Appendix F: Setpoint Defaults and Worksheet
Use this form for reference to factory settings and a worksheet for setpoint record keeping.
Series NRX
Digitrip 1150
TRIP UNIT SETTINGS
Page 1
Circuit No./Address
______________________________
Breaker Shop Order Reference
______________________________
PER UNIT MULTIPLIERS
Rating Plug Amperes (In)
______________________________
Ir = Continuous Current Rating = LD x In
______________________________
Parameter
Factory Default Setting
Installed Setting
Notes
System Frequency
60Hz
Reverse Feed Breaker
Normal Feed (top to bottom)
Power Sign Convention
IEEE
Current Demand Window
Fixed Window
Current Demand Interval
5 Minutes
Power Demand Window
Fixed Window
Power Demand Interval
15 Minutes
Energy Log Window
Off
Long Delay Slope
I
2
t
Long Delay Pickup
100%
Long Delay Time
4 s
Thermal Memory
Enabled
Time Dial Setting for IEC / IEEE Slopes only
20 s
Short Delay Slope
Flat
Short Delay Pickup
300%
Short Delay Time
300 ms
Instantaneous Pickup
400%
Ground Fault Slope
Flat
Ground Fault Pickup
40%
Ground Fault Delay Time
300 ms
External Ground Sensing Ratio
fixed
Neutral Protection
100%
Current Unbalance Trip
Off
Current Unbalance Time Delay
10 s
Phase Loss Time Delay
Off
Voltage Protection
Off
Under Voltage Trip Setting
Off
Under Voltage Trip Time Delay
30 s
Over Voltage Trip Setting
Off
Over Voltage Trip Time Delay
30 s
Voltage Unbalance Trip Setting
Off
Voltage Unbalance Trip Time Delay
30 s
94
Effective September 2013
Instructional Leaflet IL01301064E
Operating Manual for Series NRX
Digitrip Trip Units 1150 / 1150i