Settings
Contextual help of the web interface – 92
•
•
•
SNMP monitoring Battery status, power status, events, and traps are monitored using third-party SNMP managers.
To query SNMP data, you do not need to add SNMP Managers to the Notified Application page.
To set-up SNMP managers:
Configure the IP address.
Select SNMP v1 or v1 and v3.
Compile the MIB you selected to be monitored by the SNMP manager.
List of supported MIBs:
xUPS MIB | Standard IETF UPS MIB (RFC 1628) | Sensor MIB
Press the Supported MIBs button to download the MIBs.
3.7.5.1.1 Settings
This screen allows an administrator to configure SNMP settings for computers that use the MIB to request information from the
Network Module.
Default ports for SNMP are 161 (SNMP v1 and v3, set/get) and 162 (traps). These ports can be changed on the settings screen for
additional security.
To configure the SNMP settings:
a Enable the SNMP agent
In addition to this also v1 and/or v3 must be enabled, along with appropriate communities and activated user accounts to allow
SNMP communication.
Press Save after modifications.
Содержание eNMC2
Страница 1: ...PDU Network Module eNMC2 User s Guide English 10 09 2023...
Страница 2: ......
Страница 25: ...Home Contextual help of the web interface 25 3 2 2 1 3 Battery mode 3 2 2 1 4 Off mode...
Страница 27: ...Home Contextual help of the web interface 27 3 2 2 2 3 Battery mode 3 2 2 2 4 Off mode...
Страница 29: ...Home Contextual help of the web interface 29 3 2 2 3 2 Bypass mode 3 2 2 3 3 Battery mode...
Страница 30: ...Home Contextual help of the web interface 30 3 2 2 3 4 HE mode ESS mode 3 2 2 3 5 Maintenance bypass mode...
Страница 50: ...Protection Contextual help of the web interface 50 Example 2 Immediate OFF Example 4 Custom...
Страница 51: ...Protection Contextual help of the web interface 51 Settings 1 Settings 2...
Страница 224: ...Acronyms and abbreviations Information 224...
Страница 231: ......