Installation 

Absence detection 

 

To use absence detection a retractive (momentary) switch must be connected between the 2 terminals on the 
diagram. 

 

The unit ships with presence detection as default. To change to absence detection, press and release the external 
switch 5 times within the first minute of power up. The LED will turn on solid for 30 seconds to indicate absence 
mode has been selected.  

 

To change back to presence detection, repeat the above procedure—the LED will flash for 30 seconds to indicate 
presence mode has been selected. 

Note: 

the above adjustments can also be made using the HHIR-PROG or HHIR-LCD-PROG handsets. See 

When power is applied to the unit, the load will turn on immediately. 
Set the timeout to 10 seconds, vacate the room or remain very still and wait for the load to switch off . 
Check that the load switches on when movement is detected. 
The unit is now ready for programming. 

Power-up test procedure 

Choosing a Suitable Location 

The detector should be sited so that the occupants of the room fall inside the detection pattern shown opposite). 

 

Avoid positioning the unit where direct sunlight may enter the sensor element.  

 

Do not site the sensor within 1m of any lighting, forced air heating or ventilation. 

 

Do not fix the sensor to an unstable or vibrating surface. 

 

Avoid metallic objects directly in front of the sensor head.  

Input and switch connections 

OUT

+

COM

AC Supply

10VAC - 26.5VAC

MOMENTARY PUSH TO

MAKE SWITCH

Optional for presence,

mandatory for absence detection

DC Supply

11.5VDC - 36VDC

OR

-

+

INPUT & SWITCH
CONNECTIONS

OUT

+

COM

LOAD

INTERNAL

RELAY

LOAD CONNECTIONS
-PRM-LV
-PRM-LV/GOLD

OUT

+

COM

INTERNAL OPEN

COLLECTOR

TRANSISTOR

LOAD CONNECTIONS
-PRM-LV/OC

LOAD

OUT

+

COM

AC Supply

10VAC - 26.5VAC

MOMENTARY PUSH TO

MAKE SWITCH

Optional for presence,

mandatory for absence detection

DC Supply

11.5VDC - 36VDC

OR

-

+

INPUT & SWITCH
CONNECTIONS

OUT

+

COM

LOAD

INTERNAL

RELAY

LOAD CONNECTIONS
-PRM-LV
-PRM-LV/GOLD

OUT

+

COM

INTERNAL OPEN

COLLECTOR

TRANSISTOR

LOAD CONNECTIONS
-PRM-LV/OC

LOAD

Load connections 

Содержание MPAD-C-A

Страница 1: ...pring Power Input Output Connector Switch Input Connector Front features The MPAD C A 12 24V Microwave presence detector provides automatic control of low voltage loads including lighting and BMS syst...

Страница 2: ...d In either case sensitivity to movement of the Microwave sensor can be adjusted using the Sensitivity parameter HINT To assist in setting the Sensitivity turn on the Walk Test LED which will flash re...

Страница 3: ...when movement is detected The unit is now ready for programming Power up test procedure Choosing a Suitable Location The detector should be sited so that the occupants of the room fall inside the det...

Страница 4: ...before affixing the cable clamp The clamp MUST clamp the outer sheath s only Bend cores as shown Wire stripping details Flush fixing Surface fixing Head locking 1 3 2 4 Hole 30mm MAX 1 2 Remove metal...

Страница 5: ...old the R Read button for more than 1 second The handset will click every time a parameter is received The device will show multiple flashes of its LED All of the values will be shown against the para...

Страница 6: ...llows the output to turn off when movement ceases but must be manually turned on first Shift Use this button to select the settings in red and blue signified by the Shift 1 and Shift 2 LEDs Number of...

Страница 7: ...ction to be implemented with a lux off level set When the button is pressed the lights will go on regardless of ambient light level However if there is sufficient ambient light they will turn off agai...

Страница 8: ...allowable frequency of operation of this product is different depending on region Please select the correct order code using the table below Suffix Region Frequency blank UK China India Middle East M...

Отзывы: