Read also the Special Conditions for Safe Use (below) for any additional or more
specific information.
Special Conditions for Safe Use
1. The equipment shall only be powered from supplies conforming to IEC 61158
2. When a Trunk Surge Module is fitted, the power input circuit will not withstand
a 500V a.c. isolation test to earth. This must be taken into account during
installation.
3. When one or more Spur Surge Modules are fitted, the spur outputs will not
withstand a 500V a.c. isolation test to earth. This must be taken into account
during installation.
7 .3
Inspection and maintenance
a) Inspection and maintenance should be carried out in accordance with
European, national and local regulations which may refer to the IEC standard
IEC 60079-17.
In addition specific industries or end users may have specific requirements which
should also be met.
b) Care should be taken to limit dust accumulation on the exterior of the
apparatus to a depth not exceeding 5mm.
c) If the outer enclosure of the apparatus needs to be cleaned, this should be
done with a non-electrostatic generating cloth lightly moistened by a dilute
mixture of detergent in water.
d) Maintenance of internal components while powered is limited to those actions
permitted in Section 5 of this manual.
7 .4
Repair
The modules used in this product cannot be repaired by the user and must be
replaced with an equivalent certified product.
7 .5
Marking
Each certified component is marked in compliance with the Directive and CE marked
with the Notified Body Identification Number.
This information applies to products manufactured during or after the year 2014.
For full certification information visit www .mtl-inst .com/support/certificates/
Products labels (showing certification information)
Enclosure marking (Made in England)
Module Carrier