www.eaton.com
Network
Management Card
(Network-MS)
User Manual
Network Management Card
– User Manual
34003991XT_EN/JC
Page
31/143
4.2.1.3 Viewing the modules (Only with Eaton MX Frame UPS)
•
Click on
UPS Modules
scroll list to view the information about the UPS modules.
•
Active sources:
x UPS + y UPS redundant :
x indicates the minimal number of UPS necessary to power the load,
y indicates the number of UPS in redundancy.
The addition of these 2 values is the total number of available UPS.
•
The
Minimum redundant UPS modules to trigger alarm
can be configured from this page. The button
Save
makes the card setting the parameter into the UPS. A warning message informs the user about the
consequences of this parameters modification.
The redundancy lost can generate Email notification (if set in the email notification page) and SNMP
trap. It can also be used by IPP for server protection criteria.
•
The
Module Nr
gives the location of the module in the UPS.