7 Technical data
EMS2… Electronic motor starter
10/19 MN034003EN
www.eaton.com
45
7 Technical data
Size/feature
EMS2-…-24VDC
EMS2-…-230VAC
Standards
For EMS2-D(R)O-… devices without safety
function:
IEC/EN 60947-1
IEC/EN 60947-4-2
For EMS2-D(R)OS(F)-… devices
with safety function:
IEC/EN 60947-1
IEC/EN 60947-4-2
IEC 61508
ISO 13849
For EMS2-D(R)O-… devices without safety
function:
IEC/EN 60947-1
IEC/EN 60947-4-2
Ambient conditions and mounting
Ambient temperature during operation
For devices
without
safety function:
-25°C - +70°C
Condensation not permissible – prevent with
suitable measures! Observe derating!
For devices
with
safety function:
-25 °C - +55 °C (without derating for single
device)
-25 °C - +70 °C (with derating)
Condensation not permissible – prevent with
suitable measures! Observe derating!
-25 °C - +70 °C
Condensation not permissible – prevent with
suitable measures! Observe derating!
Storage temperature, permissible
-40°C - + 80°C
-40°C - + 80°C
Degree of protection
IP20
IP20
Degree of pollution
2
2
Dimensions
section 8, “Dimensions”, page 51
section 8, “Dimensions”, page 51
Mounting
on 35-mm top-hat rail according to
IEC/EN 60715
on 35-mm top-hat rail according to
IEC/EN 60715
Mounting position
Vertical, motor feeder on bottom
Vertical, motor feeder on bottom
EMC
Emitted interference is cable related:
EN 55011, class A
Emitted interference is radiated:
EN 61000-6-3, class A
This is a product for environment A.
In a domestic environment, this device may
cause radio interference, in which case the user
may be required to take adequate measures.
Emitted interference is cable related:
EN 55011, class A
Emitted interference is radiated:
EN 61000-6-3, class A
This is a product for environment A.
In a domestic environment, this device may
cause radio interference, in which case the user
may be required to take adequate measures.