List of event codes
Information – 193
10A
Warning
Input AC unbalanced
End of input AC unbalanced
-
200
Warning
Bypass phase out range
Bypass phase in range
-
201
Warning
Bypass not available
Bypass available
Service required
202
Warning
Bypass thermal overload
Bypass thermal OK
Reduce output load
203
Warning
Bypass temperature alarm
Bypass temperature OK
Check air conditioner
204
Warning
Bypass breaker open
Bypass breaker closed
-
205
Warning
Bypass mode
No more on bypass
-
206
Warning
Bypass frequency out of range
Bypass frequency in range
-
209
Warning
Bypass voltage out of range
Bypass voltage in range
-
20A
Warning
Bypass AC over voltage
End of bypass AC over voltage
-
20B
Warning
Bypass AC under voltage
End of bypass AC under voltage
-
20C
Warning
Bypass bad wiring
Bypass wiring OK
Check bypass wiring
300
Warning
DC bus + too high
DC bus + voltage OK
Service required
301
Warning
DC bus - too high
DC bus - voltage OK
Service required
302
Warning
DC bus + too low
DC bus + voltage OK
Service required
303
Warning
DC bus - too low
DC bus - voltage OK
Service required
304
Warning
DC bus unbalanced
DC bus OK
Service required
501
Warning
Charger temperature alarm
Charger temperature OK
Service required
502
Warning
Max charger voltage
Charger voltage OK
Service required
503
Warning
Min charger voltage
Charger voltage OK
Service required
600
Warning
Battery fuse fault
Battery fuse OK
Service required
602
Warning
Battery fuse fault
Battery fuse OK
Service required
604
Warning
Battery low state of charge
Battery state of charge OK
-
605
Warning
Battery temperature alarm
Battery temperature OK
Service required
606
Warning
Battery breaker open
Battery breaker closed
Service required
610
Warning
Battery low voltage
Battery voltage OK
Check battery
613
Warning
Battery voltage too high
Battery voltage OK
Check battery
616
Warning
Battery voltage unbalanced
Battery voltage OK
Check battery
61C
Warning
Communication with battery lost
Communication with battery
recovered
Check battery
61E
Warning
At least one breaker in battery is
open
All battery breakers are closed
Check battery
Содержание eNMC2
Страница 1: ...PDU Network Module eNMC2 User s Guide English 10 09 2023...
Страница 2: ......
Страница 25: ...Home Contextual help of the web interface 25 3 2 2 1 3 Battery mode 3 2 2 1 4 Off mode...
Страница 27: ...Home Contextual help of the web interface 27 3 2 2 2 3 Battery mode 3 2 2 2 4 Off mode...
Страница 29: ...Home Contextual help of the web interface 29 3 2 2 3 2 Bypass mode 3 2 2 3 3 Battery mode...
Страница 30: ...Home Contextual help of the web interface 30 3 2 2 3 4 HE mode ESS mode 3 2 2 3 5 Maintenance bypass mode...
Страница 50: ...Protection Contextual help of the web interface 50 Example 2 Immediate OFF Example 4 Custom...
Страница 51: ...Protection Contextual help of the web interface 51 Settings 1 Settings 2...
Страница 224: ...Acronyms and abbreviations Information 224...
Страница 231: ......