background image

6

Instruction Booklet 

IB01900002E

Effective June 2011

Instructions for Magnum DS Metal-Enclosed

Low-Voltage NEMA 3R Assemblies

 

EATON CORPORATION

 www.eaton.com

3.2 NEMA 3R Enclosure Construction Options (Figures 3 - 6)

Magnum DS Metal-Enclosed Low-Voltage NEMA 3R Assemblies 

are offered in four varieties to meet the limitations of space and 

customer preferences.  The options include location of power cable 

connections as well as presence or absence of a personnel ingress 

aisle-way.

3.2.1 Rear-Access with Aisle-way

Power cable connections are accessible from the rear of the assem-

bly. The rear access doors are hinged and provided with door stops. 

These braces keep the doors open at a 90 degree angle.  Power 

cables and conduits can exit through the floor or through the roof if 

the proper roof-exit flange is installed (by customer order request).  

Connection to line and/or load breaker connections is the same as 

described in IB01901001E, the indoor assembly literature for rear-

accessible enclosures.
A front operating and maintenance aisle extends through all units of 

the assembly. A large reinforced door with panic hardware is stan-

dard at each end of the aisle. These doors can be opened from the 

inside, even when padlocked from the outside.
The structure also includes, as standard, filtered ventilation open-

ings (filters can be changed without opening aisle or rear compart-

ment doors), aisle lighting, GFI protected convenience receptacles 

and space heaters. When specified, a thermostat is mounted in the 

cable compartment. Space heaters are located in the “D” position 

breaker cell, bus compartment and cable compartment of each verti-

cal section

3.2.2 Rear-Access without Aisle-way (Non walk-in)

Power cable connections are the same as described above.  

Connection to line and/or load breaker connections is the same as 

described in IB01901001E, the indoor assembly literature for rear-

accessible enclosures.
The front aisle-way is absent in the non-walk-in design, permitting an 

assembly depth reduction of approximately 32 inches (812 mm) over 

the standard rear-access walk-in assembly.  Access to the breaker 

compartment is affected through full-height doors on the front of the 

enclosure.  These doors contain the same bracing features present 

on the rear doors described above.  Ventilated filters, lighting, recep-

tacles and heaters are standard as described above.
The work space between the external shell and the internal breaker 

enclosure is approximately 7.5 inches (190 mm), therefore the need 

for a means of emergency exit is not provided.

otee:

N

A unique feature of the non-walk-in assembly is the internal breaker 

doors hinge on the right-hand side as normal convention, rather than the left.

3.2.3 Front-Access with Aisle-way

Front accessible assemblies provide further footprint reductions 

when required by customer installations.
Power cable connections are accessible from the front of the assem-

bly through the maintenance aisle-way as described below.  Power 

cables and conduits can exit through the floor or through the roof if 

the proper roof-exit flange is installed (by customer order request).  

Connection to line and/or load breaker connections is the same as 

described in IB01901001E, the indoor assembly literature for front-

accessible enclosures.
A front operating and maintenance aisle extends through all units of 

the assembly. A large reinforced door with panic hardware is stan-

dard at each end of the aisle. These doors can be opened from the 

inside, even when padlocked from the outside.
The structure also includes, as standard, filtered ventilation open-

ings (filters can be changed without opening aisle or rear compart-

ment doors), aisle lighting, GFI protected convenience receptacles 

and space heaters. When specified, a thermostat is mounted in the 

cable compartment. Space heaters are located in the “D” position 

breaker cell, bus compartment and cable compartment of each verti-

cal section.

3.2.4 Front-Acess without Aisle-way (Non walk-in)

Power cable connections are the same as described above.  

Connection to line and/or load breaker connections is the same as 

described in IB01901001E, the indoor assembly literature for front-

accessible enclosures.
The front aisle-way is absent in the non-walk-in design, permitting an 

assembly depth reduction of approximately 31 inches (784 mm) over 

the standard front-access walk-in assembly.  Access to the breaker 

compartment and power cable connections is affected through full-

height doors on the front of the enclosure.  These doors contain the 

same bracing features present on the rear doors described above.  

Ventilated filters, lighting, receptacles and heaters are standard as 

described above.
The work space between the external shell and the internal breaker 

enclosure is approximately 7.5 inches (190 mm), therefore the need 

for a means of emergency exit is not provided.

otee:

N

A unique feature of the non-walk-in assembly is the internal breaker 

doors hinge on the right-hand side as normal convention, rather than the left.

Содержание Magnum DS

Страница 1: ...andling and Storage 4 3 Equipment Description 5 4 Installation 11 5 Inspection Testing and Maintenance 14 6 Document References 14 Effective June 2011 Instruction Booklet IB01900002E Instructions for...

Страница 2: ...1 Introduction 1 1 General Information Magnum DS Metal Enclosed Low Voltage NEMA 3R Switchgear and Switchboard Assemblies are uniquely designed for use in outdoor environments or other harsh conditio...

Страница 3: ...rm that all circuits are de energized before servicing 7 After maintenance be certain every current transformer second ary circuit is completely connected or shorted DANGER IF THE SECONDARY CIRCUIT OF...

Страница 4: ...ial until it is certain that every item has been received in the proper condition and that certain packing material will not be required later for equipment storage Larger items such as portable trave...

Страница 5: ...iptions apply to standard metal enclosed con struction and wiring Special features and control schemes are often incorporated per customer specifications These special features are evident and portray...

Страница 6: ...xternal shell and the internal breaker enclosure is approximately 7 5 inches 190 mm therefore the need for a means of emergency exit is not provided Note N A unique feature of the non walk in assembly...

Страница 7: ...9255C35 120 0 3047 OVERALL DEPTH 18 4 468 BUS OPENING FROM BASE 109 1 2772 105 1 2668 51 2 1301 2 0 51 4 0 102 3 9 99 2 3 58 28 6 726 FROM BASE 26 0 660 43 4 1102 AISLE WIDTH 117 1 2974 BASE 30 2 767...

Страница 8: ...Assemblies EATON CORPORATION www eaton com Figure 4 Side Elevation NEMA 3R Assembly Rear Accessible without Walk in Aisle Way C C 9259C06 86 0 2185 BASE 26 0 660 28 6 726 FROM BASE 51 2 1301 2 0 51 4...

Страница 9: ...ON CORPORATION www eaton com Figure 5 Side Elevation NEMA 3R Assembly Front Accessible with Walk In Aisle Way 8652C19 87 1 2211 OVERALL DEPTH 29 1 740 111 4 2830 107 9 2740 2 0 51 3 9 99 111 5 2832 OV...

Страница 10: ...d Low Voltage NEMA 3R Assemblies EATON CORPORATION www eaton com Figure 6 Side Elevation NEMA 3R Assembly Front Accessible without Walk In Aisle Way 8652C25 54 2 1378 BASE 105 1 2669 110 3 2800 109 8...

Страница 11: ...tion to avoid distortion of the structure The lifting plates attached at the base perform the dual purpose of providing a convenient and robust method of securing the unit to the foundation A separate...

Страница 12: ...n sales office 4 4 Bus Cable and Control Connections Refer to Section 4 4 1 thru 4 4 6 of reference IB01901001E for com plete instructions and guidelines on various bus connections installa tion of po...

Страница 13: ...900002E Effective June 2011 Instructions for Magnum DS Metal Enclosed Low Voltage NEMA 3R Assemblies EATON CORPORATION www eaton com Figure 10 Circuit Breaker Installation with Portable Breaker Lifter...

Страница 14: ...pment Please inspect the packet attached to the outside or within an empty cell for all pertinent documentation before contact ing an Eaton service representative for replacements 2A97855 Magnum DS St...

Страница 15: ...15 Instruction Booklet IB01900002E Effective June 2011 Instructions for Magnum DS Metal Enclosed Low Voltage NEMA 3R Assemblies EATON CORPORATION www eaton com Notes...

Страница 16: ...ment between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the...

Отзывы: