3 Communication via SmartWire-DT (SWD)
3.4 Input and output data
EMS2…-SWD Electronic motor starter
10/19 MN120008EN
www.eaton.com
29
Object 4 [Index 4]
Byte 0: Motor current – phase L1 in amps
Byte 1: Motor current – phase L2 in amps
Byte 2: Motor current – phase L3 in amps
Bit
7
6
5
4
3
2
1
0
Configura-
tion
I-ABS
(MSB)
I-ABS
I-ABS
I-ABS
I-ABS
I-ABS
I-ABS
I-ABS
(LSB)
Bit
7
6
5
4
3
2
1
0
Configura-
tion
I-ABS
(MSB)
I-ABS
I-ABS
I-ABS
I-ABS
I-ABS
I-ABS
I-ABS
(LSB)
Bit
7
6
5
4
3
2
1
0
Configura-
tion
I-ABS
(MSB)
I-ABS
I-ABS
I-ABS
I-ABS
I-ABS
I-ABS
I-ABS
(LSB)
Byte
Bit
Designation
Meaning
0, 1, 2
0, 1, ... ,7
I-ABS
Motor current in amps in the three phases:
Byte 0: Phase L1
Byte 1: Phase L2
Byte 2: Phase L3
Value range: 0 - 255 % I
e
(100 %
≙
3 A or 9 A, depending on type)