www.eaton.com
Network
Management Card
(Network-MS)
User Manual
Network Management Card
– User Manual
34003991XT_EN/JC
Page
74/143
The high alarm disappears when the value drops below the High threshold - Hysteresis value
The low alarm disappears when the value returns above the Low thr Hysteresis value
Input #1
and
Input #2
: Enter an identifier corresponding to the acquired contact (e.g.: rack door, air conditioning,
generator unit, etc.). Max. length is 28 characters.
When closed and when open
: are the names associated to the two contact positions. (e.g.: "open" and "closed"
for a door, "On" and "Off" for a generator).
Each status change triggers a notification if enabled.
When the
Notification
box is enabled, the following functions are activated for each event selected:
•
display in the
list of current alarms
•
Consideration in the
UPS log
•
SNMP trap generation
•
notification by e-mail (if the Environment sensor notification option is enabled in the
e-mail notification
page)
The list of messages is provided in the
appendix
System shutdown
can be triggered for each notification if this option is enabled. If notification is disabled, the
Shutdown option cannot be used.