Diagnostics

22

H-Max HVAC Drives

    MN04008004E—September 2011    www.eaton.com

Fault Codes and Descriptions, continued

Fault 
Code

Fault
ID

Fault Name

Possible Cause

Remedy

44

430

Device changed
(different type)

Option board changed for one not present 
in the same slot before. No parameter 
settings are saved

Set the option board parameters again

45

440

Device changed
(different type)

Option board added. The option board was 
not previously present in the same slot. No 
parameter settings are saved

Set the option board parameters again

51

1051

External fault

Digital input

52

1052

Keypad communication
fault

The connection between the control 
keypad and frequency converter is broken

Check keypad connection and possible keypad 
cable

1352

53

1053

Fieldbus communication
fault

The data connection between the Fieldbus 
master and Fieldbus board is broken

Check installation and Fieldbus master

54

1354

Slot A fault

Defective option board or slot

Check board and slot

1454

Slot B fault

1654

Slot D fault

1754

Slot E fault

65

1065

PC communication fault

The data connection between the PC and 
frequency converter is broken

66

1066

Thermistor fault

The thermistor input has detected an 
increase of motor temperature

Check motor cooling and load

Check thermistor connection (if 
thermistor input is not in use it has to 
be short circuited)

69

1310

Fieldbus mapping error

Non-existing ID number is used for 
mapping values to Fieldbus Process 
Data Out

Check parameters in Fieldbus Data Mapping 
menu

1311

Not possible to convert one or more 
values for Fieldbus Process Data Out

The value being mapped may be of undefined 
type. Check parameters in Fieldbus Data 
Mapping menu

1312

Overflow when mapping and converting 
values for Fieldbus Process Data Out 
(16-bit)

101

1101

Process supervision fault
(PID1)

PID controller: Feedback value outside 
of supervision limits (and the delay if set)

105

1105

Process supervision fault
(PID2)

PID controller: Feedback value outside 
of supervision limits (and the delay if set)

Содержание H-Max Series

Страница 1: ...H Max HVAC Drives Quick Start Guide Effective September 2011 Supersedes August 2011...

Страница 2: ......

Страница 3: ...RTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCU...

Страница 4: ...77 ETN CARE 386 2273 8 00 a m 6 00 p m EST FAX 800 752 8602 After Hours Emergency 800 543 7038 6 00 p m 8 00 a m EST If you are in the U S or Canada and have OI or PLC questions you can take advantage...

Страница 5: ...or Fieldbus Control page for easy operation and monitoring of the most essential values Run interlock input damper interlock Drive will not start before this input is activated Different pre heat mod...

Страница 6: ...ode Force Bypass Contact closed bypass DIN1 DIN6 Common Output Frequency 0 20 mA Analog Output Common Ground RS 485 DATA Speed Select 0 100 Preset speed U T1 V T2 W T3 R R L1 L2 L3 Three Phase Input I...

Страница 7: ...the EMEA Keypad Functionality is quite similar The EMEA keypad does not support the bypass functionality commonly used in the United States US Keypad Buttons EMEA Keypad Buttons Switching Between Driv...

Страница 8: ...r current location The Status field gives information about the present status of the drive See Control Connections on Page 2 Main Menu Using the Graphical Keypad Editing Values Change value of a para...

Страница 9: ...is always used as control place while in hand control Hand control has higher priority than auto control Therefore if for example bypassed by parameter P2 1 17 through digital input while in Remote th...

Страница 10: ...other control places or reference values are used the display will show Frequency reference which is not editable The other values on the page are Multimonitoring values You can choose which values ap...

Страница 11: ...talled Now the Startup Wizard is done The Startup Wizard can be re initiated by pressing and holding the back reset button for two seconds The Startup Wizard will appear upon next power up 1 Run Start...

Страница 12: ...dBack1 Srce AI2 AI1 Not Used ProceDataIn8 ProceDataIn7 ProceDataIn6 ProceDataIn5 ProceDataIn4 ProceDataIn3 ProceDataIn2 ProceDataIn1 AI6 AI5 AI4 AI3 2 Process Unit Selection Several Selections 3 Proce...

Страница 13: ...d Menus Monitor Basic Diagnostics Active Faults Timer Functions Reset Faults Multimonitor Fault History Parameters Basic Parameters Total Counters Analog Inputs Trip Counters Digital Inputs Software I...

Страница 14: ...Motor Nom Freq 111 P2 1 15 Motor Nom Speed 112 P2 1 16 MotorPowerFactor 120 P2 1 17 Current Limit 107 P2 1 18 Service Factor 1357 Parameter Group 2 2 Analog Inputs Analog Input 1 P2 2 1 1 AI1 Signal s...

Страница 15: ...5 AI6 Custom Max 203 P2 2 6 6 AI6 Filter Time 200 Parameter Group 2 2 Basic Parameters Basic P2 2 7 1 Ref Scale Min 1307 P2 2 7 2 Ref Scale Max 1308 Parameter Group 2 3 Digital Inputs Digital Input 1...

Страница 16: ...0054 P2 4 1 6 AO1 Invert 10060 Parameter Group 2 5 Digital Outputs Digital Output 1 P2 5 1 1 RO1 function 11001 P2 5 1 2 RO1 Invert 11020 P2 5 1 3 RO1 ON delay 11002 P2 5 1 4 RO1 OFF delay 11003 Digit...

Страница 17: ...0 P2 6 1 15 S Ramp 2 Shape 501 Skip Frequencies P2 6 2 1 Range 1 Low Lim 509 P2 6 2 2 Range 1 High Lim 510 P2 6 2 3 Range 2 Low Lim 511 P2 6 2 4 Range 2 High Lim 512 P2 6 2 5 Range 3 Low Lim 513 P2 6...

Страница 18: ...FieldbusComm Flt 733 P2 8 1 13 InputPhaseFault 730 P2 8 1 14 MotorStall Flt 709 P2 8 1 15 PID1 Supervision 749 P2 8 1 16 PID2 Supervision 757 P2 8 1 17 SlotCommFlt 734 P2 8 1 18 Preset Alarm Freq 183...

Страница 19: ...WakeUpLevel PID Controller 1 1018 P2 9 1 2 10 SP 1 boost PID Controller 1 1071 P2 9 1 2 11 SP 2 Source PID Controller 1 431 P2 9 1 2 12 SP 2 minimum PID Controller 1 1073 P2 9 1 2 13 SP 2 maximum PID...

Страница 20: ...2 1 9 Dead Band PID Controller 2 1637 P2 9 2 1 10 Dead band delay PID Controller 2 1638 PID Controller 2 Setpoints P2 9 2 2 1 Keypad SP 1 PID Controller 2 1640 P2 9 2 2 2 Keypad SP 2 PID Controller 2...

Страница 21: ...1097 P2 12 9 Bandwidth delay 1098 Parameter Group 2 13 Braking Braking P2 13 1 DC Brake Current 507 P2 13 2 DC Time Stop 508 P2 13 3 DC BrakeFreqStop 515 P2 13 4 StartMagnTime 516 P2 13 5 StartMagnCu...

Страница 22: ...l 2 1678 P2 16 2 5 Assign to channel Interval 2 1679 Interval 3 P2 16 3 1 ON Time Interval 3 1680 P2 16 3 2 Off Time Interval 3 1681 P2 16 3 3 From Day Interval 3 1682 P2 16 3 4 To Day Interval 3 1683...

Страница 23: ...in the Fault history Entering the Fault history and clicking OK on the selected fault shows the fault time data details Fault Code Fault ID Fault Name Possible Cause Remedy 1 1 Overcurrent hardware fa...

Страница 24: ...he software for example application has caused an overload situation The source of fault has been suspended Reset the fault and restart Should the fault re occur contact the distributor near you 609 M...

Страница 25: ...odel parameters 17 160 Motor underload Motor is underloaded Check load 19 180 Power overload short time supervision Drive power is too high Decrease load 181 Power overload long time supervision 25 Mo...

Страница 26: ...Slot A fault Defective option board or slot Check board and slot 1454 Slot B fault 1654 Slot D fault 1754 Slot E fault 65 1065 PC communication fault The data connection between the PC and frequency c...

Страница 27: ......

Страница 28: ...nsuring that reliable efficient and safe power is available when it s needed most With unparalleled knowledge of electrical power management across industries experts at Eaton deliver customized integ...

Отзывы: