3 Plug-in motor starter ROSF for mounting on an adapter
3.2 Layout of devices with adapter EMS2-XTH
EMS2… Electronic motor starter
10/19 MN034003EN
www.eaton.com
23
Example
A motor with the values shown below is to be operated with an EMS2 elec-
tronic motor starter.
Questions:
•
Is operation possible?
•
How should the motor starter be mounted?
Checks:
Step 1:
Check to see if the motor starter is suitable for the maximum current (56 A).
I
max
= I
Mot
x startup factor = 4,7 A x 8.5 = 39.95 A < 56 A
Step 2:
Which motor current is permissible at an ambient temperature of 55 °C?
(
•
directly linked: 3 A < 4.7 A
→
not permissible!
•
at a 20 mm distance: 6.7 A > 4.7 A
→
permissible!
Conclusion:
The motor starter EMS2 can be used for this application; it must, however,
be mounted with at least 20 mm distance between the next device.
Motor:
Power:
P
Mot
= 2.2 kW
Rated operational current I
e
at 400 V:
I
Mot
= 4.7 A
Startup factor I
max
/ I
Mot
:
8.5
Control panel
temperature:
55 °C