![Eaton INDGW-X2 Скачать руководство пользователя страница 50](http://html.mh-extra.com/html/eaton/indgw-x2/indgw-x2_user-manual_525442050.webp)
Protection
Contextual help of the web interface – 52
•
•
•
•
•
•
•
•
•
Software is not able to communicate with the Network module
Symptoms
Contextual help>>>Protection>>>Agent list>>>Agent list table
a status.
In the Network Module, in
Contextual help>>>Settings>>>Certificate>>>Trusted remote certificates
the Protected applications (MQTT) is showing "Not valid yet".
IPP/IPM shows "The authentication has failed", "The notifications reception encountered error".
Possible cause
The IPP/IPM certificate is not yet valid for the Network Module.
Certificates of IPP/IPM and the Network Module are not matching so that authentication and encryption of connections
between the Network Module and the shutdown agents is not working.
Setup
IPP/IPM is started.
Network module is connected to the UPS and to the network.
Action #1
Check if the IPP/IPM certificate validity for the Network Module.
STEP 1: Connect to the Network Module
On a network computer, launch a supported web browser. The browser window appears.
In the Address/Location field, enter: https://xxx.xxx.xxx.xxx/ where xxx.xxx.xxx.xxx is the static IP address of the
Network Module.
The log in screen appears.
Enter the user name in the User Name field.
Enter the password in the Password field.
Click Login. The Network Module web interface appears.
STEP 2: Navigate to Settings/Certificates page
STEP 3: In the Trusted remote certificates section, check the status of the Protected applications (MQTT).
If it is "Valid" go to Action#2 STEP 2, if it is "Not yet valid", time of the need to be synchronized with IPP/IPM .
STEP 4: Synchronize the time of the Network Module with IPP/IPM and check that the status of the Protected applications
(MQTT) is now valid.
Communication will then recover, if not go to Action#2 STEP 2.
Action #2
Pair agent to the Network Module with automatic acceptance (recommended in case the installation is done in a secure and
trusted network).
For manual pairing (maximum security), go to
Содержание INDGW-X2
Страница 1: ...UPS Industrial Gateway Card INDGW X2 User s Guide English 10 18 2021 2 2 3 ...
Страница 23: ...Configuring Modbus Installing the Network Management Module 25 ...
Страница 24: ...Configuring Modbus Installing the Network Management Module 26 ...
Страница 25: ...Configuring Modbus Installing the Network Management Module 27 ...
Страница 26: ...Configuring Modbus Installing the Network Management Module 28 ...
Страница 35: ...Home Contextual help of the web interface 37 3 2 7 1 3 Battery mode 3 2 7 1 4 Off mode ...
Страница 37: ...Home Contextual help of the web interface 39 3 2 7 2 2 Bypass mode 3 2 7 2 3 Battery mode ...
Страница 61: ...Protection Contextual help of the web interface 63 Example 4 Custom ...
Страница 62: ...Protection Contextual help of the web interface 64 Settings 1 Settings 2 ...
Страница 218: ...Default settings and possible parameters Information 220 ...
Страница 266: ...Acronyms and abbreviations Information 268 ...
Страница 273: ......