Parameter List

H-Max HVAC Drives

    MN04008004E—September 2011    www.eaton.com

15

Parameter Group 2.9—PID Controller

PID Controller 1, Basic Settings

P2.9.1.1.1

Gain, PID Controller 1

118

P2.9.1.1.2

Integration Time, PID Controller 1

119

P2.9.1.1.3

Derivation Time, PID Controller 1

132

P2.9.1.1.4

ProcessUnitSel, PID Controller 1

1036

P2.9.1.1.5

ProcessUnitMin, PID Controller 1

1033

P2.9.1.1.6

ProcessUnitMax, PID Controller 1

1034

P2.9.1.1.7

ProcessUnitDecimals, PID Controller 1

1035

P2.9.1.1.8

Error Inversion, PID Controller 1

340

P2.9.1.1.9

Dead Band, PID Controller 1

1056

P2.9.1.1.10

Dead band delay, PID Controller 1

1057

PID Controller 1, Setpoints

P2.9.1.2.1

Keypad SP 1, PID Controller 1

167

P2.9.1.2.2

Keypad SP 2, PID Controller 1

168

P2.9.1.2.3

Ramp Time, PID Controller 1

1068

P2.9.1.2.4

SetPt 1 Source, PID Controller 1

332

P2.9.1.2.5

SetPt 1 min, PID Controller 1

1069

P2.9.1.2.6

SP 1 maximum, PID Controller 1

1070

P2.9.1.2.7

SP 1 Sleep Freq, PID Controller 1

1016

P2.9.1.2.8

SP 1 Sleep delay, PID Controller 1

1017

P2.9.1.2.9

SP 1 WakeUpLevel, PID Controller 1

1018

P2.9.1.2.10

SP 1 boost, PID Controller 1

1071

P2.9.1.2.11

SP 2 Source, PID Controller 1

431

P2.9.1.2.12

SP 2 minimum, PID Controller 1

1073

P2.9.1.2.13

SP 2 maximum, PID Controller 1

1074

P2.9.1.2.14

SP 2 Sleep Freq, PID Controller 1

1075

P2.9.1.2.15

SP 2 Sleep delay, PID Controller 1

1076

P2.9.1.2.16

SP 2 WakeUpLevel, PID Controller 1

1077

P2.9.1.2.17

SP 2 boost, PID Controller 1

1078

PID Controller 1, Feedbacks

P2.9.1.3.1

Function, PID Controller 1

333

P2.9.1.3.2

Gain, PID Controller 1

1058

P2.9.1.3.3

FeedBack 1 Srce, PID Controller 1

334

P2.9.1.3.4

FB 1 Minimum, PID Controller 1

336

P2.9.1.3.5

FB 1 Maximum, PID Controller 1

337

P2.9.1.3.6

FB 2 Source, PID Controller 1

335

P2.9.1.3.7

FB 2 Minimum, PID Controller 1

338

P2.9.1.3.8

FB 2 Maximum, PID Controller 1

339

PID Controller 1, Feedforward

P2.9.1.4.1

Function, PID Controller 1

1059

P2.9.1.4.2

Gain, PID Controller 1

1060

P2.9.1.4.3

FF 1 Source, PID Controller 1

1061

P2.9.1.4.4

FF1 Minimum, PID Controller 1

1062

P2.9.1.4.5

FF1 Maximum, PID Controller 1

1063

P2.9.1.4.6

FF 2 Source, PID Controller 1

1064

P2.9.1.4.7

FF2 Minimum, PID Controller 1

1065

P2.9.1.4.8

FF2 Maximum, PID Controller 1

1066

Parameter Group Name

Parameter Number

Parameter Name

ID

Содержание H-Max Series

Страница 1: ...H Max HVAC Drives Quick Start Guide Effective September 2011 Supersedes August 2011...

Страница 2: ......

Страница 3: ...RTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCU...

Страница 4: ...77 ETN CARE 386 2273 8 00 a m 6 00 p m EST FAX 800 752 8602 After Hours Emergency 800 543 7038 6 00 p m 8 00 a m EST If you are in the U S or Canada and have OI or PLC questions you can take advantage...

Страница 5: ...or Fieldbus Control page for easy operation and monitoring of the most essential values Run interlock input damper interlock Drive will not start before this input is activated Different pre heat mod...

Страница 6: ...ode Force Bypass Contact closed bypass DIN1 DIN6 Common Output Frequency 0 20 mA Analog Output Common Ground RS 485 DATA Speed Select 0 100 Preset speed U T1 V T2 W T3 R R L1 L2 L3 Three Phase Input I...

Страница 7: ...the EMEA Keypad Functionality is quite similar The EMEA keypad does not support the bypass functionality commonly used in the United States US Keypad Buttons EMEA Keypad Buttons Switching Between Driv...

Страница 8: ...r current location The Status field gives information about the present status of the drive See Control Connections on Page 2 Main Menu Using the Graphical Keypad Editing Values Change value of a para...

Страница 9: ...is always used as control place while in hand control Hand control has higher priority than auto control Therefore if for example bypassed by parameter P2 1 17 through digital input while in Remote th...

Страница 10: ...other control places or reference values are used the display will show Frequency reference which is not editable The other values on the page are Multimonitoring values You can choose which values ap...

Страница 11: ...talled Now the Startup Wizard is done The Startup Wizard can be re initiated by pressing and holding the back reset button for two seconds The Startup Wizard will appear upon next power up 1 Run Start...

Страница 12: ...dBack1 Srce AI2 AI1 Not Used ProceDataIn8 ProceDataIn7 ProceDataIn6 ProceDataIn5 ProceDataIn4 ProceDataIn3 ProceDataIn2 ProceDataIn1 AI6 AI5 AI4 AI3 2 Process Unit Selection Several Selections 3 Proce...

Страница 13: ...d Menus Monitor Basic Diagnostics Active Faults Timer Functions Reset Faults Multimonitor Fault History Parameters Basic Parameters Total Counters Analog Inputs Trip Counters Digital Inputs Software I...

Страница 14: ...Motor Nom Freq 111 P2 1 15 Motor Nom Speed 112 P2 1 16 MotorPowerFactor 120 P2 1 17 Current Limit 107 P2 1 18 Service Factor 1357 Parameter Group 2 2 Analog Inputs Analog Input 1 P2 2 1 1 AI1 Signal s...

Страница 15: ...5 AI6 Custom Max 203 P2 2 6 6 AI6 Filter Time 200 Parameter Group 2 2 Basic Parameters Basic P2 2 7 1 Ref Scale Min 1307 P2 2 7 2 Ref Scale Max 1308 Parameter Group 2 3 Digital Inputs Digital Input 1...

Страница 16: ...0054 P2 4 1 6 AO1 Invert 10060 Parameter Group 2 5 Digital Outputs Digital Output 1 P2 5 1 1 RO1 function 11001 P2 5 1 2 RO1 Invert 11020 P2 5 1 3 RO1 ON delay 11002 P2 5 1 4 RO1 OFF delay 11003 Digit...

Страница 17: ...0 P2 6 1 15 S Ramp 2 Shape 501 Skip Frequencies P2 6 2 1 Range 1 Low Lim 509 P2 6 2 2 Range 1 High Lim 510 P2 6 2 3 Range 2 Low Lim 511 P2 6 2 4 Range 2 High Lim 512 P2 6 2 5 Range 3 Low Lim 513 P2 6...

Страница 18: ...FieldbusComm Flt 733 P2 8 1 13 InputPhaseFault 730 P2 8 1 14 MotorStall Flt 709 P2 8 1 15 PID1 Supervision 749 P2 8 1 16 PID2 Supervision 757 P2 8 1 17 SlotCommFlt 734 P2 8 1 18 Preset Alarm Freq 183...

Страница 19: ...WakeUpLevel PID Controller 1 1018 P2 9 1 2 10 SP 1 boost PID Controller 1 1071 P2 9 1 2 11 SP 2 Source PID Controller 1 431 P2 9 1 2 12 SP 2 minimum PID Controller 1 1073 P2 9 1 2 13 SP 2 maximum PID...

Страница 20: ...2 1 9 Dead Band PID Controller 2 1637 P2 9 2 1 10 Dead band delay PID Controller 2 1638 PID Controller 2 Setpoints P2 9 2 2 1 Keypad SP 1 PID Controller 2 1640 P2 9 2 2 2 Keypad SP 2 PID Controller 2...

Страница 21: ...1097 P2 12 9 Bandwidth delay 1098 Parameter Group 2 13 Braking Braking P2 13 1 DC Brake Current 507 P2 13 2 DC Time Stop 508 P2 13 3 DC BrakeFreqStop 515 P2 13 4 StartMagnTime 516 P2 13 5 StartMagnCu...

Страница 22: ...l 2 1678 P2 16 2 5 Assign to channel Interval 2 1679 Interval 3 P2 16 3 1 ON Time Interval 3 1680 P2 16 3 2 Off Time Interval 3 1681 P2 16 3 3 From Day Interval 3 1682 P2 16 3 4 To Day Interval 3 1683...

Страница 23: ...in the Fault history Entering the Fault history and clicking OK on the selected fault shows the fault time data details Fault Code Fault ID Fault Name Possible Cause Remedy 1 1 Overcurrent hardware fa...

Страница 24: ...he software for example application has caused an overload situation The source of fault has been suspended Reset the fault and restart Should the fault re occur contact the distributor near you 609 M...

Страница 25: ...odel parameters 17 160 Motor underload Motor is underloaded Check load 19 180 Power overload short time supervision Drive power is too high Decrease load 181 Power overload long time supervision 25 Mo...

Страница 26: ...Slot A fault Defective option board or slot Check board and slot 1454 Slot B fault 1654 Slot D fault 1754 Slot E fault 65 1065 PC communication fault The data connection between the PC and frequency c...

Страница 27: ......

Страница 28: ...nsuring that reliable efficient and safe power is available when it s needed most With unparalleled knowledge of electrical power management across industries experts at Eaton deliver customized integ...

Отзывы: