Eaton mMINT Скачать руководство пользователя страница 5

5

05/10 AWB1230-1622

Effective May 2010

mMINT—Modbus Translator Module— 

installation and use

 

EATON CORPORATION

 www.moeller.net/en/support 

Modbus RS-485 network Rx LED (green)

The LED will be lighted whenever the module is receiving from the 

Modbus RTU network .

Modbus RS-485 network Tx LED (green)

The LED will be lighted whenever the module is transmitting on the 

Modbus RTU network .

INCOM network Rx LED (green)

The LED will be lighted whenever the module is receiving from the 

INCOM network .

INCOM network Tx LED (green)

The LED will be lighted whenever the module is transmitting on the 

INCOM network .

Status LED (green)

This indicator will be flashing whenever a voltage is supplied to 

the module and the microcontroller is executing instructions . The 

flashing rate is approximately 1 second ON/1 second OFF . Detection 

of a communications error on either the Modbus or INCOM  

network will result in an increased flashing rate approximately  

0 .5 second ON/0 .5 second OFF . The rate will return to normal when 

the network’s diagnostic reset subfunction (clear UART or slave 

counters, respectively) is processed by the mMINT . See Section 6 

and 

Table 6

 .

INCOM 100 load resistance (DIP switch SW1)

This switch should be moved to the ON position when it is the last 

device in a chain of devices or if it is a single device .

Modbus RS-485 baud rate (DIP switch SW2)

To configure the data transfer rate for the Modbus RTU network, 

three switches in DIP switch SW2 should be set . Refer to 

Table 4

 . 

SW2-1 is for mMINT diagnostics .

Table 4.  RS-485 Baud Rate Switches (Normal)

Baud

SW2-1

SW2-2

SW2-3

1200

X

On

On

9600

X

Off

On

19200

X

On

Off

mMINT diagnostics address (SW2)

The mMINT can be assigned address 247 and 248 . For the mMINT 

to respond to a diagnostic query related to address 247 or 248 on 

the Modbus network, move DIP switch SW2-1 to the OFF position . 

Refer to 

Table 5

 . Normally, this switch is in the ON position .

Table 5.  RS-485 Baud Rate Switches (Diagnostics)

Baud

SW2-1

SW2-2

SW2-3

Addr. 247 or 248

Off

X

X

Normal

On

X

X

Modbus 121 load resistance (DIP switch SW3)

This switch should be moved to the ON position only when it is the 

last device in a chain of devices or if it is a single device .

Section 6: Network communication 

protocols

The INCOM communication network for the mMINT is based  

on a master-slave protocol . The mMINT is the master on the  

INCOM network .
For further information, please see Reference Material:
IL17384—Part A: IMPACC Communications Standard, Eaton . 

Specific product profiles are located in the other Part sections .  

http://www .eaton .com, then search for 17384 .
Modicon Modbus Protocol,  

http://www .modicon .com/techpubs/toc7 .html 

Overview

The contents of Modbus registers are INCOM product objects  

(e .g ., I

A

 – phase A) . An overview of the Modbus register is shown 

in 

Table 8

 or 

Table 9

 .

INCOM objects occupy two registers except for certain energy 

objects . These energy objects occupy four registers . The mMINT 

can support 122 registers maximum .
In its default configured state, INCOM addresses are  

Modbus addresses . 
Only the RTU communications mode is supported by the mMINT .

Function codes

The mMINT supports function codes 03, 04, 08, and 16 (10

16

) .

03 Read register
04 Read entry register
08 Connection test
16 Write register

Configuring the data registers

In order to be able to request the desired combination of registers 

in a telegram, you can load a register table starting with register 

41001142481(03E8

16

/5000

16

) in which the Modbus register 

addresses are loaded in series in hex . 
For example, although object I

A

 occupies registers 404611 (1202

16

and 404612 (1203

16

), only register address (1202

16

) is loaded in 

the register table . mMINT can verify that the load was successful  

by the read function code 03 or 04 from the 41001/420481 

(03E8

16

/5000

16

) register .

The data can only be requested in a read access starting at register 

41201/420737 (04B0

16

/5100

16

) .

The total number of data block of registers is limited to 100 . 

otee:

N

An object can occupy one, two, or four registers .

The data may be read from the register using the read function  

code 03 or 04 . The address of the starting object is 5100

16

 . 

The number of registers to be read must match the number of 

configured registers .

Содержание mMINT

Страница 1: ...EDS 4 Modbus RS 485 network Rx LED green 5 Modbus RS 485 network Tx LED green 5 INCOM network Rx LED green 5 INCOM network Tx LED green 5 Status LED green 5 INCOM 100 load resistance dip switch SW1 5 Modbus RS 485 baud rate dip switch SW2 5 mMINT diagnostics address SW2 5 Modbus 121 load resistance dip switch SW3 5 Section 6 Network communication protocols 5 Overview 5 Function codes 5 Configuring...

Страница 2: ...tor 4 Table 2 INCOM Connector J2 Pins 4 Table 3 Modbus RS 485 J3 Pins 4 Table 4 RS 485 Baud Rate Switches Normal 5 Table 5 RS 485 Baud Rate Switches Diagnostics 5 Table 6 Diagnostic Sub Function Numbers 7 Table 7 Troubleshooting Guide 7 Table 8 Modbus Register Map in Register Number Order 9 Table 9 Modbus Register Map in Functional Order 10 Table 10 Primary Status Code Definitions 11 Table 11 Seco...

Страница 3: ...tallation checkout safe operation or maintenance m WARNING DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENERGIZED DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING ALWAYS FOLLOW SAFETY PROCEDURES EATON IS NOT LIABLE FOR THE MISAPPLICATION OR MISINSTALLATION OF ITS PRODUCTS Module ...

Страница 4: ...e 2 Table 2 INCOM Connector J2 Pins Pin Number Input Output Signal 1 INCOM carrier network 2 INCOM carrier network 3 Shield Connect shield to ground at master device end only Interconnect shielding where devices are daisy chained J3 J1 J2 RS 485 Modbus A B COM SHD 4 25 108 0 3 54 89 9 24 125 Vdc 120 Vac Shield INCOM Modbus connections Modbus RS 485 connector The four pole connector is for the Modb...

Страница 5: ...Off X X Normal On X X Modbus 121 load resistance dip switch SW3 This switch should be moved to the ON position only when it is the last device in a chain of devices or if it is a single device Section 6 Network communication protocols The INCOM communication network for the mMINT is based on a master slave protocol The mMINT is the master on the INCOM network For further information please see Ref...

Страница 6: ...mbers Their meaning is listed in Table 6 The format of the data is shown in Figure 5 These three registers must be written in one Modbus transaction For safety reasons a 1 s complement must be formed to correspond with each slave action byte 1 to 0 and 0 to 1 As illustrated in Figure 5 If the slave action request is successfully acknowledged by the trigger the mMINT returns a normal function code ...

Страница 7: ... 10Coefficient Table 6 Diagnostic Sub Function Numbers Sub function No Decimal Name In the Query Use 0 echo query or INCOM addr 1 restart communications mMINT or INCOM addr 4 force listen mMINT or INCOM addr 10 clear slave counters mMINT or INCOM addr 11 UART bus message count mMINT or INCOM addr 12 UART communication error count mMINT or INCOM addr 13 slave exception error count mMINT or INCOM ad...

Страница 8: ...to insert 100 ohm terminating resistor on the last module of the INCOM network 8 Set up switch SW2 to select data transfer rate on the Modbus network 9 Set up switch SW3 to insert 121 ohm terminating resistor on last module in the Modbus network 10 Feed line is any approved 300 volt 10 Amp 30 12 AWG stranded or solid 11 The register map for INCOM products is shown in register number order in Table...

Страница 9: ...10 VCN V 404635 406171 121A 181A 10 VLN V avg 404637 406173 121C 181C 10 N G voltage VNG V 404639 406175 121E 181E 10 Max current 5 minutes Max IA A 404641 406177 1220 1820 10 x Max IB A 404643 406179 1222 1822 10 x Max IC A 404645 406181 1224 1824 10 x Max IG A 404647 406183 1226 1826 10 Max IN A 404649 406185 1228 1828 10 Power real three phase power W 404651 406187 122A 182A 1 x reactive three ...

Страница 10: ... Max IN A 404649 406185 1228 1828 10 L L voltage VAB V 404623 406159 120E 180E 10 x VBC V 404625 406161 1210 1810 10 x VCA V 404627 406163 1212 1812 10 x VLLavg V avg 404629 406165 1214 1814 10 L N voltage VAN V 404631 406167 1216 1816 10 VBN V 404633 406169 1218 1818 10 VCN V 404635 406171 121A 181A 10 VLN V avg 404637 406173 121C 181C 10 N G voltage VNG V 404639 406175 121E 181E 10 Frequency fre...

Страница 11: ... position 42 Multiple causes 157 Shunt trip problem 61 Long delay phase overcurrent Table 13 Control Slave Action Number Definitions Control Group Definition Byte2 Byte1 Byte0 Reset Reset trip 0 0 2 Reset peak demand watts 0 0 4 Reset energy kilowatt hours 0 0 8 Reset synchronize demand watts window 0 0 64 4016 Snapshot command 0 0 128 8016 Reset peak demand currents 0 1 1 Reset all min max values...

Страница 12: ...nstallation and use Eaton Industries GmbH Electrical Sector 2010 by Eaton Industries GmbH Änderungen vorbehalten Subject to alterations 05 10 AWB1230 1622 Z8817 Moon Doku Heng Printed in USA 05 10 05 10 AWB1230 1622 Effective May 2010 ...

Страница 13: ...en 4 Modbus RS485 Netzwerk Rx LED Grün 5 Modbus RS485 Netzwerk Tx LED Grün 5 INCOM Netzwerk Rx LED Grün 5 INCOM Netzwerk Tx LED Grün 5 Status LED Grün 5 INCOM 100 Ω Abschlusswiderstand Kippschalter SW1 5 Modbus RS485 Baudrate Kippschalter SW2 5 mMINT Diagnose Adresse SW2 5 Modbus 121 Ω Abschlusswiderstand Kippschalter SW3 5 Abschnitt 6 Netzwerkkommunikationsprotokolle 5 Übersicht 5 Funktionscodes ...

Страница 14: ...hluss 4 Tabelle 2 Stecker J2 INCOM Anschluss 4 Tabelle 3 Stecker J3 Modbus RS485 Anschluss 4 Tabelle 4 RS485 Baudraten Schalter Normal 5 Tabelle 5 RS485 Baudraten Schalter Diagnose 5 Tabelle 6 Diagnose Sub Funktionsnummern 7 Tabelle 7 Anleitung zur Fehlersuche 7 Tabelle 8 Modbus Registerverzeichnis in Reihenfolge der Registernummern 9 Tabelle 9 Modbus Registerverzeichnis in funktionaler Reihenfolg...

Страница 15: ...m Warnung Führen Sie keine Installation oder Wartung durch während das Gerät unter spannung steht Tod oder ernsthafte Verletzungen können die Folge sein Stellen Sie immer sicher dass das Gerät nicht unter Spannung steht bevor Sie fortfahren Halten Sie sich immer an die Sicherheitshinweise Für falsche Anwendung oder Installation ist Eaton nicht haftbar Montage Stellen Sie sicher dass zur Montage de...

Страница 16: ...lle 2 Stecker J2 INCOM Anschluss Pin Eingangs Ausgangssignal 1 INCOM Trägernetzwerk 2 INCOM Trägernetzwerk 3 Abschirmung Verbinden Sie den Schirm mit der Masse des Master Gerätes Verbinden Sie die Schirmungen untereinander wenn Geräte in Serie miteinander verbunden sind J3 J1 J2 RS 485 Modbus A B GND ABS 4 25 108 0 3 54 89 9 24 125 Vdc 120 Vac Abschirmung INCOM Modbus Anschlüsse Modbus Anschluss D...

Страница 17: ...r SW3 Dieser Schalter sollte nur in ON Position gelegt werden wenn es das letzte Gerät in einer Kette von Geräten ist oder wenn es sich um ein Einzelgerät handelt Abschnitt 6 Netzwerkkommunikationsprotokolle Das INCOM Kommunikationsnetzwerk für den mMINT basiert auf einem Master Slave Protokoll Im INCOM Netzwerk ist das mMINT der Master Für weitere Informationen lesen Sie bitte folgendes Referenzm...

Страница 18: ...ese drei Register enthalten eine Slave Aktionsnummer Die Bedeutung ist in Tabelle 6 aufgelistet Das Datenformat wird in Abb 5 dargestellt Diese drei Register müssen in einer Modbus Transaktion geschrieben werden Aus Sicherheitsgründen muss zu jedem Slave Aktions Byte das Einerkomplement 1 zu 0 und 0 zu 1 gebildet werden Siehe Abb 5 Wenn die Slave Aktion Anfrage vom Auslöser erfolgreich bestätigt w...

Страница 19: ...Energie 2Mantisse Multiplikator Mantisse 10Faktor Tabelle 6 Diagnose Sub Funktionsnummern Sub Funktions Nr dezimal Name In der Abfrage 0 Echoanfrage mMINT oder INCOM Adr 1 Kommunikation erneut starten mMINT oder INCOM Adr 4 Gehör erzwingen mMINT oder INCOM Adr 10 Slave Zähler löschen mMINT oder INCOM Adr 11 Nachrichtensumme UART Bus mMINT oder INCOM Adr 12 UART Kommunikationsfehlersumme mMINT oder...

Страница 20: ...NCOM Netzwerks ein 8 Stellen Sie den Schalter SW2 zur Auswahl der Datentransferrate im Modbus Netzwerk ein 9 Stellen Sie den Schalter SW3 auf einen Abschlusswiderstand von 121 Ohm am letzten Modul im Modbus Netzwerk ein 10 Zuleitung zugelassen bis 300 Volt 10 Amp 30 12 AWG Litze oder Volldraht 11 Registerverzeichnis für INCOM Produkte wird in numerischer Reihenfolge in Tabelle 8 und funktioneller ...

Страница 21: ...VBN V 404633 406169 1218 1818 10 VCN V 404635 406171 121A 181A 10 VLN V avg 404637 406173 121C 181C 10 N G voltage VNG V 404639 406175 121E 181E 10 Max Strom 5 min Max IA A 404641 406177 1220 1820 10 x Max IB A 404643 406179 1222 1822 10 x Max IC A 404645 406181 1224 1824 10 x Max IG A 404647 406183 1226 1826 10 Max IN A 404649 406185 1228 1828 10 Leistung Wirk 3 ph Leistung W 404651 406187 122A 1...

Страница 22: ... 10 x Max IG A 404647 406183 1226 1826 10 Max IN A 404649 406185 1228 1828 10 L L voltage VAB V 404623 406159 120E 180E 10 x VBC V 404625 406161 1210 1810 10 x VCA V 404627 406163 1212 1812 10 x VLLavg V avg 404629 406165 1214 1814 10 L N voltage VAN V 404631 406167 1216 1816 10 VBN V 404633 406169 1218 1818 10 VCN V 404635 406171 121A 181A 10 VLN V avg 404637 406173 121C 181C 10 N G voltage VNG V...

Страница 23: ...Mehrere Ursachen 157 Shunt Trip Problem 61 Lange Verzögerungsphase Überstrom Tabelle 13 Steuerung Slave Aktions Nummer Definitionen Steuerungsgruppe Erklärung Byte2 Byte1 Byte0 Reset Schalter zurücksetzen Reset Trip 0 0 2 Max Leistung zurücksetzen 0 0 4 Energie Kilowattstunden zurücksetzen 0 0 8 Anforderungs Watt Fenster zurücksetzen synchronisieren 0 0 64 4016 Schnappschussbefehl zurücksetzen 0 0...

Страница 24: ...Modbus Translator Moduls Eaton Industries GmbH Electrical Sector 2010 by Eaton Industries GmbH Änderungen vorbehalten Subject to alterations 05 10 AWB1230 1622 Z8817 Moon Doku Heng Printed in USA 05 10 05 10 AWB1230 1622 Gültig ab Mai 2010 ...

Отзывы: