Connecting Relay Loads

LittKttptr® 8

 

Latching Relay Card Wiring

The latching relay is a simple closure, breaking the line and 

load wires of a normal circuit. To wire the relay into the 

control circuit:

1.  Connect a 120, 277 or 347 volt, 20 amp maximum, 

de-energized branch circuit breaker to the relay  

terminal block.

2.  Connect the load wiring to the output terminal block.

otte:

N

Terminal blocks are not polarity sensitive although it 

is recommended that line and load be brought into 

terminal blocks in the same manner for consistency.

3.  Tighten down relay terminal screws. Manufacturer’s 

recommended torque rating is 18 lb-in.  

(1.475 foot-lbs) (2.0 Nm).

4.  Document relay to circuit information for  

future reference.

 

Q1

U1

U2

U3

SR1

RP1

RP2

K8

K6

K2

K4

MOV 2

MOV 4

MOV 6

MOV 8

Q2

RN1

TB2

TB4

TB6

TB8

LED 1

Latching Relay Card Wiring

Modular Relay Card Notes

The Modular Relay Card provides flexible options for relay 

control. It is designed to allow modular relay control by 

allowing you to install a variety of relay module types on 

the same relay card. Current available relay module types 

include a Two Pole Relay Module (TPRM) Normally Open, 

the Latching Relay Module (LRM) and the Standard  

Relay Module (SRM).

K1

MOV1

TB1

U1

RP1

R4

R4

RP1

U1

TB1

MOV1

K1

MOV1

TB1

K1

Modular Relay Card

Standard Relay Module

1.  The Standard Relay Module is rated for single-pole 

load use only. Connection of 2 pole circuits/loads to 

the Standard Relay Module will void the equipment 

warranty and may result in severe injury or death, and/

or damage to the equipment.

2.  Relay ratings are 120 or 277 volt, 20 amp maximum.
3.  Relay terminal blocks have a maximum limit of  

10AWG wire.

4.  The SRM contains an LED indicator that will be lit when 

the relay is commanded by the control panel to be in 

the closed position.

Standard Relay Module (Modular Relay Card)

From Branch Circuit

Line

Line

Line 1

Line 2

Modular Relay Card 

Wiring Diagram

LRM

SRM

TPRM

Relay Status 

Indicator LED

Wiring Terminal 

Block

Relay Slot Pin Connector: 

Please note relay number 

location for programming 

purposes.

SRM

Relay Wiring 

Wire: 6 AWG Max. 

Relay Rating: 20amps, 347V

To Lighting Load

Load

Load

Load 1

Load 2

Relay Rating: 20Amps 

208/240/480 VAC 

Wire: 6 AWG max.

Relay Rating: 20Amps 

120/277 VAC 

Wire: 10 AWG max.

Relay Rating: 20Amps 

120/277/347 VAC 

Wire: 6 AWG max.

Содержание Greengate LiteKeeper 8

Страница 1: ...esult in severe injury or death and or damage to the equipment 8 Document all wiring that is terminated to the relays so that the lighting control equipment can be properly configured and programmed f...

Страница 2: ...Relay Card Notes 1 The Standard Relay Card is rated for single pole load use only Connection of 2 pole circuits loads to the Standard Relay Card will void the equipment warranty and may result in seve...

Страница 3: ...urrent available relay module types include a Two Pole Relay Module TPRM Normally Open the Latching Relay Module LRM and the Standard Relay Module SRM K1 MOV1 TB1 U1 RP1 R4 R4 RP1 U1 TB1 MOV1 K1 MOV1...

Страница 4: ...tate 6 There is a manual switch on each relay that indicates relay status and allows for a temporary override of the lighting load If the switch is moved towards the center of the Modular Relay Card t...

Страница 5: ...ement of the relays The Two Pole Relay Card will hold eight 208V two pole relays one in each mounting clip The 480V Two Pole Relay Card uses two mounting clips thus only four relays will fit per card...

Страница 6: ...board when doing initial switch input wiring Contact Input Switch Wiring This section describes the wiring for dry contact closure devices There are eight switch input wiring terminals on the left sid...

Страница 7: ...iteKeeper 8 remote power connector GND terminal 5 Tape back or cap the blue and white wires and shield wire for the cable They will not be used for connection between the GDS I and lighting controller...

Страница 8: ...it is now cleared to factory default programming Programming the LiteKeeper 8 The LiteKeeper 8 is programmed either through the keypad onboard interface or through the optional Keeper Enterprise Softw...

Страница 9: ...nt le processus de c blage Montage l int rieur du bo tier 1 Choisissez un emplacement sec qui convient au panneau lectrique 2 Montez le panneau sur une surface stable l aide des trous pr perc s 3 Bran...

Страница 10: ...de d rivation de 120 ou 277 V 20 A maximum hors tension au bornier du relais 2 Branchez le c blage de charge au bornier de sortie otte N Les borniers ne sont pas sensibles la polarit bien qu il soit...

Страница 11: ...anchez un disjoncteur de d rivation de 120 ou 277 V 20 A maximum hors tension au bornier du relais 2 Branchez le c blage de charge au bornier de sortie otte N Les borniers ne sont pas sensibles la pol...

Страница 12: ...s bipolaires occupent les deux fentes relais dans le bo tier 4 Les relais bipolaires sont normalement en configuration ouverte 5 Un voyant DEL s allume lorsque le relais est contr l par le panneau de...

Страница 13: ...ogique Veuillez v rifier qu il n y a pas de court circuit au c ble de mise la terre c a avant de proc der au branchement des dispositifs d entr e Sans gard au type d entr e les remarques suivantes s a...

Страница 14: ...e c ble sp cifi n est pas utilis et si vous prouvez des probl mes de communications qui exigent de l aide du service de d pannage des frais suppl mentaires peuvent tre applicables Les commutateurs num...

Страница 15: ...alisation une r initialisation logicielle et une r initialisation de suppression La commande de r initialisation logicielle La commande de r initialisation logicielle red marre le microprocesseur Il n...

Страница 16: ...5 8 LIGHTING CONTROL 12 OO O1 O1 0 8 2 4 7 OUTPUTS RELAY 6 5 4 3 8 7 1 6 B 9 C 3 A OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C Sch ma de r f rence...

Страница 17: ...gica para proteger los componentes contra posibles cortocircuitos durante el proceso de cableado Montaje en el recinto 1 Elija una ubicaci n seca que sea conveniente para el panel del disyuntor 2 Mont...

Страница 18: ...os y 20 amperios como m ximo desconecte el disyuntor en el bloque de terminales del rel 2 Conecte los cables de carga en el bloque de terminales de salida otte N Los bloques de terminales no son sensi...

Страница 19: ...l nea de un circuito normal Para realizar el cableado del rel en el circuito de control 1 Conecte un cable de 120 o 277 voltios y 20 amperios como m ximo desconecte el disyuntor en el bloque de termin...

Страница 20: ...20 amperios como m ximo 2 Los bloques de terminales del rel tienen un l mite m ximo de cable 6 AWG 3 Los rel s de dos polos ocupan dos ranuras del rel en el recinto 4 Los rel s de dos poleas vienen en...

Страница 21: ...lizar todo el cableado de entrada antes de aplicar energ a a la tarjeta l gica Verifique que no existan cortocircuitos a la conexi n a tierra de CA antes de conectar los dispositivos de entrada Sin im...

Страница 22: ...comunicaci n que requieran asistencia mediante el proceso de resoluci n de problemas podr haber cargos adicionales por el servicio de soporte Los interruptores digitales se deben conectar entre s con...

Страница 23: ...es de reconfiguraci n disponibles en el sistema LiteKeeper 8 un control de reconfiguraci n simple y uno de eliminaci n Control de reconfiguraci n simple El control de reconfiguraci n simple reinicia e...

Страница 24: ...OFF H 1 ON C 0 D 5 8 LIGHTING CONTROL 12 OO O1 O1 0 8 2 4 7 OUTPUTS RELAY 6 5 4 3 8 7 1 6 B 9 C 3 A OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C Dia...

Отзывы: