Technical data 

Part numbers 

 

Part number 

Description 

Detector 

MPAD-C-A 12-24V 

Ceiling Microwave presence/absence detector 12-24V AC/DC 

Accessories 

SB-C A 

Surface mounting box 

 

HHIR-PROG 

Programming IR handset 

 

HHIR-LCD-PROG 

Universal LCD IR handset 

Dimensions 

See diagrams opposite 

Weight 

0.15kg 

Supply Voltage 

Min 11.5VDC max 36VDC, min 
10VAC max 26.5VAC 

Load 

Low voltage supply with open collector 
output, rating 50mA, 30VDC max 

Power consumption 

On 1100mW, Off 767mW 

Terminal Capacity 

2.5mm

2

 

Temperature 

-10ºC to 35ºC 

Humidity 

5 to 95% non-condensing 

Material (casing) 

Flame retardant ABS and PC/ABS 

Type 

Class 2 

Safety 

The microwave radiation emitted by 
these units is extremely low power 
and complies with ANSI standard  
“IEEEC95.1-1999 Standard for Safety 
Levels with Respect to Human 
Exposure to Radio Frequency 
Electromagnetic Fields 3kHz 
300GHz.” 

 
IP rating 

IP40 

Compliance 

EMC-2014/30/EU 
LVD-2014/35/EU 

 

The allowable frequency of operation of this product is different depending on region. Please select the correct order 
code using the table below. 

Suffix 

Region 

Frequency 

blank 

UK, China, India, Middle East, Malaysia, Hong Kong, Singapore 

10.587GHz 

-R2 

Australia and all of Europe except: UK, France, Portugal, Germany, Switzerland, Austria, Slovak Republic, Republic of Ireland 

10.525GHz 

-R3 

France, Portugal, Switzerland 

9.900GHz 

-R4 

Germany, Austria, Slovak Republic 

9.350GHz 

-R5 

Republic of Ireland 

10.41GHz 

Microwave frequency compatibility 

MPAD-C-A 12-24V 

SB-C A 

IMPORTANT NOTICE! 

This device should be installed by a qualified electrician in 
accordance with the latest edition of the IEE Wiring 
Regulations and any applicable Building Regulations. 

Ref:  #WD825 Issue 2 

Due to our policy of continual product improvement Eaton reserves the right to alter the specification of this product without prior notice. 

Eaton Lighting Systems 

Usk House, Lakeside 
Llantarnam Park, 
Cwmbran, NP44 3HD, UK 
Tel: 

+44 (0)1633 838088 

Fax:   +44 (0)1633 867880 
[email protected] 
www.eatonlightingsystems.com  

Ref:  9850-000615-00 

#WD825    Issue 4.0 

Содержание MPAD-C-A

Страница 1: ...pring Power Input Output Connector Switch Input Connector Front features The MPAD C A 12 24V Microwave presence detector provides automatic control of low voltage loads including lighting and BMS syst...

Страница 2: ...d In either case sensitivity to movement of the Microwave sensor can be adjusted using the Sensitivity parameter HINT To assist in setting the Sensitivity turn on the Walk Test LED which will flash re...

Страница 3: ...when movement is detected The unit is now ready for programming Power up test procedure Choosing a Suitable Location The detector should be sited so that the occupants of the room fall inside the det...

Страница 4: ...before affixing the cable clamp The clamp MUST clamp the outer sheath s only Bend cores as shown Wire stripping details Flush fixing Surface fixing Head locking 1 3 2 4 Hole 30mm MAX 1 2 Remove metal...

Страница 5: ...old the R Read button for more than 1 second The handset will click every time a parameter is received The device will show multiple flashes of its LED All of the values will be shown against the para...

Страница 6: ...llows the output to turn off when movement ceases but must be manually turned on first Shift Use this button to select the settings in red and blue signified by the Shift 1 and Shift 2 LEDs Number of...

Страница 7: ...ction to be implemented with a lux off level set When the button is pressed the lights will go on regardless of ambient light level However if there is sufficient ambient light they will turn off agai...

Страница 8: ...allowable frequency of operation of this product is different depending on region Please select the correct order code using the table below Suffix Region Frequency blank UK China India Middle East M...

Отзывы: