Table 5. Current Voltage Frequency Metering Data
Current Metering Units
Accuracy
Notes
IA, IB, IC, IN, IG
Amperes ±1% of
Reading
j
IA, IB, IC, IN, IG
(min.)
Amperes ±1% of
Reading
jl
Group values held until reset
IA, IB, IC, IN, IG
(max.)
Amperes ±1% of
Reading
jl
Group values held until reset
IA, IB, IC, IN, IG
(demand)
Amperes ±1% of
Reading
jl
Window 5 - 60 minutes
Sliding or Fixed
IA, IB, IC, IN, IG
(demand max)
Amperes ±1% of
Reading
jl
Group values held until reset
Current Metering
Range
Notes
Current Unbalance
---
0 - 100%
Voltage Metering Units
Accuracy
Notes
VAB, VBC, VCA
Volts
±1% of
Reading
k
Line to Line Voltage
VAB, VBC, VCA
(min)
Volts
±1% of
Reading
k
VAB, VBC, VCA
(max)
Volts
±1% of
Reading
k
VAN, VBN, VCN
Volts
±1% of
Reading
k
Line to Neutral Voltage
VAN, VBN, VCN
(min)
Volts
±1% of
Reading
k
VAN, VBN, VCN
(max)
Volts
±1% of
Reading
k
Frequency
Metering
Units
Accuracy
Notes
Frequency
Hz
±0.2 Hz of
Reading
k
Range is 20 to 255 Hz
Frequency (min))
Hz
±0.2 Hz of
Reading
k
Value held until reset
Frequency (min))
Hz
±0.2 Hz of
Reading
k
Value held until reset
j
Accuracy applicable for 5 to 100% of I
n
and current will start metering at 2% of rating plug
k
Applicable to the voltage range of 34 to 690 Vac.
l
All currents share a common configured demand window. All powers share a common configured demand window.
9
EATON
www.eaton.com
Effective September 2013
Instructional Leaflet IL01301064E
Operating Manual for Series NRX
Digitrip Trip Units 1150 / 1150i
Table 6. Power and Energy Metering Data
Power Metering
Units
Accuracy
Notes
Power
kW
±2% of Reading
jk
Approximately 1- second
update
kVA
kVA
±2% of Reading
jk
Approximately 1- second
update
kvar
kvar
±2% of Reading
jk
Approximately 1- second
update
Demand kW
kW
±2% of Reading
jkl
Window 5 - 60 minutes
Sliding or Fixed
Demand (max). kW
kW
±2% of Reading
jkl
Value held until reset
Demand kVA
kVA
±2% of Reading
jkl
Window 5 - 60 minutes
Sliding or Fixed
Demand (max). kVA
kVA
±2% of Reading
jkl
Value held until reset
Demand kvar
kvar
±2% of Reading
jkl
Window 5 - 60 minutes
Sliding or Fixed
Demand (max) kvar
kvar
±2% of Reading
jkl
Value held until reset
Power Metering
Range
Notes
PF (power factor)
---
0 - ±1.00
PF (min. absolute)
---
0 - 1.00
Value held until reset
PF (max. absolute)
---
0 - 1.00
Value held until reset
Energy Metering Units
Accuracy
Notes
Energy kWh
kWh
±2% of Reading
jk
Total
Energy fwd kWh
kWh
±2% of Reading
jk
Forward
Energy rev kWh
kWh
±2% of Reading
jk
Reverse
kVAh
kVh
±2% of Reading
jk
Net Reactive
Metering
Configuration
Settings
Notes
Reverse Feed
Configuration
Normal or Reverse
Line to load is normal and
the default setting
Energy Log Interval
Off, 5, 10, 15, 20, 30, 60
minutes