background image

5

Instructional Leaflet 

IL66A7508H09

Effective October 2016

mMINT—Modbus translator module—  

installation and use 

  

EATON

 www.eaton.com

Table 4.  RS-485 baud rate switches (normal)

Baud

SW2-1

SW2-2

SW2-3

1200

X

CLOSE

CLOSE

9600

X

OPEN

CLOSE

19200

X

CLOSE 

OPEN

Unique mMINT address (SW2)

The mMINT can be assigned address 247 and 248 . For the mMINT 

to respond to a diagnostic query related to address 247 or 248 on 

the Modbus network, move DIP switch SW2-1 to the OPEN position . 

Refer to 

Table 5

 . Normally, this switch is in the CLOSE position .

Table 5.  RS-485 baud rate switches (diagnostics)

Baud

SW2-1

SW2-2

SW2-3

Addr. 247 or 248

OPEN

X

X

Normal

CLOSE

X

X

Modbus 121 ohm termination DIP switch (SW3)

This switch should be moved to the ON position only when it is the 

last unit in a chain of units or if it is a single unit .

Section 6: Network communication protocols

The lower INCOM communication network for the mMINT is  

based on a master-slave protocol . The mMINT is a master on the 

INCOM network .

In order to satisfy the mMINT communications needs, please see 

Reference Materials:

IL17384—Part A: 

INCOM Communications Standard, Eaton .  

Specific product profiles are located in the other Part sections .  

http://www .eaton .com, then search on 17384 .

“Modicon Modbus Protocol”  

http://www .modicon .com/techpubs/toc7 .html 

Overview

The contents of Modbus registers are INCOM product objects  

(e .g ., I

A

—phase A current) . The mMINT ensures that unique objects 

reside in identical registers independent of INCOM product . 

Consequently, for all INCOM products there is a single register  

map of objects . See 

Table 8

 or 

Table 9

 .

INCOM objects occupy two registers except for certain energy— 

real and reactive—objects . These energy objects occupy four 

registers . The mMINT can support a maximum of 122 registers 

within a single Modbus transaction .
The mMINT is transparent to the Modbus master and responds 

to every address of INCOM products attached to it . In its default 

configured state, INCOM product addresses are Modbus network 

addresses . The mMINT can be configured to route the Modbus 

address to a different INCOM product address or an INCOM  

sub-network product address . See Section 6 .
An upgrade has been incorporated to allow the mMINT to 

communicate with Modbus masters that can only access to  

register 9999 . Registers previously assigned above 9999 have 

been assigned dual access, both at the original register (to provide 

compatibility) and at a new register assignment below 9999 .  

The format is given as low/high register numbers followed by  

(low

16

/high

16

 Modbus register addresses), for example:  

4xxxx/4yyyyy (XXXX+1

16

/YYYY+1

16

) . See 

Table 14

 .

Only the RTU communications mode is recognized by the mMINT .

Function codes

The mMINT responds to a limited number of Modbus function 

codes . These are function codes 03, 04, 08, and 16 (10

16

) .

Block of registers

A block of registers (from the register column of 

Table 8

 or 

Table 9

can be established for each INCOM product attached to a mMINT . 
Function code 16 (10

16

) is used to load the object assignments for 

the block of registers . The block assignments are stored beginning at 

register 41001/420481 (03E8

16

/5000

16

) .Only the first object register 

address is assigned within the block of registers . For example, 

although object I

A

 occupies registers 404611 (1202

16

) and 404612 

(1203

16

), only register address (1202

16

) is loaded into the block 

of assignment registers . Verification of this block of assignment 

registers can be read from the mMINT by a read function code 03  

or 04 from these 41001/420481 (03E8

16

/5000

16

) registers .

Data pertaining to the objects configured in the block of assignment 

registers is mapped into registers starting at 41201/420737 

(04B0

16

/5100

16

) and continuing in successive order for each object 

assigned . The number of objects and their placement order in this 

data block of registers is dependent on the configuration of the block 

of assignment registers . The total number of data block of registers 

is limited to 100 . 

ote:

N

An object can occupy one, two, or four registers .

The data can be obtained from the data block of registers by a read 

function code 03 or 04 . The address of the starting object must be 

aligned with a starting address of an object within the data block 

of registers . The number of registers to obtain must align with an 

ending address of an object within the data block of registers .

Register access configurations

Non-volatile register 42001/425345 (07D0

16

/6300

16

) is used to 

configure the mMINT to respond to a group of data objects, of 

which some objects are invalid within that group . When non-zero 

(factory default value), any attempt to access a group of data objects 

that contain an invalid object will result in an illegal data object 

exception code 02 . See Section 6 .
When register 42001/425345 (07D0

16

/6300

16

) is set to zero, however, 

the mMINT will respond to a group of objects with data contained in 

the valid objects of the group along with an illegal  

value, if available else 0000

16

, data contained in the invalid objects .

Non-volatile register 42002/425346 (07D1

16

/6301

16

) is used to 

configure 32-bit IEEE floating point word order . When non-zero 

(factory default), the floating point low order word is first in the 

Modbus register space .
When register 42002/425346 (07D1

16

/6301

16

) is set to zero, however, 

the floating point high order word is first in the Modbus register 

space .
Non-volatile register 42002/425347 (07D1

16

/6302

16

) is used to 

configure 32-bit fixed point and 64-bit energy word order . When  

non-zero (factory default), the fixed point and energy low order  

word is first in the Modbus register space .
When register 42003/425347 (07D2

16

/6302

16

) is set to zero, however, 

the fixed point and energy high order word is first in the Modbus 

register space .
Registers not containing a 32-bit or 64-bit format, such as Status and 

Product ID objects, pass through registers, INCOM control registers, 

and INCOM routing address configuration registers, are not effected 

by the word order configuration registers .
Configuring any or all registers 42001/425345 through 42003/425347 

(07D0

16

/6300

16

 through 07D2

16

/6302

16

) is accomplished using a write 

function code 16 (10

16

) to mMINT diagnostic address 247 or 248 .

ote:

N

mMINT SW2-1 must be properly set . See Section 5 and 

Table 5

 .

Содержание mMINT

Страница 1: ...S 485 network Tx LED green 4 INCOM network Rx LED green 4 INCOM network Tx LED green 4 Status LED green 4 INCOM 100 ohms termination DIP switch SW1 4 Modbus RS 485 baud rate DIP switch SW2 4 Unique mM...

Страница 2: ...8 Modbus register map in register number order 10 Table 9 Modbus register map in functional order 14 Table 10 Primary status code definitions 17 Table 11 Secondary status code definitions 17 Table 12...

Страница 3: ...that it is within an enclosed space Simplified wiring rules INCOM network The following simplified rules apply to a given system consisting of a single daisy chained main cable link between master an...

Страница 4: ...network Rx LED green The LED will be lighted whenever the module is receiving from the Modbus RTU network Modbus RS 485 network Tx LED green The LED will be lighted whenever the module is transmittin...

Страница 5: ...or the block of registers The block assignments are stored beginning at register 41001 420481 03E816 500016 Only the first object register address is assigned within the block of registers For example...

Страница 6: ...s master writes the INCOM product command data using function code 16 1016 beginning at register 42601 424577 0A2816 600016 The data format for passing information through the mMINT to an INCOM produc...

Страница 7: ...ction Byte 0 Register 42902 425090 0B5516 620116 1 s Complement of Slave Action Byte 0 Slave Action Byte 2 Register 42903 425091 0B5616 620216 1 s Complement of Slave Action Byte 2 1 s Complement of S...

Страница 8: ...T or INCOM addr 12 UART communication error count mMINT or INCOM addr 13 slave exception error count mMINT or INCOM addr 14 slave message count mMINT or INCOM addr 15 slave no response count mMINT or...

Страница 9: ...bus is a registered trademark of Schneider Electric 2 mMINT modules use DIN rail mounting 3 Control voltage is 120 Vac 20 or 24 125 Vdc 4 Connectors are plug in types from Phoenix contact 5 Terminal T...

Страница 10: ...04621 406157 120C 180C 10 n n n L L voltage VAB V 404623 406159 120E 180E 10 n n n n n n n n VBC V 404625 406161 1210 1810 10 n n n n n n n n VCA V 404627 406163 1212 1812 10 n n n n n n n n VLLavg V...

Страница 11: ...6 1 n n apparent B ph VA 404681 406217 1248 1848 1 n n apparent C ph VA 404683 406219 124A 184A 1 n n Power factor displacement A ph pf 404685 406221 124C 184C 100 n n displacement B ph pf 404687 4062...

Страница 12: ...n n n n n Motor phase unbalance 404737 406273 1280 1880 100 n thermal capacity 404739 406275 1282 1882 100 n Temperature motor winding 1 C 404741 406277 1284 1884 1 n motor winding 2 C 404743 406279 1...

Страница 13: ...Network voltage A ph V 404801 406337 12C0 18C0 10 B ph V 404803 406339 12C2 18C2 10 C ph V 404805 406341 12C4 18C4 10 Transformer voltage A ph V 404807 406343 12C6 18C6 10 B ph V 404809 406345 12C8 18...

Страница 14: ...n n n n n n n IN A 404619 406155 120A 180A 10 n n n n n n n n n IAvg A avg 404621 406157 120C 180C 10 n n n peak IA demand A 404641 406177 1220 1820 10 n n n n n n n n n peak IB demand A 404643 40617...

Страница 15: ...18D6 10 B ph quadrature V 404825 406361 12D8 18D8 10 C ph direct V 404827 406363 12DA 18DA 10 C ph quadrature V 404829 406365 12DC 18DC 10 pos seq direct V 404831 406367 12DE 18DE 10 pos seq quadratur...

Страница 16: ...72 1 n n n n n n n n reverse kWh N A 406261 N A 1874 1 n n n n n n n n total kWh N A 406263 N A 1876 1 n n n n n n n n n apparent kVAh N A 406271 N A 187E 1 n n n n n Energy 4 reg objects forward Wh N...

Страница 17: ...neutral overcurrent 44 Diagnostic warning 3 6 Instantaneous residual overcurrent 45 Diagnostic warning 4 7 Phase inverse time overcurrent 46 Diagnostic warning 5 8 Ground inverse time overcurrent 47...

Страница 18: ...watt VAR 110 Jam 152 Power 111 Under load Reserved 153 2043 112 Delay ground overcurrent 113 Calibration 114 Emergency 115 Torque limit 116 Deceleration 2044 Product Specific Code 2044 117 Voltage sa...

Страница 19: ...ed motor start profile buffer 3 0 9 Relay Control Activate relay output X X relay number 0 255 4 1 X De activate relay output X X relay number 0 255 4 2 X Automatic Transfer Switch Control Initiate AT...

Страница 20: ...een Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFIC...

Отзывы: