Instructions for Magnum DS Metal-Enclosed

Low-Voltage NEMA 3R Assemblies

 

EATON CORPORATION

 www.eaton.com

1.2 Safety Features

Each Magnum DS Assembly is manufactured with built-in interlocks 

and safety-related features. They are provided to reduce hazards to 

operating personnel and provide proper operating sequences.

DANGER

METAL-ENCLOSED LOW-VOLTAGE ASSEMBLIES ARE PROVIDED WITH 

MANY SAFETY FEATURES.  NEVERTHELESS, WHEN CONNECTED THEY 

CONTAIN POWER CIRCUITS WITH HIGH FAULT CAPACITY. THE VOLTAGES 

AND POWER LEVELS AVAILABLE IN THIS EQUIPMENT MAKE CONTACT 

WITH BARE CONDUCTORS OR TERMINALS EXTREMELY DANGEROUS, 

AND IS LIKELY TO BE FATAL.  ALL POWER SHOULD BE TURNED OFF OR 

APPROPRIATE PROTECTIVE EQUIPMENT USED WHEN WORKING ON SUCH 

EQUIPMENT. IN ADDITION TO THE HAZARDS INHERENT TO THE LOW-

VOLTAGE ASSEMBLY ITSELF, OPERATION BY UNQUALIFIED PERSONS MAY 

CAUSE INDIRECT DAMAGE TO CONNECTED EQUIPMENT AND INJURY TO 

OPERATORS OF CONNECTED EQUIPMENT 

 

UNDER NO CIRCUMSTANCE SHOULD THE INTERLOCKS OR OTHER SAFETY 

FEATURES BE MADE INOPERATIVE OR DISABLED, AS THIS MAY RESULT IN 

DEATH, BODILY INJURY OR PROPERTY DAMAGE. 

 

TO PROTECT PERSONNEL DURING THE INSTALLATION, OPERATION 

AND MAINTENANCE OF THIS, THE FOLLOWING PRACTICES MUST BE 
FOLLOWED:

1.3 Safety Practices

WARNING

MAGNUM DS LOW-VOLTAGE SWITCHGEAR AND SWITCHBOARD 

ASSEMBLIES ARE COMPLEX, HIGH CURRENT ELECTRICAL EQUIPMENT 

DESIGNED TO OPERATE WITHIN THE VOLTAGE AND CURRENT 

LIMITATIONS SHOWN ON THEIR RESPECTIVE NAMEPLATES.  DO 

NOT APPLY THIS EQUIPMENT TO SYSTEMS WITH VOLTAGES AND/OR 

CURRENTS IN EXCESS OF THESE LIMITS.

1.  Only qualified electrical personnel familiar with the construction 

and operation of this equipment and the associated hazards 

should be permitted to work on such equipment. Additionally, 

only qualified personnel should be permitted to install or operate 

such equipment.

2.  Always be certain that the primary and secondary circuits are de-

energized before attempting any maintenance

3.  For maximum safety, only insert a completely assembled breaker 

into an energized cell. Front covers are safety features and must 

be in place when energized.

4.  While in the assembly, always ensure that drawout circuit bea-

kers are in one of three intended positions: “Connect”, “Test” or 

“Disconnect”.  A circuit breaker permitted to remain in an inter-

mediate position could result in control circuits being improperly 

connected causing other equipment to malfunction

5.  Do not remove access covers unless the circuits to be exposed 

are de-energized.

6.  Use calibrated test equipment of known reliability to confirm that 

all circuits are de-energized before servicing

7.  After maintenance, be certain every current transformer second-

ary circuit is completely connected or shorted. 

DANGER

IF THE SECONDARY CIRCUIT OF ANY CURRENT TRANSFORMER IS LEFT 

OPEN WITHOUT LOAD, AND ITS PRIMARY CIRCUIT IS ENERGIZED, A 

DANGEROUSLY HIGH VOLTAGE IS DEVELOPED ACROSS TRANSFORMER 

SECONDARY TERMINALS. TO PREVENT DEATH, BODILY INJURY OR 

ELECTRICAL SHOCK, EITHER DE-ENERGIZE THE CIRCUIT BY OPENING THE 

BREAKER, OR SHORT CIRCUIT CURRENT TRANSFORMER SECONDARY 

TERMINALS, BEFORE ENERGIZING THE CIRCUIT AND PROCEEDING WITH 

MAINTENANCE.

8.  Always be certain that all assembly hardware is in place and 

bolted tightly before inserting a drawout circuit breaker into its 

compartment.

WARNING

FAILURE TO FOLLOW THESE DIRECTIONS MAY RESULT IN DEATH, SERIOUS 

BODILY INJURY OR PROPERTY DAMAGE.

1.4 Qualified Personnel

For the purpose of operating switchgear and switchboard assem-

blies, a person who has been thoroughly trained in the operation of 

circuit breakers and any included instrumentation and who has com-

plete knowledge of the loads connected to the assembly may be 

considered to be a qualified person.
For the purpose of installing, inspecting and maintaining switchgear 

and switchboard assemblies, a qualified person 

MUST

 also be a 

qualified electrician, who is thoroughly trained in regard to recogniz-

ing and avoiding the hazards inherent to working with electricity 

and in the proper way to perform such work. The individual must be 

able to de-energize, clear and lockout/tagout circuits in accordance 

with established safety practices. In addition, the individual must 

be equipped with, and trained in the use of, Personal Protective 

Equipment (PPE) (rubber gloves, arc-flash clothes, etc.) for those 

occasions when it is not possible to de-energize all circuits before 

doing maintenance work in the area.

1.5 Precautions

1.  If relays are included, remove all blocking. Check control circuits 

(except voltage and current transformer circuits) for grounds and 

short circuits before applying control power.

2.  Connect the assembly to the station ground before applying any 

power

3.  In case of fire, do not use liquid fire extinguisher until all circuits 

have been disconnected.

4.  If an assembly is to be stored for an extended period prior to 

installation, provisions must be made for energizing the space 

heaters to prevent condensation of moisture inside the assem-

bly.

1.6 Other Publications and Documentation

In addition to this instruction manual, other printed information and 

documentation is supplied with each assembly. This additional infor-

mation will include, but not necessarily be limited to, a Magnum DS 

Low-Voltage Power Circuit Breaker instruction manual, arrangement 

drawings, and connection diagrams.  For additional references see 

Section 6. 

 

 

 

Содержание Magnum DS

Страница 1: ...andling and Storage 4 3 Equipment Description 5 4 Installation 11 5 Inspection Testing and Maintenance 14 6 Document References 14 Effective June 2011 Instruction Booklet IB01900002E Instructions for...

Страница 2: ...1 Introduction 1 1 General Information Magnum DS Metal Enclosed Low Voltage NEMA 3R Switchgear and Switchboard Assemblies are uniquely designed for use in outdoor environments or other harsh conditio...

Страница 3: ...rm that all circuits are de energized before servicing 7 After maintenance be certain every current transformer second ary circuit is completely connected or shorted DANGER IF THE SECONDARY CIRCUIT OF...

Страница 4: ...ial until it is certain that every item has been received in the proper condition and that certain packing material will not be required later for equipment storage Larger items such as portable trave...

Страница 5: ...iptions apply to standard metal enclosed con struction and wiring Special features and control schemes are often incorporated per customer specifications These special features are evident and portray...

Страница 6: ...xternal shell and the internal breaker enclosure is approximately 7 5 inches 190 mm therefore the need for a means of emergency exit is not provided Note N A unique feature of the non walk in assembly...

Страница 7: ...9255C35 120 0 3047 OVERALL DEPTH 18 4 468 BUS OPENING FROM BASE 109 1 2772 105 1 2668 51 2 1301 2 0 51 4 0 102 3 9 99 2 3 58 28 6 726 FROM BASE 26 0 660 43 4 1102 AISLE WIDTH 117 1 2974 BASE 30 2 767...

Страница 8: ...Assemblies EATON CORPORATION www eaton com Figure 4 Side Elevation NEMA 3R Assembly Rear Accessible without Walk in Aisle Way C C 9259C06 86 0 2185 BASE 26 0 660 28 6 726 FROM BASE 51 2 1301 2 0 51 4...

Страница 9: ...ON CORPORATION www eaton com Figure 5 Side Elevation NEMA 3R Assembly Front Accessible with Walk In Aisle Way 8652C19 87 1 2211 OVERALL DEPTH 29 1 740 111 4 2830 107 9 2740 2 0 51 3 9 99 111 5 2832 OV...

Страница 10: ...d Low Voltage NEMA 3R Assemblies EATON CORPORATION www eaton com Figure 6 Side Elevation NEMA 3R Assembly Front Accessible without Walk In Aisle Way 8652C25 54 2 1378 BASE 105 1 2669 110 3 2800 109 8...

Страница 11: ...tion to avoid distortion of the structure The lifting plates attached at the base perform the dual purpose of providing a convenient and robust method of securing the unit to the foundation A separate...

Страница 12: ...n sales office 4 4 Bus Cable and Control Connections Refer to Section 4 4 1 thru 4 4 6 of reference IB01901001E for com plete instructions and guidelines on various bus connections installa tion of po...

Страница 13: ...900002E Effective June 2011 Instructions for Magnum DS Metal Enclosed Low Voltage NEMA 3R Assemblies EATON CORPORATION www eaton com Figure 10 Circuit Breaker Installation with Portable Breaker Lifter...

Страница 14: ...pment Please inspect the packet attached to the outside or within an empty cell for all pertinent documentation before contact ing an Eaton service representative for replacements 2A97855 Magnum DS St...

Страница 15: ...15 Instruction Booklet IB01900002E Effective June 2011 Instructions for Magnum DS Metal Enclosed Low Voltage NEMA 3R Assemblies EATON CORPORATION www eaton com Notes...

Страница 16: ...ment between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the...

Отзывы: