background image

16

NOVA™ STS Single-Tank, Triple-Single, Electronically Controlled Recloser

INSTALLATION AND OPERATION INSTRUCTIONS

  MN280046EN   May 2016

Service information

Service requirements

The NOVA STS recloser requires minimum routine 

inspection to check for physical damage and verify proper 

operation.
It should not be necessary to access the mechanism of the 

NOVA STS recloser. If entry is required, the trip and close 

capacitor must be discharged prior to any contact with the 

mechanism. The capacitor retains an electrical charge, even 

with the control cable disconnected.

Discharge trip and close capacitor

 WARNING 

Personal injury . The trip and close capacitor retains 

an electrical charge . Always discharge the trip and 

close capacitor prior to performing any service on the 

mechanism . Contact with a charged capacitor can result 

in skin burn or electrical shock .

T

3

89 .0

To discharge the trip and close capacitor:
1.  Remove the recloser from service. Refer to the 

Remove recloser from service

 section of this manual. 

Follow standard utility procedures regarding removal of 

the recloser from service. Refer to the section in this 

manual on moving and lifting the NOVA STS recloser.

 WARNING 

Falling equipment . Use the lifting lugs provided and 

follow all locally approved safety practices when lifting 

and mounting the equipment . Lift the unit smoothly 

and do not allow the unit to shift . Improper lifting 

can result in severe personal injury, death, and/or 

equipment damage . 

G106 .3

2.  Loosen bolts that secure the tank and remove the tank 

bottom from the tank top.

CAUTION

Equipment damage . Always unplug the control cable 

from the control prior to discharging the capacitor . 

Failure to do so can result in resistor damage . 

T267 .0

3.  Locate the white discharge button on each actuator 

circuit board. See Figure 15.

Discharge button

LED

Figure 15 .  Location of white discharge button and LED 

discharge indicator on actuator circuit board .

4.  Push and hold in the discharge button. The discharge 

LED will light up and gradually dim as capacitor energy 

is discharged. This will take approximately 45 to 60 

seconds.

5.  When the light completely dims, release the button.
6.  The capacitor is now discharged.

otee:

N

This procedure must be completed on all three actua-

tor boards prior to conducting maintenance.

otee:

N

After approximately twenty minutes, the discharged 

capacitor may have recharged up to 7 volts. If 

this occurs, the Discharge LED will light up if the 

Discharge button is pushed.

7.  Reassemble the tank. Tighten the twelve bolts that 

secure the tank to approximately 7 Nm (5 ft•lbs).

Frequency of inspection

Because these reclosers are applied under widely varying 

operating and climatic conditions, service intervals are 

best determined by the user based on actual operating 

experience. However, solid-insulated, vacuum-interrupting 

reclosers should be inspected every ten years.

Содержание NOVA STS-15

Страница 1: ...NOVA STS 27 and NOVA STS 38 Single Tank Triple Single Electronically Controlled Recloser Installation and Operation Instructions COOPER POWER SERIES Reclosers MN280046EN Effective May 2016 Supersedes...

Страница 2: ...LAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT...

Страница 3: ...ing the recloser 4 Lifting the recloser 4 Remove recloser from service 6 Grounding the NOVA STS recloser 7 RECLOSER OPERATION 8 Vacuum interrupter 8 Mechanism tripping and closing 8 Electronic control...

Страница 4: ...EN May 2016 SERVICE INFORMATION 16 Service requirements 16 Discharge trip and close capacitor 16 Frequency of inspection 16 High potential withstand testing 17 Module flashover service 18 TROUBLESHOOT...

Страница 5: ...igh voltage lines and equipment and support our Safety For Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all...

Страница 6: ...incurred during shipment If damage is discovered file a claim with the carrier immediately Handling and storage Be careful during handling and storage of the recloser to minimize the possibility of da...

Страница 7: ...kV 38 kV Rated Continuous Current 630 A 630 A 630 A 630 A 630 A Short Circuit Current Symmetrical 12 5 kA 12 5 kA 12 5 kA 12 5 kA 12 5 kA Making Current Asymmetrical Peak 32 0 kA 32 0 kA 32 0 kA 32 0...

Страница 8: ...5 Flat Pad 4 hole 800 A maximum 121 4 75 Stud Type 1 125 12 threads 800 A maximum 82 3 25 Table 7 Terminal options continued Description B C NOVA STS 15 110 kV BIL 1008 39 75 733 29 NOVA STS 15 125 kV...

Страница 9: ...t in cuts and abrasions T258 1 3 Install the recloser Install the recloser in the appropriate Eaton s Cooper Power series pole or substation mounting frame See Figure 3 for moving and lifting instruct...

Страница 10: ...es and bypass switches are not required but are highly recommended as they facilitate switching and isolation Disconnect switches for AC sensing and power connections are necessary to isolate the Form...

Страница 11: ...ich will cause death or severe personal injury G108 1 WARNING Hazardous voltage Do not rely on the open position of the yellow operating handle or the contact position indicator it does not ensure tha...

Страница 12: ...ice Eaton recommends transporting Cooper Power series NOVA reclosers in the closed position to maxi mize the operational performance of the unit Grounding the NOVA STS recloser IMPORTANT In pole mount...

Страница 13: ...responds to trip and close commands from the control per the settings programmed in the control Refer to Service Information S280 70 7 Form 6 Triple Single Microprocessor Based Pole Mount Recloser Con...

Страница 14: ...der the sleet hood Note N When the recloser electronically operates to lockout the yellow operating handle will not drop down from under the sleet hood The yellow operating handle remains in the OPEN...

Страница 15: ...that the voltage is zero and the line has been de energized Always follow proper safety practices and use a separate detection method to verify a de energized condition Failure to do so can result in...

Страница 16: ...refer to Tables 9 and 10 These are entered in the System Configuration screen see Figure 12 When programming the Form 6 Triple Single control the PT connection must be set for a wye connection Also t...

Страница 17: ...uch the receptacle connections of the control voltage sensing cable If the recloser is energized and the control voltage sensing cable is disconnected from the recloser or the control a voltage clampe...

Страница 18: ...B phase b white black red black G H C phase a green black orange black J K C phase b blue black black white L M unused unused unused N P See Figure 6 A phase is designated as terminals 1 and 2 B phase...

Страница 19: ...Cable Range 800 A maximum 108 4 25 Flat Pad 2 hole 630 A maximum 114 4 5 Flat Pad 4 hole 800 A maximum 121 4 75 Stud Type 1 125 12 threads 800 A maximum 82 3 25 Table 14 Terminal options continued De...

Страница 20: ...e not included with the brackets Refer to Figure 14 Inboard arrester mounting accessory 374 14 75 min 523 20 5 650 25 5 395 15 5 650 25 5 523 20 5 395 15 5 285 11 25 469 18 5 1030 40 5 107 4 25 394 15...

Страница 21: ...it smoothly and do not allow the unit to shift Improper lifting can result in severe personal injury death and or equipment damage G106 3 2 Loosen bolts that secure the tank and remove the tank bottom...

Страница 22: ...s Solidly ground all equipment Failure to comply can result in death severe personal injury and equipment damage T221 5 CAUTION Radiation At voltages up to the specified test voltages the radiation em...

Страница 23: ...ized service center or your Eaton s Cooper Power series product representative Note N Test results for NOVA reclosers equipped with the internal voltage sensing option will be influenced by the source...

Страница 24: ...LOSE position Check all cables for proper connection Check the condition of the battery located in the control cabinet Refer to Service Information S280 70 7 Form 6 Triple Single Microprocessor Based...

Страница 25: ...se T Yellow Handle B phase P 53 V Common B phase B 53 V dc B phase W CT B phase b Voltage Sensor B phase G Trip C phase K Close C phase U Yellow Handle C phase R 53 V Common C phase C 53 V dc C phase...

Страница 26: ...LK WHT WHT ORG BRN P1 7 CT COM Optional Voltage Sensor VTC 28 V dc NO TRIP Yellow Handle CLOSE Common 28 V dc 53 V Common 53 V dc YEL RED P2 2 MS3 yellow handle NC Actuator Circuit Board P2 3 MS2 52b...

Страница 27: ...K CLOSE C L Common 28 V dc M Chassis Ground A N 53 V Common A P 53 V Common B R 53 V Common C S Yellow Handle A T Yellow Handle B U Yellow Handle C V CT A W CT B X CT C Y CT Common Z Opt Voltage Sens...

Страница 28: ...es Eaton com cooperpowerseries 2016 Eaton All Rights Reserved Printed in USA Publication No MN280046EN May 2016 KA20480749 REV00 Eaton is a registered trademark All trademarks are property of their re...

Отзывы: