NOVA™ STS Single-Tank, Triple-Single, Electronically Controlled Recloser

INSTALLATION AND OPERATION INSTRUCTIONS

  MN280046EN   May 2016

4. 

Ground the reclosers and mounting hanger

. Make 

the ground connection to the ground connector in 

accordance with approved utility standards. The ground 

connector is located on the back of the mechanism 

housing. See Figure 4 for ground connector location. 

The ground clamp accepts #10 to #2 stranded cables. 

See Figures 8 and 9 for recommended grounding for 

the NOVA STS recloser.

Ground

Figure 4 .  NOVA STS recloser ground and receptacles .

5. 

Install the control

. Refer to 

Service Information S280-

70-7 Form 6 Triple-Single, Microprocessor-Based Pole 

Mount Recloser Control Installation and Operation 

Instructions

. Make sure the control cable is connected 

between the control and the recloser, the control is 

properly programmed for the planned installation, and 

the control is grounded.
To ensure proper installation of this cable, securely 

fasten the aluminum cable coupler ring (Figure 5).

Figure 5 .  Cable with aluminum cable coupler ring .

 CAUTION 

Equipment damage . Check the heater input power label 

located near the receptacle on the recloser to insure 

the input power matches the heater rating . Failure 

to comply can result in recloser misoperation and 

equipment damage . 

T354 .0

6. 

Connect heater power cable

. The recloser tank 

includes either a 120 Vac or 240 Vac heater for humidity 

control. Connect the two-wire input cable to the 

recloser input receptacle.

7. 

Make bypass and disconnect provisions in 

accordance with approved utility standards

: the 

recloser contacts are open, the bypass switches are 

closed, and the disconnected switches are open.

otee:

N

Disconnect switches and bypass switches are 

not required, but are highly recommended as 

they facilitate switching and isolation. Disconnect 

switches for AC sensing and power connections are 

necessary to isolate the Form 6-TS control for testing 

and servicing.

 CAUTION 

Equipment damage . Do not adjust or rotate bushing 

terminals . The bushing terminals are factory-calibrated 

to meet the continuous current requirement of the 

switchgear . Adjusting or rotating the bushing terminals 

can damage the encapsulated interrupter, resulting in 

equipment damage or personal injury . 

T270 .0

CAUTION

Equipment damage may occur if torque values are 

exceeded . 

T370 .0

8. 

Make the high-voltage line connections

.

A. Connect high-voltage lines to recloser bushings 

terminals. Refer to Figure 6 for terminal identification 

of the NOVA STS recloser. Terminal connection to 

copper conductors only are recommended.
To rotate a flat-pad or eyebolt bushing terminal prior 

to connecting power line leads, loosen the pinch 

bolt on the terminals. After rotating the terminal, 

retighten the pinch bolt as follows: torque 3/8-16 

pinch bolts to 20—23 Nm (15—17 ft•lbs); torque 

1/2-13 pinch bolts to 39—42 Nm (29—31 ft•lbs).
Recommended torque for bushing terminal to line 

connection of 45-50 ft•lbs.

IMPORTANT

The default connections use the horizontal bushing as the 

source side and vertical bushing as the load side. Also, the 

horizontal bushing may be used as the load side and vertical 

bushing as the source side. Note that reversing the source 

and load bushings has no effect on overcurrent protection 

but may require setting or wiring changes to the control for 

correct metering. 

 

If equipped with internal voltage sensors, the horizontal 

bushings (1, 3, 5) must be connected to the source. The 

internal voltage sensors cannot monitor source-side voltage 

when the NOVA STS recloser is in the OPEN position if the 

horizontal bushings are connected to the load.

Содержание NOVA STS-15

Страница 1: ...NOVA STS 27 and NOVA STS 38 Single Tank Triple Single Electronically Controlled Recloser Installation and Operation Instructions COOPER POWER SERIES Reclosers MN280046EN Effective May 2016 Supersedes...

Страница 2: ...LAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT...

Страница 3: ...ing the recloser 4 Lifting the recloser 4 Remove recloser from service 6 Grounding the NOVA STS recloser 7 RECLOSER OPERATION 8 Vacuum interrupter 8 Mechanism tripping and closing 8 Electronic control...

Страница 4: ...EN May 2016 SERVICE INFORMATION 16 Service requirements 16 Discharge trip and close capacitor 16 Frequency of inspection 16 High potential withstand testing 17 Module flashover service 18 TROUBLESHOOT...

Страница 5: ...igh voltage lines and equipment and support our Safety For Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all...

Страница 6: ...incurred during shipment If damage is discovered file a claim with the carrier immediately Handling and storage Be careful during handling and storage of the recloser to minimize the possibility of da...

Страница 7: ...kV 38 kV Rated Continuous Current 630 A 630 A 630 A 630 A 630 A Short Circuit Current Symmetrical 12 5 kA 12 5 kA 12 5 kA 12 5 kA 12 5 kA Making Current Asymmetrical Peak 32 0 kA 32 0 kA 32 0 kA 32 0...

Страница 8: ...5 Flat Pad 4 hole 800 A maximum 121 4 75 Stud Type 1 125 12 threads 800 A maximum 82 3 25 Table 7 Terminal options continued Description B C NOVA STS 15 110 kV BIL 1008 39 75 733 29 NOVA STS 15 125 kV...

Страница 9: ...t in cuts and abrasions T258 1 3 Install the recloser Install the recloser in the appropriate Eaton s Cooper Power series pole or substation mounting frame See Figure 3 for moving and lifting instruct...

Страница 10: ...es and bypass switches are not required but are highly recommended as they facilitate switching and isolation Disconnect switches for AC sensing and power connections are necessary to isolate the Form...

Страница 11: ...ich will cause death or severe personal injury G108 1 WARNING Hazardous voltage Do not rely on the open position of the yellow operating handle or the contact position indicator it does not ensure tha...

Страница 12: ...ice Eaton recommends transporting Cooper Power series NOVA reclosers in the closed position to maxi mize the operational performance of the unit Grounding the NOVA STS recloser IMPORTANT In pole mount...

Страница 13: ...responds to trip and close commands from the control per the settings programmed in the control Refer to Service Information S280 70 7 Form 6 Triple Single Microprocessor Based Pole Mount Recloser Con...

Страница 14: ...der the sleet hood Note N When the recloser electronically operates to lockout the yellow operating handle will not drop down from under the sleet hood The yellow operating handle remains in the OPEN...

Страница 15: ...that the voltage is zero and the line has been de energized Always follow proper safety practices and use a separate detection method to verify a de energized condition Failure to do so can result in...

Страница 16: ...refer to Tables 9 and 10 These are entered in the System Configuration screen see Figure 12 When programming the Form 6 Triple Single control the PT connection must be set for a wye connection Also t...

Страница 17: ...uch the receptacle connections of the control voltage sensing cable If the recloser is energized and the control voltage sensing cable is disconnected from the recloser or the control a voltage clampe...

Страница 18: ...B phase b white black red black G H C phase a green black orange black J K C phase b blue black black white L M unused unused unused N P See Figure 6 A phase is designated as terminals 1 and 2 B phase...

Страница 19: ...Cable Range 800 A maximum 108 4 25 Flat Pad 2 hole 630 A maximum 114 4 5 Flat Pad 4 hole 800 A maximum 121 4 75 Stud Type 1 125 12 threads 800 A maximum 82 3 25 Table 14 Terminal options continued De...

Страница 20: ...e not included with the brackets Refer to Figure 14 Inboard arrester mounting accessory 374 14 75 min 523 20 5 650 25 5 395 15 5 650 25 5 523 20 5 395 15 5 285 11 25 469 18 5 1030 40 5 107 4 25 394 15...

Страница 21: ...it smoothly and do not allow the unit to shift Improper lifting can result in severe personal injury death and or equipment damage G106 3 2 Loosen bolts that secure the tank and remove the tank bottom...

Страница 22: ...s Solidly ground all equipment Failure to comply can result in death severe personal injury and equipment damage T221 5 CAUTION Radiation At voltages up to the specified test voltages the radiation em...

Страница 23: ...ized service center or your Eaton s Cooper Power series product representative Note N Test results for NOVA reclosers equipped with the internal voltage sensing option will be influenced by the source...

Страница 24: ...LOSE position Check all cables for proper connection Check the condition of the battery located in the control cabinet Refer to Service Information S280 70 7 Form 6 Triple Single Microprocessor Based...

Страница 25: ...se T Yellow Handle B phase P 53 V Common B phase B 53 V dc B phase W CT B phase b Voltage Sensor B phase G Trip C phase K Close C phase U Yellow Handle C phase R 53 V Common C phase C 53 V dc C phase...

Страница 26: ...LK WHT WHT ORG BRN P1 7 CT COM Optional Voltage Sensor VTC 28 V dc NO TRIP Yellow Handle CLOSE Common 28 V dc 53 V Common 53 V dc YEL RED P2 2 MS3 yellow handle NC Actuator Circuit Board P2 3 MS2 52b...

Страница 27: ...K CLOSE C L Common 28 V dc M Chassis Ground A N 53 V Common A P 53 V Common B R 53 V Common C S Yellow Handle A T Yellow Handle B U Yellow Handle C V CT A W CT B X CT C Y CT Common Z Opt Voltage Sens...

Страница 28: ...es Eaton com cooperpowerseries 2016 Eaton All Rights Reserved Printed in USA Publication No MN280046EN May 2016 KA20480749 REV00 Eaton is a registered trademark All trademarks are property of their re...

Отзывы: