Diagnostics
20
H-Max HVAC Drives
MN04008004E—September 2011 www.eaton.com
Fault Codes and Descriptions, continued
Fault
Code
Fault
ID
Fault Name
Possible Cause
Remedy
7
60
Saturation
Various causes:
•
Defective component
•
Brake resistor short-circuit or overload
•
Cannot be reset from keypad
•
Switch off power
•
DO NOT RECONNECT POWER! Contact
factory
•
If this fault appears simultaneously with
F1, check motor cables and motor
8
600
System fault
Communication between control board
and power unit has failed
Reset the fault and restart. Should the fault
re-occur, contact the distributor near you
602
Watchdog has reset the CPU
603
Voltage of auxiliary power in power unit
is too low
604
Phase fault: Voltage of an output phase
does not follow the reference
605
CPLD has faulted but there is no detailed
information about the fault
606
Control and power unit software are
incompatible
Update software. Should the fault re-occur,
contact the distributor near you
607
Software version cannot be read. There is
no software in power unit
Update power unit software. Should the fault
re-occur, contact the distributor near you
608
CPU overload. Some part of the software
(for example application) has caused an
overload situation. The source of fault
has been suspended
Reset the fault and restart. Should the fault
re-occur, contact the distributor near you
609
Memory access has failed. For example,
retain variables could not be restored
610
Necessary device properties cannot be read
647
Software error
Update software. Should the fault re-occur,
contact the distributor near you
648
Invalid function block used in application.
System software and application are not
compatible
649
Resource overload:
•
Error when loading parameter initial
values
•
Error when restoring parameters
•
Error when saving parameters
9
80
Undervoltage
(fault)
DC link voltage is under the voltage limits
defined:
•
Most probable cause: Too low a supply
voltage
•
AC drive internal fault
•
Defect input fuse
•
External charge switch not closed
Note:
This fault is activated only if the drive
is in Run state.
In case of temporary supply voltage break reset
the fault and restart the AC drive. Check the
supply voltage. If it is adequate, an internal
failure has occurred. Contact the distributor
near you
81
Undervoltage
(alarm)
10
91
Input phase
Input line phase is missing
Check supply voltage, fuses and cable
11
100
Output phase
supervision
Current measurement has detected that there
is no current in one motor phase
Check motor cable and motor