THREE-PHASE SERIES 9
Powerware 9355 (10–15 kVA)
(continued)
POWERWARE 9 BATTERY BACKUP TIMES (in minutes) @ 0.9 POWER FACTOR
Load
UPS + Internal
UPS + Internal
VA
Watt
32 Battery
+(1) EBM 64 +(2) EBM 64 +(3) EBM 64 +(4) EBM 64
64 Battery
+(1) EBM 96
+(2) EBM 96 +(3) EBM 96
15000 13500
4.6
23.0
43.0
65.1
88.6
13.3
43.0
76.7
113.0
14500 13050
4.9
24.1
45.2
68.3
93.0
14.1
45.2
80.5
119.0
14000 12600
5.2
25.2
47.3
71.5
97.4
14.9
47.3
84.2
125.0
13500 12150
5.5
26.4
49.4
74.7
102.0
15.8
49.4
88.1
130.0
13000 11700
5.8
27.6
51.6
78.1
106.0
16.7
51.6
92.0
136.0
12500 11250
6.1
28.8
54.0
81.6
111.0
17.6
54.0
96.2
142.0
12000 10800
6.5
30.2
56.5
85.5
116.0
18.6
56.5
101.0
149.0
11500 10350
6.9
31.6
59.3
89.7
122.0
19.2
59.3
106.0
156.0
11000 9900
7.3
33.3
62.4
94.4
129.0
20.2
62.4
111.0
164.0
10500 9450
7.8
35.1
65.9
99.6
136.0
21.4
65.9
117.0
174.0
10000 9000
8.4
37.2
69.8
106.0
144.0
22.6
69.8
124.0
184.0
9500
8550
9.1
39.6
74.2
112.0
153.0
24.1
74.2
132.0
196.0
9000
8100
9.9
42.3
79.4
120.0
163.0
25.7
79.4
141.0
209.0
8500
7650
10.8
45.5
85.2
129.0
175.0
27.6
85.2
152.0
225.0
8000
7200
11.9
49.1
91.9
139.0
189.0
29.8
91.9
164.0
242.0
7500
6750
13.1
53.2
99.7
151.0
205.0
32.3
99.7
178.0
263.0
7000
6300
14.6
58.0
109.0
164.0
224.0
35.2
109.0
194.0
286.0
6500
5850
16.3
63.5
119.0
180.0
245.0
38.6
119.0
212.0
314.0
6000
5400
18.4
70.0
131.0
198.0
270.0
42.5
131.0
234.0
346.0
5500
4950
20.1
77.6
145.0
220.0
300.0
47.2
145.0
259.0
383.0
5000
4500
22.4
86.6
162.0
245.0
334.0
52.6
162.0
289.0
428.0
4500
4050
25.2
97.4
182.0
276.0
376.0
59.2
182.0
325.0
-
4000
3600
28.6
110.0
207.0
313.0
426.0
67.1
207.0
369.0
-
3500
3150
32.8
127.0
238.0
359.0
-
77.0
238.0
423.0
-
3000
2700
38.3
148.0
277.0
418.0
-
89.7
277.0
-
-
2500
2250
45.6
176.0
329.0
-
-
107.0
329.0
-
-
Note: Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.