
Protection
Contextual help of the web interface – 48
•
•
•
3.5.3.1 Shutdown on power outage criteria
Shutdown criteria are set per power source (outlet groups) if they are present in the UPS.
3.5.3.1.1 Shutdown criteria selection
The available criteria for shutdown are listed below:
a Maximize availability (default)
To end the shutdown sequence 30s before the end of backup time.
b Immediate OFF
To initiate the shutdown sequence when on battery for 10 seconds.
c Custom
Several conditions can be set to define shutdown criteria:
To initiate the shutdown sequence when on battery for 10 seconds.
To initiate the sequence when the battery reaches the set capacity in (%)
To initiate or end the shutdown sequence after the set time in (s) before the end of backup time.
When there are several conditions to start the shutdown sequence, the shutdown sequence will start as soon as one of the
condition is reached.
By default, shutdown criterias are set to Maximize availability.
Содержание eNMC2
Страница 1: ...PDU Network Module eNMC2 User s Guide English 10 09 2023...
Страница 2: ......
Страница 25: ...Home Contextual help of the web interface 25 3 2 2 1 3 Battery mode 3 2 2 1 4 Off mode...
Страница 27: ...Home Contextual help of the web interface 27 3 2 2 2 3 Battery mode 3 2 2 2 4 Off mode...
Страница 29: ...Home Contextual help of the web interface 29 3 2 2 3 2 Bypass mode 3 2 2 3 3 Battery mode...
Страница 30: ...Home Contextual help of the web interface 30 3 2 2 3 4 HE mode ESS mode 3 2 2 3 5 Maintenance bypass mode...
Страница 50: ...Protection Contextual help of the web interface 50 Example 2 Immediate OFF Example 4 Custom...
Страница 51: ...Protection Contextual help of the web interface 51 Settings 1 Settings 2...
Страница 224: ...Acronyms and abbreviations Information 224...
Страница 231: ......