Diagnostics

20

H-Max HVAC Drives

    MN04008004E—September 2011    www.eaton.com

Fault Codes and Descriptions, continued

Fault 
Code

Fault
ID

Fault Name

Possible Cause

Remedy

7

60

Saturation

Various causes:

Defective component

Brake resistor short-circuit or overload

Cannot be reset from keypad

Switch off power

DO NOT RECONNECT POWER! Contact 
factory

If this fault appears simultaneously with 
F1, check motor cables and motor

8

600

System fault

Communication between control board 
and power unit has failed

Reset the fault and restart. Should the fault 
re-occur, contact the distributor near you

602

Watchdog has reset the CPU

603

Voltage of auxiliary power in power unit 
is too low

604

Phase fault: Voltage of an output phase 
does not follow the reference

605

CPLD has faulted but there is no detailed 
information about the fault

606

Control and power unit software are 
incompatible

Update software. Should the fault re-occur, 
contact the distributor near you

607

Software version cannot be read. There is 
no software in power unit

Update power unit software. Should the fault 
re-occur, contact the distributor near you

608

CPU overload. Some part of the software 
(for example application) has caused an 
overload situation. The source of fault 
has been suspended

Reset the fault and restart. Should the fault 
re-occur, contact the distributor near you

609

Memory access has failed. For example, 
retain variables could not be restored

610

Necessary device properties cannot be read

647

Software error

Update software. Should the fault re-occur, 
contact the distributor near you

648

Invalid function block used in application. 
System software and application are not 
compatible

649

Resource overload:

Error when loading parameter initial 
values

Error when restoring parameters

Error when saving parameters

9

80

Undervoltage
(fault)

DC link voltage is under the voltage limits 
defined:

Most probable cause: Too low a supply 
voltage

AC drive internal fault

Defect input fuse

External charge switch not closed

Note:

 This fault is activated only if the drive 

is in Run state.

In case of temporary supply voltage break reset 
the fault and restart the AC drive. Check the 
supply voltage. If it is adequate, an internal 
failure has occurred. Contact the distributor 
near you

81

Undervoltage
(alarm)

10

91

Input phase

Input line phase is missing

Check supply voltage, fuses and cable

11

100

Output phase
supervision

Current measurement has detected that there 
is no current in one motor phase

Check motor cable and motor

Содержание H-Max Series

Страница 1: ...H Max HVAC Drives Quick Start Guide Effective September 2011 Supersedes August 2011...

Страница 2: ......

Страница 3: ...RTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCU...

Страница 4: ...77 ETN CARE 386 2273 8 00 a m 6 00 p m EST FAX 800 752 8602 After Hours Emergency 800 543 7038 6 00 p m 8 00 a m EST If you are in the U S or Canada and have OI or PLC questions you can take advantage...

Страница 5: ...or Fieldbus Control page for easy operation and monitoring of the most essential values Run interlock input damper interlock Drive will not start before this input is activated Different pre heat mod...

Страница 6: ...ode Force Bypass Contact closed bypass DIN1 DIN6 Common Output Frequency 0 20 mA Analog Output Common Ground RS 485 DATA Speed Select 0 100 Preset speed U T1 V T2 W T3 R R L1 L2 L3 Three Phase Input I...

Страница 7: ...the EMEA Keypad Functionality is quite similar The EMEA keypad does not support the bypass functionality commonly used in the United States US Keypad Buttons EMEA Keypad Buttons Switching Between Driv...

Страница 8: ...r current location The Status field gives information about the present status of the drive See Control Connections on Page 2 Main Menu Using the Graphical Keypad Editing Values Change value of a para...

Страница 9: ...is always used as control place while in hand control Hand control has higher priority than auto control Therefore if for example bypassed by parameter P2 1 17 through digital input while in Remote th...

Страница 10: ...other control places or reference values are used the display will show Frequency reference which is not editable The other values on the page are Multimonitoring values You can choose which values ap...

Страница 11: ...talled Now the Startup Wizard is done The Startup Wizard can be re initiated by pressing and holding the back reset button for two seconds The Startup Wizard will appear upon next power up 1 Run Start...

Страница 12: ...dBack1 Srce AI2 AI1 Not Used ProceDataIn8 ProceDataIn7 ProceDataIn6 ProceDataIn5 ProceDataIn4 ProceDataIn3 ProceDataIn2 ProceDataIn1 AI6 AI5 AI4 AI3 2 Process Unit Selection Several Selections 3 Proce...

Страница 13: ...d Menus Monitor Basic Diagnostics Active Faults Timer Functions Reset Faults Multimonitor Fault History Parameters Basic Parameters Total Counters Analog Inputs Trip Counters Digital Inputs Software I...

Страница 14: ...Motor Nom Freq 111 P2 1 15 Motor Nom Speed 112 P2 1 16 MotorPowerFactor 120 P2 1 17 Current Limit 107 P2 1 18 Service Factor 1357 Parameter Group 2 2 Analog Inputs Analog Input 1 P2 2 1 1 AI1 Signal s...

Страница 15: ...5 AI6 Custom Max 203 P2 2 6 6 AI6 Filter Time 200 Parameter Group 2 2 Basic Parameters Basic P2 2 7 1 Ref Scale Min 1307 P2 2 7 2 Ref Scale Max 1308 Parameter Group 2 3 Digital Inputs Digital Input 1...

Страница 16: ...0054 P2 4 1 6 AO1 Invert 10060 Parameter Group 2 5 Digital Outputs Digital Output 1 P2 5 1 1 RO1 function 11001 P2 5 1 2 RO1 Invert 11020 P2 5 1 3 RO1 ON delay 11002 P2 5 1 4 RO1 OFF delay 11003 Digit...

Страница 17: ...0 P2 6 1 15 S Ramp 2 Shape 501 Skip Frequencies P2 6 2 1 Range 1 Low Lim 509 P2 6 2 2 Range 1 High Lim 510 P2 6 2 3 Range 2 Low Lim 511 P2 6 2 4 Range 2 High Lim 512 P2 6 2 5 Range 3 Low Lim 513 P2 6...

Страница 18: ...FieldbusComm Flt 733 P2 8 1 13 InputPhaseFault 730 P2 8 1 14 MotorStall Flt 709 P2 8 1 15 PID1 Supervision 749 P2 8 1 16 PID2 Supervision 757 P2 8 1 17 SlotCommFlt 734 P2 8 1 18 Preset Alarm Freq 183...

Страница 19: ...WakeUpLevel PID Controller 1 1018 P2 9 1 2 10 SP 1 boost PID Controller 1 1071 P2 9 1 2 11 SP 2 Source PID Controller 1 431 P2 9 1 2 12 SP 2 minimum PID Controller 1 1073 P2 9 1 2 13 SP 2 maximum PID...

Страница 20: ...2 1 9 Dead Band PID Controller 2 1637 P2 9 2 1 10 Dead band delay PID Controller 2 1638 PID Controller 2 Setpoints P2 9 2 2 1 Keypad SP 1 PID Controller 2 1640 P2 9 2 2 2 Keypad SP 2 PID Controller 2...

Страница 21: ...1097 P2 12 9 Bandwidth delay 1098 Parameter Group 2 13 Braking Braking P2 13 1 DC Brake Current 507 P2 13 2 DC Time Stop 508 P2 13 3 DC BrakeFreqStop 515 P2 13 4 StartMagnTime 516 P2 13 5 StartMagnCu...

Страница 22: ...l 2 1678 P2 16 2 5 Assign to channel Interval 2 1679 Interval 3 P2 16 3 1 ON Time Interval 3 1680 P2 16 3 2 Off Time Interval 3 1681 P2 16 3 3 From Day Interval 3 1682 P2 16 3 4 To Day Interval 3 1683...

Страница 23: ...in the Fault history Entering the Fault history and clicking OK on the selected fault shows the fault time data details Fault Code Fault ID Fault Name Possible Cause Remedy 1 1 Overcurrent hardware fa...

Страница 24: ...he software for example application has caused an overload situation The source of fault has been suspended Reset the fault and restart Should the fault re occur contact the distributor near you 609 M...

Страница 25: ...odel parameters 17 160 Motor underload Motor is underloaded Check load 19 180 Power overload short time supervision Drive power is too high Decrease load 181 Power overload long time supervision 25 Mo...

Страница 26: ...Slot A fault Defective option board or slot Check board and slot 1454 Slot B fault 1654 Slot D fault 1754 Slot E fault 65 1065 PC communication fault The data connection between the PC and frequency c...

Страница 27: ......

Страница 28: ...nsuring that reliable efficient and safe power is available when it s needed most With unparalleled knowledge of electrical power management across industries experts at Eaton deliver customized integ...

Отзывы: