6 Implemented EtherNet/IP objects
6.2 Manufacturer-specific object classes
66
SmartWire-DT Gateway EU5C-SWD-EIP-MODTCP
08/17 MN120003Z EN
www.eaton.com
Gateway status
Table 15:
Gateway status; possible values of instance attribute 101, gateway object 0x64
??Heribert: Something's not right here
SmartWire-DT project parameters
Table 16:
SmartWire-DT device parameters; possible values of instance attribute 107,
gateway object 0x64
&Value
Description
0x0000
no error
0x0001
FAILSAFE: no SmartWire-DT communication
0x0002
no project configuration present
0x0004
no target configuration present
0x0040
Renew Target Configuration
0x007F
SmartWire-DT initialization
0x0080
Wiring test active
0x0081
Error when comparing the target configuration and the actual
configuration
0x0082
Error when comparing the project configuration and the target
configuration
BIT
Name
&Valu
e
Value / Description
0
SWD Compatibility
0
Using the M22-NOP universal module is not permitted
1
The M22-NOP universal module can be used as a substi-
tute for a planned module
1
SWD Optional Modules
0
0=Default setting
The device parameter on each SWD module is used to
define whether the module is optional.
1
All SWD modules are optional.
The SWD line can be run with any number of failed SWD
modules.
Data will be transferred to the field bus master.
The setting in the SWD modules
Device parameters of SWD modules”, page 93, will have
no effect.
3 - 15
reserved