
Available May 2007
$1,025
Meter Configuration
11
0
TVSS Option
None
12
0
$0
TVSS Installed (208v)
1
$350
TVSS Installed (400v)
2
$350
Future Option
13
0
14
0
15
0
Notes
How to order:
1. Select base model voltage (208V or 400V), 2. Select input connector option, 3. Select input cord length (corded units only), 4. Select first receptacle plate
option, 5. Select second receptacle plate option, 6. Select metering option, 7. Select TVSS option
Example of configured model part number: Y03111022300000
SERVICE PLANS
For service plans, please see the service section beginning on page 81.
POWERWARE BLADEUPS BATTERY BACKUP TIMES (IN MINUTES)
Load
Internal
(kw)
Load %
Battery
+(1) EBM 64
+(2) EBM 64
+(3) EBM 64
+(4) EBM 64
1.6
13%
55
118
183
253
329
2.4
20%
37
78
119
163
211
4
33%
23
46
69
94
120
6
50%
13
30
44
59
76
8
67%
9
21
32
43
54
9.6
80%
6.9
17
26
34
44
12
100%
4.8
12
20
27
34
Note: Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
1 EBM needed per BladeUPS.
POWERWARE BLADEUPS BATTERY BACKUP TIMES (Parallel UPS, in minutes)
Number of
Total Load
Internal
UPS Models
(kw)
Configuration
Battery
+(1) EBM 64
+(2) EBM 64
+(3) EBM 64
+(4) EBM 64
6
60
N+1
6
15
22
29
37
5
48
N+1
6.9
17
26
34
44
4
36
N+1
7.7
18
28
37
47
3
24
N+1
9
21
32
43
54
2
12
N+1
13
30
44
59
76