17
Instructional Leaflet
IL66A7508H09
Effective October 2016
mMINT—Modbus translator module—
installation and use
EATON
www.eaton.com
Table 10. Primary status code definitions
Code
Definition
Code
Definition
0
Unknown
19
Phase A alarm
1
Open
20
Phase B alarm
2
Closed
21
Phase C alarm
3
Tripped
22
Neutral alarm
4
Alarmed
23
Ground/earth alarm
5
On
24
Phase AB alarm
6
Off
25
Phase BC alarm
7
Ready
26
Phase CA alarm
8
Starting
27
On good source
9
Operational
28
Running
10
Stopped
Reserved 29…251
11
Locked-out
12
Transferred
13
Picked-up
14
Phase A trip
15
Phase B trip
252
Product-Specific Code 252
16
Phase C trip
253
Product-Specific Code 253
17
Neutral trip
254
Product-Specific Code 254
18
Ground/earth trip
255
Product-Specific Code 255
Table 11. Secondary status code definitions
Code
Definition
Code
Definition
0
Unknown
Reserved 9…27
1
Not applicable
2
Program mode
3
Test mode
4
Disabled
5
Disarmed
28
Product-Specific Code 28
6
Controlled device failed to operate
29
Product-Specific Code 29
7
Powered up
30
Product-Specific Code 30
8
Alarm
31
Product-Specific Code 31
Table 12. Cause-of-status code definitions
Code Definition
Code
Definition
0
Unknown
39
Diagnostic warning #1
1
Normal operating mode
40
Diagnostic failure #1
2
External condition #1
41
Low battery
3
Instantaneous phase overcurrent
42
Multiple causes
4
Instantaneous ground overcurrent
43
Diagnostic warning #2
5
Instantaneous neutral overcurrent
44
Diagnostic warning #3
6
Instantaneous residual overcurrent 45
Diagnostic warning #4
7
Phase inverse-time overcurrent
46
Diagnostic warning #5
8
Ground inverse-time overcurrent
47
Diagnostic warning #6
9
Neutral inverse-time overcurrent
48
Diagnostic warning #7
10
Residual inverse-time overcurrent
49
Diagnostic warning #8
11
Overvoltage
50
Diagnostic warning #9
12
Undervoltage
51
Diagnostic warning #10
13
Auxiliary overvoltage
52
Diagnostic failure #2
14
Auxiliary undervoltage
53
Diagnostic failure #3
15
Underfrequency
54
Diagnostic failure #4
16
Overfrequency
55
Diagnostic failure #5
17
Current unbalance
56
Diagnostic failure #6
18
Voltage unbalance
57
Diagnostic failure #7
19
Apparent power factor
58
Diagnostic failure #8
20
Displacement power factor
59
Diagnostic failure #9
21
Zone interlock phase
60
Diagnostic failure #10
22
Zone interlock ground
61
Long delay phase overcurrent
23
Watt
62
Short delay phase overcurrent
24
VA
63
Fixed instantaneous phase
overcurrent #1
25
Var
64
Bad / missing rating plug
26
Power demand
65
Reverse power
27
VA demand
66
Fixed instantaneous phase
overcurrent #2
28
Var demand
67
Reverse phase
29
Current demand
68
Reverse sequence
30
Total harmonic distortion
69
Phase current loss
31
Operations count
70
Phase voltage loss
32
Contact maintenance
71
Alarm active
33
Control via communications
72
Bad frame
34
Contact disagreement
73
Phase currents near pickup
35
Breaker failure
74
Lockout
36
Operation time exceeded
75
Making current release
37
Coil supervision
76
Fixed instantaneous phase
overcurrent #3
38
Programmable logic
77
Set points error