Eaton mMINT Скачать руководство пользователя страница 6

6

mMINT—Modbus Translator Module— 

installation and use

 

EATON CORPORATION

 www.moeller.net/en/support 

05/10 AWB1230-1622

Effective May 2010

Register access configurations

The following parameters can be set as configurations for  

register access:

• 

Register 42001/425347 (07D0

16

/6300

16

Reading a register group with invalid registers

When non-zero (factory default value), any attempt to access a 

group of data objects that contain an invalid object will result in  

an illegal data object exception code 02 . See Section 6 .
When the register is set to zero, however, the mMINT will respond 

to a group of objects with data contained in the valid objects of the 

group along with an illegal value that is set to 0000

16

 .

• 

Register 42002/425346 (07D1

16

/6301

16

Configuration of the 32-bit IEEE data format

When non-zero (factory default), the low floating point word is first 

in the Modbus register space .
When the register is set to zero, the high floating point word is first 

in the Modbus register space .

• 

Register 42002/425347 (07D1

16

/6302

16

Sequence of the fixed point register

The register is used to configure 32-bit fixed point and 64-bit word 

order . When non-zero (factory default), the low word is first in the 

Modbus register space .
When register 42003/425347 (07D2

16

/6302

16

) is set to zero, 

however, the fixed point and energy high order word is first in the 

Modbus register space .
Configuring any or all registers 42001/425345 through 42003/425347 

(07D0

16

/6300

16

 through 07D2

16

/6302

16

) is accomplished using a write 

function code 16 (10

16

) to mMINT diagnostic address 247 or 248 . 

otee:

N

mMINT SW2-1 must be properly set . See Section 5 and 

Table 5

 .

Control commands

A set of registers is reserved for control commands . They begin 

at register 42901/425089 (0B54

16

/6200

16

) and extend through 

42903/425091 (0B56

16

/6202

16

) . These three registers include ‘slave 

action numbers .’ Their meaning is listed in 

Table 6

 . The format of 

the data is shown in 

Figure 5

 . These three registers must be written 

in one Modbus transaction .
For safety reasons, a 1’s complement must be formed to correspond 

with each slave action byte (1 to 0 and 0 to 1) . As illustrated in 

Figure 5

 . If the slave action request is successfully acknowledged 

by the trigger, the mMINT returns a normal function code 16 (10

16

response to the Modbus master . The Modbus master may further 

determine if the INCOM product completed the slave action function 

successfully by interrogating the product, for example, by reading  

its status .
If the INCOM product does not acknowledge the slave action 

request, the mMINT returns an exception code 04 . If the ‘slave 

action number’ and its 1’s complement are invalid, the mMINT 

responds to the Modbus master with a data value illegal exception 

code 03 . 

Figure 5. Control to INCOM Product Data Format

Data format for energy values

Energy objects in the mMINT are supported in two-register fixed 

point object format and a four-register power/mantissa format . 

These objects do not support IEEE floating point format .
The two-register format is presented in kilowatt hours (kWh)  

or in watthours . 
The four-register format indicates the energy values in watthours . 

These are register 3 through register 0 . Register 3 is of the highest 

value and register 0 is of the lowest value .
Register 3 high byte contains a coefficient . Register 3 low byte 

contains a Mantissa Multiplier value .
Register 2 through register 0 contains a 48-bit energy mantissa value 

in watthours . 
The data format of these four registers is illustrated in 

Figure 6

 .

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Register 42901/425089 (0B54

16

/6200

16

)

Slave Action Byte 1

Slave Action Byte 0

Register 42902/425090 (0B55

16

/6201

16

)

1’s Complement of Slave Action Byte 0

Slave Action Byte 2

Register 42903/425091 (0B56

16

/6202

16

)

1’s Complement of Slave Action Byte 2

1’s Complement of 

Slave Action Byte 1

Содержание mMINT

Страница 1: ...EDS 4 Modbus RS 485 network Rx LED green 5 Modbus RS 485 network Tx LED green 5 INCOM network Rx LED green 5 INCOM network Tx LED green 5 Status LED green 5 INCOM 100 load resistance dip switch SW1 5 Modbus RS 485 baud rate dip switch SW2 5 mMINT diagnostics address SW2 5 Modbus 121 load resistance dip switch SW3 5 Section 6 Network communication protocols 5 Overview 5 Function codes 5 Configuring...

Страница 2: ...tor 4 Table 2 INCOM Connector J2 Pins 4 Table 3 Modbus RS 485 J3 Pins 4 Table 4 RS 485 Baud Rate Switches Normal 5 Table 5 RS 485 Baud Rate Switches Diagnostics 5 Table 6 Diagnostic Sub Function Numbers 7 Table 7 Troubleshooting Guide 7 Table 8 Modbus Register Map in Register Number Order 9 Table 9 Modbus Register Map in Functional Order 10 Table 10 Primary Status Code Definitions 11 Table 11 Seco...

Страница 3: ...tallation checkout safe operation or maintenance m WARNING DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENERGIZED DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING ALWAYS FOLLOW SAFETY PROCEDURES EATON IS NOT LIABLE FOR THE MISAPPLICATION OR MISINSTALLATION OF ITS PRODUCTS Module ...

Страница 4: ...e 2 Table 2 INCOM Connector J2 Pins Pin Number Input Output Signal 1 INCOM carrier network 2 INCOM carrier network 3 Shield Connect shield to ground at master device end only Interconnect shielding where devices are daisy chained J3 J1 J2 RS 485 Modbus A B COM SHD 4 25 108 0 3 54 89 9 24 125 Vdc 120 Vac Shield INCOM Modbus connections Modbus RS 485 connector The four pole connector is for the Modb...

Страница 5: ...Off X X Normal On X X Modbus 121 load resistance dip switch SW3 This switch should be moved to the ON position only when it is the last device in a chain of devices or if it is a single device Section 6 Network communication protocols The INCOM communication network for the mMINT is based on a master slave protocol The mMINT is the master on the INCOM network For further information please see Ref...

Страница 6: ...mbers Their meaning is listed in Table 6 The format of the data is shown in Figure 5 These three registers must be written in one Modbus transaction For safety reasons a 1 s complement must be formed to correspond with each slave action byte 1 to 0 and 0 to 1 As illustrated in Figure 5 If the slave action request is successfully acknowledged by the trigger the mMINT returns a normal function code ...

Страница 7: ... 10Coefficient Table 6 Diagnostic Sub Function Numbers Sub function No Decimal Name In the Query Use 0 echo query or INCOM addr 1 restart communications mMINT or INCOM addr 4 force listen mMINT or INCOM addr 10 clear slave counters mMINT or INCOM addr 11 UART bus message count mMINT or INCOM addr 12 UART communication error count mMINT or INCOM addr 13 slave exception error count mMINT or INCOM ad...

Страница 8: ...to insert 100 ohm terminating resistor on the last module of the INCOM network 8 Set up switch SW2 to select data transfer rate on the Modbus network 9 Set up switch SW3 to insert 121 ohm terminating resistor on last module in the Modbus network 10 Feed line is any approved 300 volt 10 Amp 30 12 AWG stranded or solid 11 The register map for INCOM products is shown in register number order in Table...

Страница 9: ...10 VCN V 404635 406171 121A 181A 10 VLN V avg 404637 406173 121C 181C 10 N G voltage VNG V 404639 406175 121E 181E 10 Max current 5 minutes Max IA A 404641 406177 1220 1820 10 x Max IB A 404643 406179 1222 1822 10 x Max IC A 404645 406181 1224 1824 10 x Max IG A 404647 406183 1226 1826 10 Max IN A 404649 406185 1228 1828 10 Power real three phase power W 404651 406187 122A 182A 1 x reactive three ...

Страница 10: ... Max IN A 404649 406185 1228 1828 10 L L voltage VAB V 404623 406159 120E 180E 10 x VBC V 404625 406161 1210 1810 10 x VCA V 404627 406163 1212 1812 10 x VLLavg V avg 404629 406165 1214 1814 10 L N voltage VAN V 404631 406167 1216 1816 10 VBN V 404633 406169 1218 1818 10 VCN V 404635 406171 121A 181A 10 VLN V avg 404637 406173 121C 181C 10 N G voltage VNG V 404639 406175 121E 181E 10 Frequency fre...

Страница 11: ... position 42 Multiple causes 157 Shunt trip problem 61 Long delay phase overcurrent Table 13 Control Slave Action Number Definitions Control Group Definition Byte2 Byte1 Byte0 Reset Reset trip 0 0 2 Reset peak demand watts 0 0 4 Reset energy kilowatt hours 0 0 8 Reset synchronize demand watts window 0 0 64 4016 Snapshot command 0 0 128 8016 Reset peak demand currents 0 1 1 Reset all min max values...

Страница 12: ...nstallation and use Eaton Industries GmbH Electrical Sector 2010 by Eaton Industries GmbH Änderungen vorbehalten Subject to alterations 05 10 AWB1230 1622 Z8817 Moon Doku Heng Printed in USA 05 10 05 10 AWB1230 1622 Effective May 2010 ...

Страница 13: ...en 4 Modbus RS485 Netzwerk Rx LED Grün 5 Modbus RS485 Netzwerk Tx LED Grün 5 INCOM Netzwerk Rx LED Grün 5 INCOM Netzwerk Tx LED Grün 5 Status LED Grün 5 INCOM 100 Ω Abschlusswiderstand Kippschalter SW1 5 Modbus RS485 Baudrate Kippschalter SW2 5 mMINT Diagnose Adresse SW2 5 Modbus 121 Ω Abschlusswiderstand Kippschalter SW3 5 Abschnitt 6 Netzwerkkommunikationsprotokolle 5 Übersicht 5 Funktionscodes ...

Страница 14: ...hluss 4 Tabelle 2 Stecker J2 INCOM Anschluss 4 Tabelle 3 Stecker J3 Modbus RS485 Anschluss 4 Tabelle 4 RS485 Baudraten Schalter Normal 5 Tabelle 5 RS485 Baudraten Schalter Diagnose 5 Tabelle 6 Diagnose Sub Funktionsnummern 7 Tabelle 7 Anleitung zur Fehlersuche 7 Tabelle 8 Modbus Registerverzeichnis in Reihenfolge der Registernummern 9 Tabelle 9 Modbus Registerverzeichnis in funktionaler Reihenfolg...

Страница 15: ...m Warnung Führen Sie keine Installation oder Wartung durch während das Gerät unter spannung steht Tod oder ernsthafte Verletzungen können die Folge sein Stellen Sie immer sicher dass das Gerät nicht unter Spannung steht bevor Sie fortfahren Halten Sie sich immer an die Sicherheitshinweise Für falsche Anwendung oder Installation ist Eaton nicht haftbar Montage Stellen Sie sicher dass zur Montage de...

Страница 16: ...lle 2 Stecker J2 INCOM Anschluss Pin Eingangs Ausgangssignal 1 INCOM Trägernetzwerk 2 INCOM Trägernetzwerk 3 Abschirmung Verbinden Sie den Schirm mit der Masse des Master Gerätes Verbinden Sie die Schirmungen untereinander wenn Geräte in Serie miteinander verbunden sind J3 J1 J2 RS 485 Modbus A B GND ABS 4 25 108 0 3 54 89 9 24 125 Vdc 120 Vac Abschirmung INCOM Modbus Anschlüsse Modbus Anschluss D...

Страница 17: ...r SW3 Dieser Schalter sollte nur in ON Position gelegt werden wenn es das letzte Gerät in einer Kette von Geräten ist oder wenn es sich um ein Einzelgerät handelt Abschnitt 6 Netzwerkkommunikationsprotokolle Das INCOM Kommunikationsnetzwerk für den mMINT basiert auf einem Master Slave Protokoll Im INCOM Netzwerk ist das mMINT der Master Für weitere Informationen lesen Sie bitte folgendes Referenzm...

Страница 18: ...ese drei Register enthalten eine Slave Aktionsnummer Die Bedeutung ist in Tabelle 6 aufgelistet Das Datenformat wird in Abb 5 dargestellt Diese drei Register müssen in einer Modbus Transaktion geschrieben werden Aus Sicherheitsgründen muss zu jedem Slave Aktions Byte das Einerkomplement 1 zu 0 und 0 zu 1 gebildet werden Siehe Abb 5 Wenn die Slave Aktion Anfrage vom Auslöser erfolgreich bestätigt w...

Страница 19: ...Energie 2Mantisse Multiplikator Mantisse 10Faktor Tabelle 6 Diagnose Sub Funktionsnummern Sub Funktions Nr dezimal Name In der Abfrage 0 Echoanfrage mMINT oder INCOM Adr 1 Kommunikation erneut starten mMINT oder INCOM Adr 4 Gehör erzwingen mMINT oder INCOM Adr 10 Slave Zähler löschen mMINT oder INCOM Adr 11 Nachrichtensumme UART Bus mMINT oder INCOM Adr 12 UART Kommunikationsfehlersumme mMINT oder...

Страница 20: ...NCOM Netzwerks ein 8 Stellen Sie den Schalter SW2 zur Auswahl der Datentransferrate im Modbus Netzwerk ein 9 Stellen Sie den Schalter SW3 auf einen Abschlusswiderstand von 121 Ohm am letzten Modul im Modbus Netzwerk ein 10 Zuleitung zugelassen bis 300 Volt 10 Amp 30 12 AWG Litze oder Volldraht 11 Registerverzeichnis für INCOM Produkte wird in numerischer Reihenfolge in Tabelle 8 und funktioneller ...

Страница 21: ...VBN V 404633 406169 1218 1818 10 VCN V 404635 406171 121A 181A 10 VLN V avg 404637 406173 121C 181C 10 N G voltage VNG V 404639 406175 121E 181E 10 Max Strom 5 min Max IA A 404641 406177 1220 1820 10 x Max IB A 404643 406179 1222 1822 10 x Max IC A 404645 406181 1224 1824 10 x Max IG A 404647 406183 1226 1826 10 Max IN A 404649 406185 1228 1828 10 Leistung Wirk 3 ph Leistung W 404651 406187 122A 1...

Страница 22: ... 10 x Max IG A 404647 406183 1226 1826 10 Max IN A 404649 406185 1228 1828 10 L L voltage VAB V 404623 406159 120E 180E 10 x VBC V 404625 406161 1210 1810 10 x VCA V 404627 406163 1212 1812 10 x VLLavg V avg 404629 406165 1214 1814 10 L N voltage VAN V 404631 406167 1216 1816 10 VBN V 404633 406169 1218 1818 10 VCN V 404635 406171 121A 181A 10 VLN V avg 404637 406173 121C 181C 10 N G voltage VNG V...

Страница 23: ...Mehrere Ursachen 157 Shunt Trip Problem 61 Lange Verzögerungsphase Überstrom Tabelle 13 Steuerung Slave Aktions Nummer Definitionen Steuerungsgruppe Erklärung Byte2 Byte1 Byte0 Reset Schalter zurücksetzen Reset Trip 0 0 2 Max Leistung zurücksetzen 0 0 4 Energie Kilowattstunden zurücksetzen 0 0 8 Anforderungs Watt Fenster zurücksetzen synchronisieren 0 0 64 4016 Schnappschussbefehl zurücksetzen 0 0...

Страница 24: ...Modbus Translator Moduls Eaton Industries GmbH Electrical Sector 2010 by Eaton Industries GmbH Änderungen vorbehalten Subject to alterations 05 10 AWB1230 1622 Z8817 Moon Doku Heng Printed in USA 05 10 05 10 AWB1230 1622 Gültig ab Mai 2010 ...

Отзывы: