manualshive.com logo in svg
background image

p/n: P-164001106

Revision 01

Setup and Operation Manual

Eaton

®

PDI WaveStar Infinity 2 Monitoring System

Содержание PDI WaveStar Infinity 2

Страница 1: ...p n P 164001106 Revision 01 Setup and Operation Manual Eaton PDI WaveStar Infinity 2 Monitoring System...

Страница 2: ...formance of your Eaton PDI WaveStar Infinity 2 Monitoring System please carefully read the instructions before trying to install operate service or maintain the system For any questions regarding the...

Страница 3: ...of threats including power outages surges lighting strikes and enable you to monitor and control your power infrastructure We trust that your Eaton Uninterruptible Power Supply system and Accessory Pr...

Страница 4: ......

Страница 5: ...n nn ne ec ct tiio on ns s 1 11 1 4 1 Sensor Types 11 4 1 1 Sensor Boards 12 4 1 2 Sensor Board Configuration 12 4 2 Sensor Board Layout 12 4 2 1 Sensor Board Order 12 4 2 2 Monitoring Compartments 12...

Страница 6: ...ME Screen 51 6 2 Analog Circuits Measurements and Status 53 6 2 1 Analog Sensors Single Circuits 53 6 2 2 Analog Sensors Panelboard CT Strips 54 6 2 3 Resetting Accumulators and Min Max Readings Clear...

Страница 7: ...t and SNMP MIB 25 Figure 17 Guest User Access 28 Figure 18 NAMES Screen Changing Banner Name 30 Figure 19 GENERAL Screen BASIC Tab 31 Figure 20 GENERAL Screen BASIC Tab Zero Fault Alarm in Alarm Heade...

Страница 8: ...Rev 01 Figure 40 Current Sensor Screens 53 Figure 41 Panelboard Screens Part One 54 Figure 42 Panelboard Screens Part 2 55 Figure 43 Clear Meters 56 Figure 44 Active Alarms vs Alarm History 58 Figure...

Страница 9: ...t o of f T Ta ab blle es s Table 1 Sensor Board Errors and Descriptions 22 Table 2 Sensor Status List vs Modbus Point List 23 Table 3 User Administration 28 Table 4 Calibration Procedure with Calibra...

Страница 10: ...x Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P 164001106 Rev 01 List of Tables...

Страница 11: ...igh voltages representing a hazard for electric shock burn or explosion Follow the instructions carefully to avoid serious or fatal injury Follow safe electrical work practices Read understand and fol...

Страница 12: ...2 Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P 164001106 Rev 01 Safety...

Страница 13: ...and Modbus RTU connectivity allowing Infinity 2 to interface to various customer management systems Single consolidated Modbus Points list and SNMP Management Information Block MIB matching your custo...

Страница 14: ...countries Call your local service representative Please use the following e mail for manual comments suggestions or to report a technical error in this manual E ESSDocumentation eaton com 2 2 2 2 W Wa...

Страница 15: ...simultaneously Ethernet Modbus TCP IP TCP IP for browser access to Infinity 2 SNMP Versions 1 2 or 3 Modbus RTU 2 wire or 4 wire Each Infinity 2 configuration has a single Modbus points list and SNMP...

Страница 16: ...n be up to 4000 ft if you use the correct cable The cable resistance should be 27 ohms 1000ft 1 kHz and the mutual capacitance should be 14pf ft 1 kHz 4 wire cabling RS422 is typically used for 4 wire...

Страница 17: ...own on pcb with jumpers on pin 2 and pin 6 only For 2 wire Modbus RTU install a jumper on Pins 1 and 2 and a jumper on Pins 5 and 6 Modbus Connectors RS1 RS2 TX TX RX RX GND TX TX RX RX GND Modbus RTU...

Страница 18: ...evice wires to RX on the next Monitor PCB see Figure 3 A second pair of wires connects the other pair of customer client TX to chain RX and customer client TX to chain RX The TX TX going to the RX RX...

Страница 19: ...be comprised of a twisted wire pair residing in the same shield Figure 4 Daisy chained Infinity 2 Monitors with 2 wire Modbus RTU Modbus Client Device In inity Monitor 2 In inity Monitor 3 In inity Mo...

Страница 20: ...10 Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P 164001106 Rev 01 Customer Network Connections...

Страница 21: ...rgency Power Off REPO Local digital input connections such as building alarms Local relay output connections such as a summary alarm 4 4 1 1 S Se en ns so or r T Ty yp pe es s To monitor your system I...

Страница 22: ...Se en ns so or r B Bo oa ar rd d C Co on nf fiig gu ur ra at tiio on n Eaton Manufacturing generates a sensor board configuration based on the physical power distribution configuration of your unit a...

Страница 23: ...rtment is behind the Monitor Modular Compact RPP typically has a Sensor Base Board and optionally a Sensor Combo Board The yellow arrow shows the network order of Sensor Boards in the Monitoring Compa...

Страница 24: ...d Sensor Combo Board Sensor Base Board Sensor Combo Board is located on Monitor side behind dead front panel Optional Sensor Base Board is located behind the Sensor Base Board on reverse side of panel...

Страница 25: ...Base Board and up to 4 Sensor Combo Boards The yellow arrow shows the network order of Sensor Boards in the Monitoring Compartment The network order of sensor boards is followed in the Modbus point l...

Страница 26: ...rrent Transformer the sensor types on the board A VVIT Sensor Combo Board is typically the first Sensor Board in a PDU Sensor Board chain see Figure 9 and has connections typical for a PDU such as tra...

Страница 27: ...n Boards Option Board positions are numbered 1 4 The order of the Option Boards is re lected in your Sensors Status screen Modbus Points List and SNMP MIB In this example the Voltage Option Board 1 wo...

Страница 28: ...one Digital Inputs Option Board it will be listed on your Sensors Status screen as Digital 1 Digital Inputs on the board are numbered 1 8 and are identified as D1 D8 on the Digital Inputs Screen Figu...

Страница 29: ...6 If Status Normal AND Enable Alarm is checked THEN an Alarm is signaled D1 D8 correspond to the D1 D8 connections on the Digital Inputs Options board Normal shows whether the normal non low 0 Check t...

Страница 30: ...ays Each relay can function as Normally Open NO or Normally Closed NC Relays are identified on the board as Relay 1 Relay 4 The first Relay Option Board is listed on your Sensors Status screen as Rela...

Страница 31: ...am me e T Ty yp pe e You may have more than one Option Board of the same type For example Digital Inputs are used for circuit breaker aux contacts and on a PDU with many subfeeds you may have more th...

Страница 32: ...d staus within a given period Error None no errors See table below for list of errors and their meanings Sensor Board List of sensor boards in the system Sensor boards can be renamed on screen with th...

Страница 33: ...odbus Digital Points section 1st point in each section is shown The Digital Points section is found after the Analog Points section Global Points in your Points List Prolong are not found on any senso...

Страница 34: ...ensors Status Screen Modbus Analog Points section 1st point in each section is shown Modbus Digital Points section 1st point in each section is shown The Digital Points section is found after the Anal...

Страница 35: ...ur configuration from a browser See Figure 16 for instructions Figure 16 Download Modbus Points List and SNMP MIB To download your Modbus Points List and SNMP MIB 1 From a browser log in to have admin...

Страница 36: ...26 Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P 164001106 Rev 01 Customer Sensor Board Connections...

Страница 37: ...side of banner time date user to display the log in screen Changes are automatically saved except in certain cases where there is a Save Changes button NOTE After pressing the Save Changes button the...

Страница 38: ...r no login required 5 5 1 1 2 2 U Us se er r S Se et tu up p User administration is very simple The only identified users are administrators The only user changes are adding an administrator Add User...

Страница 39: ...t the Setup Icon 4 Select USERS command button 5 Select user from Users drop down list and choose EDIT USER 6 Change User Credentials appears Only the password can be changed To change the user name i...

Страница 40: ...the NAMES command button These changes only affect names used on Infinity 2 monitoring screens They do NOT change names in the Modbus points list or SNMP MIB Not all names can be changed Scroll throug...

Страница 41: ...nges are automatically saved as you make them BASIC Tab Enter parameters for Monitor behavior Figure 19 GENERAL Screen BASIC Tab Audible Alarm Check Audio Alarm if you want an audible alarm to sound a...

Страница 42: ...tion Check Subfeed Cascading to allow subfeeds and panelboards to display as an overlapping cascade on the HOME screen 1 line mimic When you have many subfeeds and or panelboards cascading allows thei...

Страница 43: ...date into the text box in the specified date format Time Set time based on your local time zone in 12 hour clock format with AM PM 24 hour clock time is not used Time resolution is in minutes Time Zo...

Страница 44: ...34 Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P 164001106 Rev 01 Figure 22 GENERAL Screen DATE TIME NTP Service Selected Setup...

Страница 45: ...K P PR RO OT TO OC CO OL LS S S Sc cr re ee en n You must set up Infinity 2 software to match the physical network configuration you connected to Infinity 2 in paragraph 3 2 Network Connections Select...

Страница 46: ...ress Subnet mask and Gateway address Alternatively check USE DHCP to have your installation dynamically assign these addresses The MAC address is stored in the ROM chip and cannot be changed Changes a...

Страница 47: ...peration Manual P 164001106 Rev 01 37 SNMP Tab If you are using SNMP you must also select the SNMP tab to set up additional SNMP parameters V1 V2 Communities Enter your Get Set and Trap Communities Fi...

Страница 48: ...rsion 1 2 or 3 Specify Trap Interval in seconds using drop down list SNMP sends only a summary alarm trap The trap is sent repeatedly at this interval if alarms remain outstanding Define the addresses...

Страница 49: ...on Manual P 164001106 Rev 01 39 V3 Settings Specify Authentication User Name Select Algorithm using the drop down list Enter Password Specify Encryption Select Algorithm using the drop down list Enter...

Страница 50: ...ure 28 Setup NETWORK PROTOCOLS SNMP Service Tab TEST TRAP sends a single test trap to your specified trap servers LOAD DEFAULT loads SNMP information created in manufacturing and shipped with the unit...

Страница 51: ...rameters created in manufacturing and shipped with the unit Select Baud Rate and Parity using drop down lists Specify the Modbus Address of the Infinity 2 Monitor 1 247 Specify a Unit ID Infinity 2 re...

Страница 52: ...etup and Operation Manual P 164001106 Rev 01 Figure 30 Setup NETWORK PROTOCOLS Modbus Tab Reboot Message Select POINTS LIST to download the Modbus points list for your unit See also parapgraph 4 4 1 D...

Страница 53: ...s you must logged in then select the Tool icon in the banner The LIMITS screen is displayed The Sensors drop down list shows all sensors in your Infinity 2 system Select a sensor from the list to disp...

Страница 54: ...alues and Alarm check boxes are in bold lettering showing that the logged in user can set limits Phase neutral limits are set but alarms are not enabled boxes not checked Phase phase limits are set he...

Страница 55: ...3 Panelboard Sensor Strip Applying the Same Parameters to All Circuits You should specify Circuit Breaker CB size default 20A Warning Threshold W Thresh as percent of CB size default 70 Alarm Threshol...

Страница 56: ...S and NEXT to scroll to the settings for the other half of the sensor strip Value A shows the last measured amperage for the circuit When you remove the check mark in All the values in the first colum...

Страница 57: ...l state for a digital input bit 1 or bit 0 When the digital point s status does not match its normal state an alarm is triggered if you have enabled alarms for that digital input The only Digital Inpu...

Страница 58: ...ip are set up in manufacturing Transformer temperature status is also shown on the HOME screen Figure 36 Transformer Screen Digital Points If Status Normal AND Enable Alarm is checked THEN an alarm is...

Страница 59: ...names are set during manufacturing An administrator can change the Relay Option Board name by default Relay 1 Relay 2 etc on screen with the NAMES command but not the specific relay name The Relay Se...

Страница 60: ...50 Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P 164001106 Rev 01 Setup...

Страница 61: ...nts on this screen a user can navigate to other screens to display monitoring information or to set system parameters To select screen elements On the Infinity 2 display touch the screen element On a...

Страница 62: ...pecific item in the group select the icon group to show a list Select the appropriate item to display its status screen Figure 39 HOME Screen with Cascading Panel 1 CB CLOSED Panel 2 CB CLOSED Subfeed...

Страница 63: ...voltage V transformer output voltage and current VI or current I for subfeeds or panelboard main feeds Select the V I or VI icon to display a screen with readings Screens for all single circuit sensor...

Страница 64: ...rds have multiple menus that can be viewed using the slide out side menu Figure 41 Panelboard Screens Part One Select the Menu Icon to view options Select Panel 1 Panelboard circuits can have limits s...

Страница 65: ...ax A since reset THD F Crest Factor CF POWER DEMAND screen Current A Demand A Max Demand A Demand KW Max Demand KW KWH KW Crest Factor CF Unlike major circuits or subfeeds panelboard circuits have 3 a...

Страница 66: ...igure 43 You have these options CLEAR MIN MAX for all sensors or specific sensors CLEAR KWH for all sensors or specific sensors Figure 43 Clear Meters 6 6 3 3 D Diig giit ta all P Po oiin nt ts s S St...

Страница 67: ...gital sensor page will show the alarm active Transformer temperature alarms will show color coded by severity on the HOME screen 1 line The Modbus Points List will provide alarm status If so configure...

Страница 68: ...to display ALARM Screen But alarms remain in the Alarm History until removed Select Garbage Can icon to clear the Alarm History Alarms cannot be individually cleared You must be logged in to clear th...

Страница 69: ...s including all severities Alarm Warning Zero Digital Input or Relay User log in User log out Relay activated Infinity 2 rebooted To view the Log Events screen select the left section of the banner Th...

Страница 70: ...60 Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P 164001106 Rev 01 Operation Monitoring Your System...

Страница 71: ...of any input voltage input current or current for an individual panel board circuit can be calibrated To use calibration screens the user must be logged in Table 4 Calibration Procedure with Calibrat...

Страница 72: ...3 Touch or click an analog measurement field on the HOME screen such as V VI I or Panels Output Voltage is used in this example 4 Touch or click the measurement field you wish to calibrate When using...

Страница 73: ...ed unit Figure 46 CT Fix Positions on Panelboard CT Strip 1 2 3 Replacement split core CTs have the same monitoring accuracy as the on strip solid core CTs The following procedure to replace a failing...

Страница 74: ...from the drop down list 7 The CT Fix screen shows available and assigned CT Fix positions Three 3 substitute CT positions are available for each panelboard strip 8 Select a CT Fix position CT Fix 1 T...

Страница 75: ...2 11 Connect the split core CT monitoring cable to the CT Fix position on the CT Strip that corresponds to the screen CT Fix position 1 Top 2 Middle 3 Bottom NOTE On 84 pole panelboards there are four...

Страница 76: ...66 Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P 164001106 Rev 01 Maintenance...

Страница 77: ...em can be downloaded from the product page on the Eaton website https www eaton com us en us catalog backup power ups surge it power distribution eaton pdi wavestar infinity monitoring system html Eat...

Страница 78: ...P 16400110601 P 164001106 01...

Отзывы: