Dimensions
39
09/10 MN05013011Z-EN
Technical data
General ambient conditions
Climatic conditions
(damp heat constant to IEC 60068-2-78;
cyclical to IEC 60068-2-30)
(cold to IEC 60068-2-1, heat to IEC 60068-2-2)
Operating ambient temperature
Installed horizontally/vertically
°C, (°F)
–25 to 55, (–13 to 131)
Condensation
Prevent condensation by
means of suitable measures
Display legibility
°C, (°F)
–5 to 50, (23 to 122)
Storage/transport temperature
°C, (°F)
–40 to 70, (–40 to 158)
Relative humidity (IEC 60068-2-30), non-condensing
%
5 to 95
Air pressure (in operation)
hPa
795 up to 1080
Ambient mechanical conditions
Pollution degree
Power supply unit/CPU
2
Display/operating unit
3
Degree of protection (EN 50178, IEC 60529, VBG4)
Power supply unit/CPU
IP20
Display/operating unit
IP65
Display/operating unit with protective cover
IP65
Display/operating unit with protective diaphragm
IP65
Vibration (IEC 60068-2-6)
Constant amplitude 0.15 mm
Hz
10 up to 57
Constant acceleration, 2 g
Hz
57 up to 150
Shocks (IEC 60068-2-27) semi-sinusoidal 15 g/11 ms
Shocks
18
Drop (IEC 60068-2-31)
Drop
height
mm
50
Free fall, when packed (IEC 60068-2-32)
m
1