5. Operations

UPS

BYPASS

UPS

BYPASS

5.1 UPS start-up with HotSwap MBP

 

Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload alarm.

1. Check that the UPS is correctly connected to the HotSwap MBP (see previous chapter 4)

 

 If the UPS if equipped with outlets

, those outlets can no longer be used (loads can only be connected to the 

MBP outlets or the MBP Output terminal blocks).

2. Verify that the MBP terminal blocks are connected to the AC source, and to the Bypass AC source 

(*)

3. Check that the MBP manual Bypass switch is to the 

"Bypass" position

4.  Set the upstream circuit breaker (not provided) to the "I" position (On) to switch On the utility power, and 

also set the Bypass source upstream circuit breaker (not provided) to the "I" position (On) to switch on the 

Bypass power 

(*)

5.  Verify that the 

“Bypass mode”red light 

of the MBP goes On, indicating that the load is now powered  

by the AC source, or Bypass AC source 

(*)

6. Set the Normal AC source switch and the Bypass AC source switch 

(*)

 

of the MBP to the "I" position

7. Verify that the UPS is correctly powered (UPS display panel illuminates)
8. Press the UPS 

“ON”

 button to start the UPS

9. Put the UPS in 

“internal Bypass mode”

 (refer to the UPS User Manual)

10. Verify that the UPS is on Bypass mode by checking UPS display panel (refer to the UPS user manual)
11.  Verify that the

 “UPS mode”

 

green light

 of the MBP goes On, indicating that the UPS output power is 

available on the MBP

 

Important:

  do not continue to next step if the 

"UPS mode" green light 

of the MBP is still Off  

(the load will be lost)

12.  Set the MBP manual Bypass switch to the 

"UPS" position

: the 

"Bypass mode" red light 

of the MBP goes 

Off, indicating that the load is now powered by the UPS

13. Put the UPS in 

"normal mode"

 (refer to the UPS User Manual)

14.  Check that the UPS is in Online mode by checking UPS display panel (refer to the UPS user manual)  

the load is now protected by the UPS

(*) only in case of Bypass AC source option connected (MBP11Ki and MBP11Ki31 only).

Содержание MBP11Ki

Страница 1: ...ENGLISH HotSwap MBP Maintenance Bypass MBP6Ki MBP11Ki MBP11Ki31 Installation and user manual Copyright 2013 EATON All rights reserved Service and support Call your local service representative SK 9051...

Страница 2: ...nt This equipment has been tested and found to comply with Class A UPS pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when...

Страница 3: ...ing The upstream circuit breaker must be easily accessible The unit can be disconnected from AC power source by opening this circuit breaker and if still connected to UPS by previously shutting down t...

Страница 4: ...ng the accessory kit 9 3 4 Mechanical Mounting 10 3 5 Installation requirements 10 4 Power cables connection 11 4 1 MBP6Ki 11 4 2 MBP11Ki MBP11ki31 with common Normal and Bypass AC source 12 4 3 MBP11...

Страница 5: ...g To improve waste treatment and facilitate recycling separate the various packing components The cardboard we use comprises over 50 of recycled cardboard Sacks and bags are made of polyethylene Packi...

Страница 6: ...Hotswap MBP 5 6kVA range make before break feature to allow full servicing electrical power continuity when switching from UPS position to Bypass and vice versa Communication feature with UPS detecti...

Страница 7: ...ower installation Rack installation Wall mounting Description Weight lb kg Dimensions inch mm D x W x H MBP6Ki 5 5 2 5 4 3 x 7 0 x 5 1 110 x 177 x 130 MBP11Ki 12 1 5 5 5 2 x 13 2 x 5 1 132 x 336 x 130...

Страница 8: ...nance replacing MBP status detection A signal cable with RJ11 connector to plug to the UPS allows the communication to the UPS to manage the MBP status and the indication on UPS display panel of both...

Страница 9: ...e use Place the cabinet in a protected area that has adequate airflow and is free of humidity flammable gas and corrosion Packing materials must be disposed of in compliance with all local regulations...

Страница 10: ...MBP Normal AC source 2 Recommended cable cross sections 3 Installation Terminal position Wire function Terminal wire size rating Minimum input wire size rating Tightening torque MBP6ki L1 Phase 0 5 10...

Страница 11: ...n 2 Connect the MBP detection cable from the I O cord Set 1 to the specific UPS connector MBP detect refer to UPS User Manual Only with compatible EATON UPS contact your Eaton reseller for more inform...

Страница 12: ...cess to MBP terminal blocks 4 Insert the Normal AC source cable through the cable gland 5 Connect the wires to the Normal AC source Input terminal blocks do not remove the Input Bypass AC jumper 4 and...

Страница 13: ...s Input power cable to the UPS I O terminal blocks following color coding on the cables and the UPS I O cover blue for UPS Input red for UPS Output yellow for UPS Input Bypass refer to the UPS user ma...

Страница 14: ...e gland 17 Connect the wires to the Output terminal blocks 18 Tighten the cable glands 19 Slide back and secure the MBP I O cover 3 with the 5 screws OUTPUT L1 N t INPUT BP L1 N t 1 5 2 3 Utility Powe...

Страница 15: ...the load is now powered by the AC source or Bypass AC source 6 Set the Normal AC source switch and the Bypass AC source switch of the MBP to the I position 7 Verify that the UPS is correctly powered...

Страница 16: ...urce 4 Switch the Normal AC source switch of the MBP to the 0 position and wait 30 seconds 5 UPS stops the UPS can now be disconnected as described below First disconnect the I O cord Set 1 from the M...

Страница 17: ...irst lock the Normal AC source switch 4 and the Bypass AC source switch 5 of the MBP to the 0 position the switch protection frames are able to fit a cable tie or a metallic locker 5 4 After opening t...

Страница 18: ...will be lost 8 Set the MBP manual Bypass switch to the UPS position the Bypass mode red light of the MBP goes Off indicating that the load is now powered by the UPS 9 Put the UPS in normal mode refer...

Страница 19: ...r 6000 VA 11000 VA 11000 VA Standards HotSwap MBP used with UPS Safety IEC EN 62040 1 Ed 1 2008 EMC IEC 62040 2 Ed 2 2005 EN 62040 2 Ed 2 2006 Performance IEC EN 62040 3 Ed 2 0 2011 ESD IEC 61000 4 2...

Страница 20: ...Page 20 SK 90510 Y4_EN...

Отзывы: