Advanced programming 

Parameter Name   Default Value   Range / Options   Description  

HHIR-

PROG 

HHIR-LCD

-PROG 

Detector Parameters

 

Walk Test LED 

Off 

On or Off 

When set to On this causes a red LED to flash on the sensor when it detects 

movement. Use this feature to check for adequate sensitivity levels. 

   

Time Out 

(Time adjustment) 

20 minutes 

0-99 minutes 

Once the detector is turned on, this value sets how long the lights will stay on once 

movement has ceased. Select 0 for 10 second delay – use for commissioning only.  

   

Manual Time Out 

10 minutes 

0-99 minutes 

When a manual operation occurs, either via the switch input or the infrared, it 

invokes the timeout period. 

Example 1: a detector in presence mode has a detector timeout of 15 minutes and 

a manual timeout of 3 minutes. When the user leaves the room they press the off 

button. The sensor will revert to automatic after 3 minutes, and then walking back 

in the room will turn the lights on. 

Example 2: using the settings above, the user turns the lights off (say for a 

presentation) but stays in the room. Every time a movement is detected, the 

manual timeout period is re-triggered, but when it doesn’t pick up for the short 

timeout period, the sensor will timeout and revert to automatic. This means the 

lights may turn on inadvertently during the presentation, if the occupants are still 

for the manual timeout period, so adjust the timing carefully. 

   

Sensitivity On 

1 (min) to 9 (max) 

Sensitivity level for detecting movement when the detector is already on.  

*HHIR-

PROG sets Sensitivity On and Off to the same value. 

*

   

Sensitivity Off 

1 (min) to 9 (max) 

Sensitivity level for detecting movement when the detector is off.  

*HHIR-PROG 

sets Sensitivity On and Off to the same value.

 

*

   

Lux time 

0 (disabled) 
1-99 minutes 

If the detector measures the lux level and decides that the output needs switching 
on or off as a consequence, the lux time must elapse first. If at any time during the 
timed delay the lux change reverses then the process is cancelled. Lux Time 
enables absence detection to be implemented with a lux off level set. When the 
button is pressed, the lights will go on, regardless of ambient light level. However, 
if there is sufficient ambient light, they will turn off again after the Lux Time. 

Note 

that whenever the an external switch is pressed, whether in absence or presence 
mode, if the lights were out because of the lux level, they will be immediately 
turned on again for at least the Lux Time.

 

   

Power Up State 

On 

On or Off 

Select No for a 30 second delay on start up. If Yes is selected,   there will be no 

delay on start up and the detector will always  power up detecting. 

   

Inhibit 

4 seconds 

1 to 999 seconds 

When the detector turns off, a delay is instigated to prevent retriggering. In certain 

circumstances this delay may not be enough. This parameter allows the delay to 

be changed. 

   

Factory default 

Restores factory default settings 

   

User Modes

 

Override On 

If the lights are off, sending the IR command will turn them on immediately and 

revert to automatic operation using the manual timeout period . 

   

Override Off 

If the lights are on, sending the IR command will turn them off immediately. After 

the manual timeout period (described above), the sensor will revert to automatic. 

   

Cancel 

Cancels the on or off override, returning the detector to normal operation.  

   

Switching functions

 

Detection Mode 

Presence 

Presence or 
Absence 

Presence mode allows the output to turn on when movement is detected and off 
when movement ceases. Absence mode allows the output to turn off when 
movement ceases, but must be manually turned on first. 

 

 

Lux on level 

(Switch level on) 

1 to 9 
For a higher 
resolution a scale 
of 101-199 is 
available 

Sets a minimum light level below which the Microwave sensor is enabled, allowing 
lights to be turned on by movement. 

Note: the Lux Level Off value must always be greater than the Lux Level On value. 

   

Lux off level 

(Switch level off) 

1 to 9 
For a higher 
resolution a scale 
of 101-199 is 
available 

Sets a maximum light level above which the Microwave sensor is disabled, 
preventing lights from being turned on by movement. 

   

Switch Input Modes

 

1 position switch 
together 

Default 

Short press on, long press off.  

   

2 position switch 
together 

Short press on, short press off.  

   

Содержание MPAD-C-A

Страница 1: ...pring Power Input Output Connector Switch Input Connector Front features The MPAD C A 12 24V Microwave presence detector provides automatic control of low voltage loads including lighting and BMS syst...

Страница 2: ...d In either case sensitivity to movement of the Microwave sensor can be adjusted using the Sensitivity parameter HINT To assist in setting the Sensitivity turn on the Walk Test LED which will flash re...

Страница 3: ...when movement is detected The unit is now ready for programming Power up test procedure Choosing a Suitable Location The detector should be sited so that the occupants of the room fall inside the det...

Страница 4: ...before affixing the cable clamp The clamp MUST clamp the outer sheath s only Bend cores as shown Wire stripping details Flush fixing Surface fixing Head locking 1 3 2 4 Hole 30mm MAX 1 2 Remove metal...

Страница 5: ...old the R Read button for more than 1 second The handset will click every time a parameter is received The device will show multiple flashes of its LED All of the values will be shown against the para...

Страница 6: ...llows the output to turn off when movement ceases but must be manually turned on first Shift Use this button to select the settings in red and blue signified by the Shift 1 and Shift 2 LEDs Number of...

Страница 7: ...ction to be implemented with a lux off level set When the button is pressed the lights will go on regardless of ambient light level However if there is sufficient ambient light they will turn off agai...

Страница 8: ...allowable frequency of operation of this product is different depending on region Please select the correct order code using the table below Suffix Region Frequency blank UK China India Middle East M...

Отзывы: