Using the EMP for temperature compensated battery charging
Servicing the EMP – 171
•
6.2 Using the EMP for temperature compensated battery charging
This section applies only to UPS that provides temperature compensated battery charging option.
6.2.1 Addressing the EMP
Set the address 31 to the sensor dedicated to the battery room temperature:
Set all the Modbus address switches to 1 to set the EMP to the address 31 as indicated on the picture below:
6.2.2 Commissioning the EMP
Refer to the section
Contextual help>>>Environment>>>Commissioning/Status
6.2.3 Enabling temperature compensated battery charging in the UPS
To enable the temperature compensated battery charging, refer to the UPS user manual.
Address must be defined before EMP power-up; otherwise, the changes will not be applied.
Do not set Modbus address to 0; otherwise, the EMP will not be detected.
Define a unique address for all the EMPs in the daisy-chain.
Set the RS485 termination (TER) to 1 on the last EMP of the daisy chain. On other EMPs this should be set to 0.
The temperature compensated battery charging feature needs to be enabled in the UPS.
Содержание eNMC2
Страница 1: ...PDU Network Module eNMC2 User s Guide English 10 09 2023...
Страница 2: ......
Страница 25: ...Home Contextual help of the web interface 25 3 2 2 1 3 Battery mode 3 2 2 1 4 Off mode...
Страница 27: ...Home Contextual help of the web interface 27 3 2 2 2 3 Battery mode 3 2 2 2 4 Off mode...
Страница 29: ...Home Contextual help of the web interface 29 3 2 2 3 2 Bypass mode 3 2 2 3 3 Battery mode...
Страница 30: ...Home Contextual help of the web interface 30 3 2 2 3 4 HE mode ESS mode 3 2 2 3 5 Maintenance bypass mode...
Страница 50: ...Protection Contextual help of the web interface 50 Example 2 Immediate OFF Example 4 Custom...
Страница 51: ...Protection Contextual help of the web interface 51 Settings 1 Settings 2...
Страница 224: ...Acronyms and abbreviations Information 224...
Страница 231: ......