3 Communication via SmartWire-DT (SWD)
3.1 Commissioning EMS2-…-SWD motor starters
EMS2…-SWD Electronic motor starter
10/19 MN120008EN
www.eaton.com
19
3 Communication via SmartWire-DT (SWD)
3.1 Commissioning EMS2-…-SWD motor starters
EMS2-…-SWD motor starters are supplied with voltage via the SWD flat
ribbon cable.
A distinction is made between two different supply voltages:
•
The control voltage U
S
(24 V) to supply the electronics in the devices
•
The supply voltage U
SWD
(15 V) for the communications
When the external control voltage is connected, all the LEDs on the front of
the device light up for a short period of time. After this, the
PWR
(green) LED
remains on.
When the supply voltage U
SWD
is first connected, the
SWD
LED flashes
every 1 -second-. The electronic motor starter is now ready for commission-
ing. The automatic addressing of all modules in the SmartWire-DT line is
performed via the gateway (actuation of the configuration pushbutton on the
gateway) during commissioning.
The
SWD
LED flashes during the addressing process.
The LED changes to a static green after the addressing process.
3.2 Replacing EMS2-…-SWD motor starters
→
With types EMS2-…-24VDC, parameterizing the rated current
must be completed by pressing the “Reset/Set” button in order
for the set current to be applied.
With types EMS2-…-SWD, the current is set by the PLC program
or the SWD Assist software.
→
REPLACING MOTOR STARTERS EMS2-…-SWD
A motor starter must only be replaced after the entire
SmartWire-DT system has been switched off.
In doing so, the order of the SWD modules must not be
changed.
After replacing a motor starter and reconnecting the voltage,
the configuration button on the gateway must be pressed.
This assigns the replaced motor starter with an address.