2 Installation
2.1 Setting the gateway's field bus address
SmartWire-DT Gateway EU5C-SWD-EIP-MODTCP
08/17 MN120003Z EN
www.eaton.com
15
•
Dynamic address allocation: The address assigned by the DHCP server
is reserved only for a specific period of time. Once this time elapses, or if
a client "explicitly" releases the address during this period, the address is
re-assigned.
•
Manual address allocation: A field bus administrator assigns the IP
address. In this case, DHCP is only used to transmit the assigned
address to the client.
Address setting BOOTP server
An address is acquired from a BOOTP server on the field bus when the gate-
way is put into operation. To activate the "BOOTP-Server" operating mode,
set dip switches 2 and 9 to "ON".
The dip switches 1, 3 and 4 are set to OFF .
The BOOTP server will deliver the IP address, the subnet mask, and the
default gateway address.
Address setting PGM
"PGM" refers to a method used to obtain addresses from the gateway's non-
volatile memory.
The IP address, the subnet mask, and the default gateway address are
entered under the "Ethernet parameters" tab when creating a project in the
SWD-Assist planning program. After the project is downloaded using the
SWD-Assist program, the values entered are transferred to the gateway,
where they are stored in non-volatile memory. Once the project is down-
loaded, the corresponding addresses will take effect immediately.
Figure 4:
Adjusting Ethernet parameters with the SWD assist planning program
DIP Switch
1
2
3
4
5
6
7
8
9
0
Description
2
0
2
1
2
2
2
3
2
4
2
5
2
6
2
7
MODE
OFF
ON
OFF
OFF
X
X
X
X
ON
X
Used to adjust the IP
address via a BOOTP
server
1) X means that the position of the corresponding dip switch will be ignored.