Basic programming 

Parameter 
Name 

Default 
Value 

0 

1 

2 

3 

HHIR-PROG Handset 
Graphics 

Description 

 

 

Button Activation 

 

 

On 

 

On 

 

 

 

 

Turn lights on. 

Off  

 

Off 

 

 

 

 

Turn lights off. 

Walk test 

Off 

On 

Off 

 

 

 

When set to On this causes a red LED to flash on 
the sensor when it detects movement. Use this 
feature to check for adequate sensitivity levels. 

Time Out 
(Time 
adjustment) 

20 mins 

1, 10 & 
20 
minutes 

5, 15 & 
30 
minutes 

10 
seconds 

 

 

Once the detector is turned on, this value sets 
how long the lights will stay on once movement 
has ceased. 

Lux on 
level 
(Switch 
level on) 

2, 5 & 7 

4, 6 & 9   

 

 

Lux level setting to prevent the luminaires being 
switched on if the ambient light level is sufficient 
(adjustable between 1 and 9). The luminaires will 
always be switched on at level 9.  

Lux off 
level 
(Switch 
level off) 

2, 5 & 7 

4, 6 & 9   

 

 

Lux level setting to switch the luminaires off during 
occupancy if the ambient light level goes above 
the setting (adjustable between 1 and 9). Level 9 
will always keep the lights on. This setting can be 
used for “window row switching”. 

Note: the Lux Off Level value must always be 
greater than the Lux On Level value. 

Sensitivity 

1, 5 & 9 

3, 6 & 8   

 

 

Sensitivity level for detecting movement. 
1 = low sensitivity 
9 = high sensitivity 

Defaults 

 

 

 

 

 

Returns the unit to the default settings. 

Presence / 
Absence 

Presence  Presence  Absence   

 

 

Presence mode allows the output to turn on when 
movement is detected and off when movement 
ceases. Absence mode allows the output to turn 
off when movement ceases, but must be manually 
turned on first. 

Shift 

 

 

 

 

 

 

Use this button to select the settings in red and 
blue signified by the ‘Shift 1’ and ‘Shift 2’ LEDs 

Number of Shift key presses 

The functionality of the MPAD-C-A 12-24V is controlled by a number of parameters which 
can be changed or programmed by any of the following devices: 

 

HHIR-PROG

 Infrared Handset. See below for programmable functions. 

 

HHIR-LCD-PROG 

Infrared Handset (with LCD). See user guide for full 

programming details. 

For most basic programming operations the HHIR-PROG handset can be used and the following 
procedures are based on using this device. 
Point the handset at the Sensor and send the required programming commands to the unit as shown 
below. 
Valid commands will be indicated by a red LED flash. See page 1 for details of other LED responses. 

SHIFT 1  SHIFT 2 

SHIFT 1  SHIFT 2 

SHIFT 1  SHIFT 2 

SHIFT 1  SHIFT 2 

What if the load does not turn ON? 

 

Check that the supply to the circuit is good.  

 

If the detection range is smaller than expected, check the diagram on page 2. Adjusting the angle of the sensor head 
slightly may improve the detection range. If still reduced it may be compromised by the ceiling construction / 
material. Add the supplied 20mm spacer ring. See page 4 for fitting details. 

HINT: 

The Walk Test LED function can be used to check that the unit is detecting movement in the required area. 

What if the load does not turn OFF? 

 

Ensure that the area is left unoccupied for longer than the Time Out Period. 

 

Ensure that the sensor is not adjacent to circulating air, heaters or lamps. 

Fault finding 

Содержание MPAD-C-A

Страница 1: ...pring Power Input Output Connector Switch Input Connector Front features The MPAD C A 12 24V Microwave presence detector provides automatic control of low voltage loads including lighting and BMS syst...

Страница 2: ...d In either case sensitivity to movement of the Microwave sensor can be adjusted using the Sensitivity parameter HINT To assist in setting the Sensitivity turn on the Walk Test LED which will flash re...

Страница 3: ...when movement is detected The unit is now ready for programming Power up test procedure Choosing a Suitable Location The detector should be sited so that the occupants of the room fall inside the det...

Страница 4: ...before affixing the cable clamp The clamp MUST clamp the outer sheath s only Bend cores as shown Wire stripping details Flush fixing Surface fixing Head locking 1 3 2 4 Hole 30mm MAX 1 2 Remove metal...

Страница 5: ...old the R Read button for more than 1 second The handset will click every time a parameter is received The device will show multiple flashes of its LED All of the values will be shown against the para...

Страница 6: ...llows the output to turn off when movement ceases but must be manually turned on first Shift Use this button to select the settings in red and blue signified by the Shift 1 and Shift 2 LEDs Number of...

Страница 7: ...ction to be implemented with a lux off level set When the button is pressed the lights will go on regardless of ambient light level However if there is sufficient ambient light they will turn off agai...

Страница 8: ...allowable frequency of operation of this product is different depending on region Please select the correct order code using the table below Suffix Region Frequency blank UK China India Middle East M...