3 Communication via SmartWire-DT (SWD)
3.4 Input and output data
EMS2…-SWD Electronic motor starter
10/19 MN120008EN
www.eaton.com
23
Byte 1: Set value of the motor protection, trip indication
Bit
7
6
5
4
3
2
1
0
Configura-
tion
ACKR
TRIPP
(MSB)
TRIPP
TRIPP
(LSB)
Ir
(MSB)
Ir
Ir
Ir
(LSB)
Bit
Designation
Meaning
0, 1, 2, 3
Ir
Set value of the internal motor protection
4, 5, 6
TRIPP
Cause of a possible error
7
ACKR
0: There is no overload present.
1: There is overload present. The message must be acknowledged.
Bit
Setting I
n
in A
Bit 3
Bit 2
Bit 1
Bit 0 I
e
= 3 A
I
e
= 9 A
0
0
0
0
0,18
1,5
0
0
0
1
0,3
1,0
0
0
1
0
0,44
2,5
0
0
1
1
0,6
3,0
0
1
0
0
0,68
3,5
0
1
0
1
0,88
4,0
0
1
1
0
1,0
4,5
0
1
1
1
1,1
5,0
1
0
0
0
1,2
5,5
1
0
0
1
1,5
6,0
1
0
1
0
1,6
6,5
1
0
1
1
1,9
7,0
1
1
0
0
2,1
7,5
1
1
0
1
2,4
8,0
1
1
1
0
2,7
8,5
1
1
1
1
3,0
9,0
Bit 6
Bit 5
Bit 4 Ursache
0
0
0
not used
0
0
1
overload
0
1
0
instantaneous trip
0
1
1
phase imbalance
1
0
0
phase failure
1
0
1
obstruction
1
1
0
not used
1
1
1
not used
Содержание EMS2 SWD Series
Страница 1: ...Manual EMS2 SWD Electronic motor starters with SWD 10 19 MN120008EN ...
Страница 4: ......
Страница 58: ...7 Technical data 54 EMS2 SWD Electronic motor starter 10 19 MN120008EN www eaton com ...
Страница 60: ...8 Dimensions 56 EMS2 SWD Electronic motor starter 10 19 MN120008EN www eaton com ...