NOVA™ STS Single-Tank, Triple-Single, Electronically Controlled Recloser

INSTALLATION AND OPERATION INSTRUCTIONS

  MN280046EN   May 2016

Actuator circuit board

The actuator circuit board, located within the mechanism, 

drives the mechanism based upon signals sent from the 

control. The actuator board manages the high power path by 

providing precharge and discharge capabilities and provides 

the proper current pulses and timing to the mechanism. 

It also prevents closing when there is insufficient energy 

stored in the trip and close capacitor.

Trip and close capacitor

 WARNING 

Personal injury . The trip and close capacitor retains 

an electrical charge . Always discharge the trip and 

close capacitor prior to performing any service on the 

mechanism . Contact with a charged capacitor can result 

in skin burn or electrical shock . 

T266 .0

A trip and close capacitor, located within the mechanism, 

stores the necessary energy for operating the recloser. 
The Discharge Trip and Close Capacitor procedure is located 

in the 

Service information

 section.

Internal voltage sensing option

 WARNING 

This equipment is not intended to protect human 

life . Follow all locally approved procedures and safety 

practices when installing or operating this equipment . 

Failure to comply can result in death, severe personal 

injury, and equipment damage . 

G102 .1

 WARNING 

H

azardous voltage . Always use a hotstick when working 

with this equipment . Failure to do so could result in 

contact with high voltage, which will cause death or 

severe personal injury . 

G108 .1

 WARNING 

Hazardous voltage . Solidly ground all equipment . Failure 

to comply can result in death, severe personal injury, 

and equipment damage . 

T223 .2

IMPORTANT

Disconnect switches for AC control power are necessary to 

isolate the control for testing and servicing.

 WARNING 

Hazardous voltage . If terminal connections are reversed, 

the internal voltage sensing option may indicate zero 

voltage with the contacts open . Do not rely on internal 

voltage sensing to ensure that the voltage is zero and 

the line has been de-energized . Always follow proper 

safety practices and use a separate detection method 

to verify a de-energized condition . Failure to do so can 

result in contact with high voltage, which will cause 

death or severe personal injury .  

T365 .0

The NOVA STS recloser is available with internal voltage 

sensing when specified at time of order with the Form 6 

Triple-Single control. Refer to the 

Installation procedure 

section of this manual for information on the NOVA STS 

recloser installation procedure. Refer to 

Service Information 

S280-70-7 Form 6 Triple-Single, Microprocessor-Based 

Pole Mount Recloser Control Installation and Operation 

Instructions

 for further information on installing the Form 6 

Triple-Single pole-mount control. 
Verify the correct load-side and source-side terminal 

connections. This is required for correct operation of the 

internal voltage sensors.
Verify correct ground of the NOVA STS recloser and control 

prior to making any high-voltage connections and before 

high-potential testing. A proper ground connection consists 

of a good electrical ground connection to the surge ground 

connector located on the mechanism housings. Provide a 

good electrical ground connection to the control cabinet 

ground.

otee:

N

Painted surfaces of the mechanism housing may 

prevent a ground connection to the recloser housing. 

Always provide a good electrical connection to the 

mechanism surge ground connector. 

 

Poor grounding of the mechanism housing may result 

in the presence of high voltage on the mechanism 

housing associated with the high-voltage resistor 

connections used with internal voltage sensing.

 CAUTION 

Hazardous voltage . Do not touch the receptacle 

connections of the control/voltage-sensing cable . If the 

recloser is energized and the control/voltage-sensing 

cable is disconnected from the recloser or the control, 

a voltage clamped at 250 Vac will be present at the 

receptacle . Contact with this voltage can result in 

personal injury . 

T346 .1

The recloser utilizes a 26-pin control cable to carry the 

internal voltage sensing signal from the recloser to the 

control. There are no additional external connections 

required.

Содержание NOVA STS-15

Страница 1: ...NOVA STS 27 and NOVA STS 38 Single Tank Triple Single Electronically Controlled Recloser Installation and Operation Instructions COOPER POWER SERIES Reclosers MN280046EN Effective May 2016 Supersedes...

Страница 2: ...LAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT...

Страница 3: ...ing the recloser 4 Lifting the recloser 4 Remove recloser from service 6 Grounding the NOVA STS recloser 7 RECLOSER OPERATION 8 Vacuum interrupter 8 Mechanism tripping and closing 8 Electronic control...

Страница 4: ...EN May 2016 SERVICE INFORMATION 16 Service requirements 16 Discharge trip and close capacitor 16 Frequency of inspection 16 High potential withstand testing 17 Module flashover service 18 TROUBLESHOOT...

Страница 5: ...igh voltage lines and equipment and support our Safety For Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all...

Страница 6: ...incurred during shipment If damage is discovered file a claim with the carrier immediately Handling and storage Be careful during handling and storage of the recloser to minimize the possibility of da...

Страница 7: ...kV 38 kV Rated Continuous Current 630 A 630 A 630 A 630 A 630 A Short Circuit Current Symmetrical 12 5 kA 12 5 kA 12 5 kA 12 5 kA 12 5 kA Making Current Asymmetrical Peak 32 0 kA 32 0 kA 32 0 kA 32 0...

Страница 8: ...5 Flat Pad 4 hole 800 A maximum 121 4 75 Stud Type 1 125 12 threads 800 A maximum 82 3 25 Table 7 Terminal options continued Description B C NOVA STS 15 110 kV BIL 1008 39 75 733 29 NOVA STS 15 125 kV...

Страница 9: ...t in cuts and abrasions T258 1 3 Install the recloser Install the recloser in the appropriate Eaton s Cooper Power series pole or substation mounting frame See Figure 3 for moving and lifting instruct...

Страница 10: ...es and bypass switches are not required but are highly recommended as they facilitate switching and isolation Disconnect switches for AC sensing and power connections are necessary to isolate the Form...

Страница 11: ...ich will cause death or severe personal injury G108 1 WARNING Hazardous voltage Do not rely on the open position of the yellow operating handle or the contact position indicator it does not ensure tha...

Страница 12: ...ice Eaton recommends transporting Cooper Power series NOVA reclosers in the closed position to maxi mize the operational performance of the unit Grounding the NOVA STS recloser IMPORTANT In pole mount...

Страница 13: ...responds to trip and close commands from the control per the settings programmed in the control Refer to Service Information S280 70 7 Form 6 Triple Single Microprocessor Based Pole Mount Recloser Con...

Страница 14: ...der the sleet hood Note N When the recloser electronically operates to lockout the yellow operating handle will not drop down from under the sleet hood The yellow operating handle remains in the OPEN...

Страница 15: ...that the voltage is zero and the line has been de energized Always follow proper safety practices and use a separate detection method to verify a de energized condition Failure to do so can result in...

Страница 16: ...refer to Tables 9 and 10 These are entered in the System Configuration screen see Figure 12 When programming the Form 6 Triple Single control the PT connection must be set for a wye connection Also t...

Страница 17: ...uch the receptacle connections of the control voltage sensing cable If the recloser is energized and the control voltage sensing cable is disconnected from the recloser or the control a voltage clampe...

Страница 18: ...B phase b white black red black G H C phase a green black orange black J K C phase b blue black black white L M unused unused unused N P See Figure 6 A phase is designated as terminals 1 and 2 B phase...

Страница 19: ...Cable Range 800 A maximum 108 4 25 Flat Pad 2 hole 630 A maximum 114 4 5 Flat Pad 4 hole 800 A maximum 121 4 75 Stud Type 1 125 12 threads 800 A maximum 82 3 25 Table 14 Terminal options continued De...

Страница 20: ...e not included with the brackets Refer to Figure 14 Inboard arrester mounting accessory 374 14 75 min 523 20 5 650 25 5 395 15 5 650 25 5 523 20 5 395 15 5 285 11 25 469 18 5 1030 40 5 107 4 25 394 15...

Страница 21: ...it smoothly and do not allow the unit to shift Improper lifting can result in severe personal injury death and or equipment damage G106 3 2 Loosen bolts that secure the tank and remove the tank bottom...

Страница 22: ...s Solidly ground all equipment Failure to comply can result in death severe personal injury and equipment damage T221 5 CAUTION Radiation At voltages up to the specified test voltages the radiation em...

Страница 23: ...ized service center or your Eaton s Cooper Power series product representative Note N Test results for NOVA reclosers equipped with the internal voltage sensing option will be influenced by the source...

Страница 24: ...LOSE position Check all cables for proper connection Check the condition of the battery located in the control cabinet Refer to Service Information S280 70 7 Form 6 Triple Single Microprocessor Based...

Страница 25: ...se T Yellow Handle B phase P 53 V Common B phase B 53 V dc B phase W CT B phase b Voltage Sensor B phase G Trip C phase K Close C phase U Yellow Handle C phase R 53 V Common C phase C 53 V dc C phase...

Страница 26: ...LK WHT WHT ORG BRN P1 7 CT COM Optional Voltage Sensor VTC 28 V dc NO TRIP Yellow Handle CLOSE Common 28 V dc 53 V Common 53 V dc YEL RED P2 2 MS3 yellow handle NC Actuator Circuit Board P2 3 MS2 52b...

Страница 27: ...K CLOSE C L Common 28 V dc M Chassis Ground A N 53 V Common A P 53 V Common B R 53 V Common C S Yellow Handle A T Yellow Handle B U Yellow Handle C V CT A W CT B X CT C Y CT Common Z Opt Voltage Sens...

Страница 28: ...es Eaton com cooperpowerseries 2016 Eaton All Rights Reserved Printed in USA Publication No MN280046EN May 2016 KA20480749 REV00 Eaton is a registered trademark All trademarks are property of their re...

Отзывы: