19
Instructional Leaflet
IL66A7508H09
Effective October 2016
mMINT—Modbus translator module—
installation and use
EATON
www.eaton.com
Table 13
.
Control ‘Slave Action Number’ definitions (continued)
Control
group
Definition
Byte2
Byte1
Byte0
Motor
Start-Stop
No action
2
0
0
Start fast forward
2
0
1
Start fast reverse
2
0
2
Stop
2
0
3
Start
2
0
4
Start slow forward
2
0
5
Start slow reverse
2
0
6
Set direction to forward
2
0
7
Set direction to reverse
2
0
8
Emergency override
2
0
10
System
Control
Release time-stamped event buffer
3
0
0
Capture waveform
3
0
1
Reset INCOM slave-interface
statistics
3
0
2
Reset product-specific statistics
3
0
3
Acknowledge triggered event(s)
3
0
4
Reset sun-network master
INCOM statistics
3
0
5
Acknowledge energy-reset
3
0
6
Acknowledge set points change
buffer
3
0
7
Release time-stamped minor
event buffer
3
0
8
Release time-stamped motor
start profile buffer
3
0
9
Relay
Control
Activate relay output #X
(X = relay number 0–255)
4
1
X
De-activate relay output #X
(X = relay number 0–255)
4
2
X
Automatic
Transfer
Switch
Control
Initiate ATS test
5
0
1
Bypass TDNE/TDEN
5
0
2
Initiate manual transfer
5
0
4
Cancel ATS test
5
0
5
Go to emergency
5
0
6
Cancel Go to emergency
5
0
7
Table 14. mMINT configuration registers
Register definition
R/W
Register
10
Modbus
address
16
No. of
regs
10
Low
High
Low
High
mMINT (247 or 248 addressed)
Invalid Object Access
Configuration
R/W 42001
425345 07D0
6300
1
Floating Pt Data Word
Order Configuration
R/W 42002
425346 07D1
6301
1
Fixed Pt Data Word
Order Configuration
R/W 42003
425347 07D2
6302
1
INCOM Routing
Address Configuration
R/W 42101
0834
2 * 246
INCOM (device addressed)
Mapped Block of
Registers Configuration
R/W 41001
420481 03E8
5000
100
Mapped Block of
Registers Data
R
41201
420737 04B0
5100
4 * 100
Modbus-to-INCOM Query
W
42601
424577 0A28
6000
2
Modbus-to-INCOM Response R
42701
424833 0A8C
6100
2 * 63
Supervisory Control Query
R/W 42901
425089 0B54
6200
3