background image

18

NOVA™ STS Single-Tank, Triple-Single, Electronically Controlled Recloser

INSTALLATION AND OPERATION INSTRUCTIONS

  MN280046EN   May 2016

Test results for NOVA STS reclosers equipped with the 

internal voltage sensing option will be influenced by the 

source-to-ground connected sensing resistor.
The following tests should be applied to the NOVA STS 

Single-Tank, Triple-Single recloser system:

Test 1

1.  Close the recloser contacts.
2.  Ground the recloser.
3.  Connect terminals 2, 4, and 6 (see Figure 16) together.
4.  Apply proper test voltage (see Table 15) to terminals 2, 

4, and 6. 

5.  The recloser should withstand the test voltage for 60 

seconds.

Test 2

1.  Close the recloser contacts.
2.  Ground the recloser.
3.  Ground terminal 2 and terminal 6.
4.  Apply proper test voltage to terminal 3.
5.  The recloser should withstand the test voltage for 60 

seconds.

Test 3

1.  Open the recloser contacts.
2.  Ground the recloser.
3.  Connect and ground terminals 1, 3, and 5 (see Figure 

16).

4.  Connect terminals 2, 4, and 6.
5.  Apply proper test voltage to terminals 2, 4, and 6.
6.  The recloser should withstand the test voltage for 60 

seconds. 

7.  Reverse the connections: ground terminals 2, 4, and 6.
8.  Apply test voltage to terminals 1, 3, and 5 for 60 

seconds. 

9.  The recloser should withstand the test voltage for 60 

seconds.

Withstand test results

The high-potential withstand tests provide information on 

the dielectric condition of the recloser and the vacuum 

integrity of the interrupters. 
If the recloser passes the closed-contacts tests (Tests 1 

and 2), but fails the open-contacts test (Test 3), the cause is 

likely to be in the interrupter assembly. Retest each phase 

individually to determine the failed phase or phases.

If a recloser fails the closed-contacts test, the cause is likely 

to be a diminished electrical clearance or failed insulation.
If the recloser does not pass Tests 1, 2, or 3, contact an 

authorized service center or your Eaton’s Cooper Power 

series product representative.

otee:

N

Test results for NOVA reclosers equipped with the 

internal voltage sensing option will be influenced by 

the source-to-ground connected sensing resistor, 

especially if DC high-potential testing is performed.

Module flashover service

If a NOVA recloser module was exposed to an external 

flashover, an inspection process is recommended to assure 

proper operation of the recloser. Should the NOVA recloser 

exhibit external flashover attributes (carbon tracking or 

discoloration), the following procedure is recommended:
1.  Bypass and remove the recloser from service as 

described in this manual.

2.  Confirm the dielectric strength of the recloser by 

performing high-potential withstand test. Refer to the 

High-potential withstand testing

 section of this 

manual.

3.  Inspect the housing and lifting lugs for damage that 

may affect electrical and/or mechanical performance. 

If there is damage to either the housing or lifting lugs 

they must be replaced or repaired.

4.  Inspect module for damage to the terminals. Remove 

any damaged terminals and replace.

5.  Inspect module for damage to the module conductor 

rods (0.63” diameter threaded rods on top and side of 

module for affixing terminals). If there is damage to the 

module rods, the module must be replaced. Contact an 

authorized service center or your Eaton’s Cooper Power 

series representative.

6.  Inspect the operating rod for damage. Check the 

module surface and major and minor sheds for cracks, 

holes, and major chips. If damage is present, the 

module must be replaced. Contact your Eaton’s Cooper 

Power series product representative.

7.  If no damage is found, clean the module with isopropyl 

alcohol and a scratch-free, nylon scouring pad to 

remove any carbon deposit.

8.  Before returning to service confirm electrical operation 

by opening and closing the recloser with a control. 

Confirm the dielectric strength of the recloser by 

performing a high-potential withstand test. Refer to 

the 

High-potential withstand testing

 section of this 

manual.

Содержание NOVA STS-15

Страница 1: ...NOVA STS 27 and NOVA STS 38 Single Tank Triple Single Electronically Controlled Recloser Installation and Operation Instructions COOPER POWER SERIES Reclosers MN280046EN Effective May 2016 Supersedes...

Страница 2: ...LAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT...

Страница 3: ...ing the recloser 4 Lifting the recloser 4 Remove recloser from service 6 Grounding the NOVA STS recloser 7 RECLOSER OPERATION 8 Vacuum interrupter 8 Mechanism tripping and closing 8 Electronic control...

Страница 4: ...EN May 2016 SERVICE INFORMATION 16 Service requirements 16 Discharge trip and close capacitor 16 Frequency of inspection 16 High potential withstand testing 17 Module flashover service 18 TROUBLESHOOT...

Страница 5: ...igh voltage lines and equipment and support our Safety For Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all...

Страница 6: ...incurred during shipment If damage is discovered file a claim with the carrier immediately Handling and storage Be careful during handling and storage of the recloser to minimize the possibility of da...

Страница 7: ...kV 38 kV Rated Continuous Current 630 A 630 A 630 A 630 A 630 A Short Circuit Current Symmetrical 12 5 kA 12 5 kA 12 5 kA 12 5 kA 12 5 kA Making Current Asymmetrical Peak 32 0 kA 32 0 kA 32 0 kA 32 0...

Страница 8: ...5 Flat Pad 4 hole 800 A maximum 121 4 75 Stud Type 1 125 12 threads 800 A maximum 82 3 25 Table 7 Terminal options continued Description B C NOVA STS 15 110 kV BIL 1008 39 75 733 29 NOVA STS 15 125 kV...

Страница 9: ...t in cuts and abrasions T258 1 3 Install the recloser Install the recloser in the appropriate Eaton s Cooper Power series pole or substation mounting frame See Figure 3 for moving and lifting instruct...

Страница 10: ...es and bypass switches are not required but are highly recommended as they facilitate switching and isolation Disconnect switches for AC sensing and power connections are necessary to isolate the Form...

Страница 11: ...ich will cause death or severe personal injury G108 1 WARNING Hazardous voltage Do not rely on the open position of the yellow operating handle or the contact position indicator it does not ensure tha...

Страница 12: ...ice Eaton recommends transporting Cooper Power series NOVA reclosers in the closed position to maxi mize the operational performance of the unit Grounding the NOVA STS recloser IMPORTANT In pole mount...

Страница 13: ...responds to trip and close commands from the control per the settings programmed in the control Refer to Service Information S280 70 7 Form 6 Triple Single Microprocessor Based Pole Mount Recloser Con...

Страница 14: ...der the sleet hood Note N When the recloser electronically operates to lockout the yellow operating handle will not drop down from under the sleet hood The yellow operating handle remains in the OPEN...

Страница 15: ...that the voltage is zero and the line has been de energized Always follow proper safety practices and use a separate detection method to verify a de energized condition Failure to do so can result in...

Страница 16: ...refer to Tables 9 and 10 These are entered in the System Configuration screen see Figure 12 When programming the Form 6 Triple Single control the PT connection must be set for a wye connection Also t...

Страница 17: ...uch the receptacle connections of the control voltage sensing cable If the recloser is energized and the control voltage sensing cable is disconnected from the recloser or the control a voltage clampe...

Страница 18: ...B phase b white black red black G H C phase a green black orange black J K C phase b blue black black white L M unused unused unused N P See Figure 6 A phase is designated as terminals 1 and 2 B phase...

Страница 19: ...Cable Range 800 A maximum 108 4 25 Flat Pad 2 hole 630 A maximum 114 4 5 Flat Pad 4 hole 800 A maximum 121 4 75 Stud Type 1 125 12 threads 800 A maximum 82 3 25 Table 14 Terminal options continued De...

Страница 20: ...e not included with the brackets Refer to Figure 14 Inboard arrester mounting accessory 374 14 75 min 523 20 5 650 25 5 395 15 5 650 25 5 523 20 5 395 15 5 285 11 25 469 18 5 1030 40 5 107 4 25 394 15...

Страница 21: ...it smoothly and do not allow the unit to shift Improper lifting can result in severe personal injury death and or equipment damage G106 3 2 Loosen bolts that secure the tank and remove the tank bottom...

Страница 22: ...s Solidly ground all equipment Failure to comply can result in death severe personal injury and equipment damage T221 5 CAUTION Radiation At voltages up to the specified test voltages the radiation em...

Страница 23: ...ized service center or your Eaton s Cooper Power series product representative Note N Test results for NOVA reclosers equipped with the internal voltage sensing option will be influenced by the source...

Страница 24: ...LOSE position Check all cables for proper connection Check the condition of the battery located in the control cabinet Refer to Service Information S280 70 7 Form 6 Triple Single Microprocessor Based...

Страница 25: ...se T Yellow Handle B phase P 53 V Common B phase B 53 V dc B phase W CT B phase b Voltage Sensor B phase G Trip C phase K Close C phase U Yellow Handle C phase R 53 V Common C phase C 53 V dc C phase...

Страница 26: ...LK WHT WHT ORG BRN P1 7 CT COM Optional Voltage Sensor VTC 28 V dc NO TRIP Yellow Handle CLOSE Common 28 V dc 53 V Common 53 V dc YEL RED P2 2 MS3 yellow handle NC Actuator Circuit Board P2 3 MS2 52b...

Страница 27: ...K CLOSE C L Common 28 V dc M Chassis Ground A N 53 V Common A P 53 V Common B R 53 V Common C S Yellow Handle A T Yellow Handle B U Yellow Handle C V CT A W CT B X CT C Y CT Common Z Opt Voltage Sens...

Страница 28: ...es Eaton com cooperpowerseries 2016 Eaton All Rights Reserved Printed in USA Publication No MN280046EN May 2016 KA20480749 REV00 Eaton is a registered trademark All trademarks are property of their re...

Отзывы: